Outdoor Knight XL Installation & Operation Manual
9 Maintenance
Maintenance and annual startup
Table 9A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
| General: |
|
|
| |
| • Address reported problems | ||||
| • Inspect interior; clean and vacuum if | ||||
| necessary; |
|
| ||
| • Clean condensate trap and fill with fresh | ||||
| water |
|
|
| |
| • Check for leaks (water, gas, flue, | ||||
| condensate) |
|
| ||
| • Verify flue and air passage ways in good | ||||
| condition and sealed tight | ||||
| • Check | system | water | pressure/system | |
UP | piping/expansion tank |
| |||
• Check control settings |
| ||||
- |
|
|
|
| |
START | • Check | ignition | and | flame sense | |
| |||||
| electrodes (sand off any deposits; clean | ||||
| and reposition) |
|
| ||
ANNUAL | • Check wiring and connections | ||||
• Perform | |||||
| |||||
| verification per Section 7. | ||||
| • Flame inspection (stable, uniform) | ||||
| • Flame signal (at least 10 microamps at | ||||
| high fire) |
|
| ||
| • Clean the heat exchanger if flue temperature | ||||
| is more than 54°F (30°C) above return water | ||||
| temperature. |
|
|
If combustion or performance indicate need:
•Clean heat exchanger
•Remove and clean burner using compressed air only
•Clean the blower wheel
Owner maintenance
(see the Outdoor Knight XL User’s Information
Manual for instructions)
Daily | • Check boiler area | |
• Check pressure/temperature | ||
| ||
| gauge | |
|
| |
| • Check air and vent termination | |
Monthly | screens | |
| ||
| • Check relief valve | |
| • Check condensate drain system | |
|
| |
| • Test low water cutoff (if used) | |
Periodically | • Reset button (low water cutoff) | |
| ||
|
| |
Every | • Check boiler piping (gas and | |
water) for leaks | ||
6 months | • Operate relief valve | |
| ||
|
| |
End | • Shut boiler down (unless boiler | |
of season | ||
used for domestic hot water) | ||
months | ||
| ||
|
|
49