FIG. 25 Air Inlet Cap for Sidewall Termination

The sidewall combustion air inlet cap MUST NOT be installed above the sidewall flue outlet if it is located within a 10 foot (3.05 m) radius of the flue outlet.

The sidewall combustion air inlet cap must not be installed closer than 10 feet (3.05 m) from an inside corner of an L-shaped structure.

The sidewall combustion air cap assembly used MUST adequately protect the combustion air inlet from wind and weather.

The sidewall combustion air inlet cap and flue gas outlet MUST be located on the same sidewall surface and in the same pressure zone.

Combustion air supplied from outdoors must be free of contaminants (see Combustion and Ventilation Air). To prevent recirculation of flue products into the combustion air inlet, follow all instructions in this section.

Multiple Horizontal Direct Vent Installations

FLUE OUTLETS

3' HORIZONTALLY

1' BELOW FLUE

AIR INLET CAP

FIG. 26 Multiple Horizontal Direct Vent Caps Installed on a Sidewall

The combustion air inlet caps for multiple appliance installations must maintain the same minimum clearance from the closest vent cap installed within a 10 foot (3.05 m) radius of the point of flue gas termination as specified in single appliance installations. Multiple flue outlet caps may be installed side by side and multiple air inlet caps may be installed side by side but the minimum clearance of 3 feet (0.91 m) horizontal radius and 12 inches (0.30 m) below the closest flue outlet to the air inlet cap must be maintained. All clearance and installation requirements in this section and the applicable portions of the general Category IV venting section must be maintained on multiple appliance installations.

INTELLI-VENT SYSTEMS

An Intelli-Vent system is a Category IV flue installed with a separate combustion air pipe to the outdoors. The Intelli-Vent system terminates the flue and the combustion air inlet pipe in different pressure zones. The Intelli-Vent system may terminate the flue and combustion air in any one of three configurations.

These are:

(1)

The

flue

on

the

roof

top

and

combustion

air intake

 

on the sidewall;

 

 

 

 

 

 

(2)

The

flue

on

the

sidewall

and

combustion

air

from

 

the rooftop;

 

 

 

 

 

 

 

(3)

The

flue

on

the

sidewall and the combustion air on

 

a sidewall other

than

the

sidewall where

the

flue

 

is located.

 

 

 

 

 

 

 

 

All appliances are shipped from the factory equipped for Category IV venting system. The optional Intelli-Vent systems require the installation of specific venting materials that are purchased locally. Sidewall termination caps for flue products and combustion air must be purchased from the manufacturer. The sidewall caps for combustion air and flue products are available as vent kits. The following is a detailed explanation of the installation requirements for each venting system, components used and part numbers of vent kits for each model.

Follow all requirements in the General Category IV Venting sections for proper installation and of venting flue products to the outdoors with either a rooftop or a sidewall termination. All other general installation requirements must be followed.

The Intelli-Vent System requires the installation of an additional pipe to supply combustion air from outdoors directly to the appliance. The air inlet pipe must use one of the specified materials.

18

Image 18
Contents Warranty Special Instructions To OwnerIFB/IFW-i&s-05 Table of Contents What to do if YOU Smell GAS Checking EquipmentDo not Owner WarningTable a Installation Procedure Location of UnitRecommended Service Clearances Clearances from Combustible ConstructionCombustion Air Direct from Outside AIR Supply to Mechanical Room Table BMinimum Recommended Combustion 500 in2 3226 cm2 667 in2 4303 cm2 000 in2 12,903 cm2Construction AIR Filter Construction Air FilterTable D Construction AIR Filter Kits Table CVenting Category IV Flue Pipe SizesCategory IV Flue Pipe Materials Category IV Positive Pressure Venting SystemCategory IV Venting Venting Guidelines for a Category IV VentDrain Tee Installation General Category IV Vent Termination ClearancesExceed a maximum of 100 equivalent feet 30.5 m in length Masonry Chimney Installations Vertical Venting TerminationsSidewall Vent Cap Kits Sidewall Venting TerminationsTable E Sidewall VentLocation of a Sidewall Vent Termination Direct Vent INTELLI-VENT SystemsAir Inlet Table FDirect Vent and Intelli-Vent Flue Air Inlet Pipe Sizes Length of Air Inlet PipeVertical Direct Vent Systems Combined Combustion Air Inlet PointsMultiple Vertical Direct Vent Installations Horizontal Direct VentSidewall Combustion AIR Inlet Table GLocation of a Sidewall Air Inlet Cap Multiple Horizontal Direct Vent Installations These areMaximum Length of an Intelli-Vent System Table HCombined Air Inlet Points Air Inlet Sidewall Input Flue Pipe Btu/hr SizeBtu/hr Size Cap Kit Horizontal INTELLI-VENT with Vertical Combustion AIRAir Inlet Sidewall Input Flue Pipe 500,000 SVK3026Vertical Combustion Horizontal INTELLI-VENT AIR Inlet Location of a Rooftop Air Inlet CapTable J GAS Connection GAS Supply GAS Pressure TestTable K Table LTable M Recommended Gas Pipe Size Single Appliance InstallationsMultiple Appliance Installations Gas Pipe Size Chart Table NGAS Piping GAS Manifold Pressure AdjustmentInstall Piping to Control Checking GAS Supply PressureChecking Manifold GAS Pressure Water Connections Water ConnectionsSecondary Heat Exchanger Primary Heat Exchanger Inlet and Outlet ConnectionsMinimum Pipe Size Requirements Integral Bypass Bypass Valve SynchronizationOptional Intermittent Pump Operation Bypass Piping AssemblyIntegral Circulator Bypass Initial Set-up of Maximum Water FlowTable P Minimum Water TemperaturesBtu/hr Input Temperature Rise Bypass OperationLOW Water Cutoff Water Flow SwitchTable Q GAS Train and ControlsRelief Valve Diaphragm GAS Valve Ratio GAS ValveJacket Assembly Electrical ConnectionsAccess to Components and Controls Front Control Panel LocationsVariable Frequency Drive Transformer and Relay LocationsHigh GAS Pressure Switch LOW GAS Pressure Switch Optional LOW AIR Pressure SwitchExcel Be used as a diagnostic indicator Table S Temperature AdjustmentDefault Values Pre-programmed in the Excel To Activate the Manual OverrideTable T Display Default Values Password FunctionConfiguring Command Display Accessing the SIX Changeable Points from Command DisplaySet Point Temp Calculated Set PointTotal Run Time Sequencing TypeCommand Display Data Screen Status Point Operational Modes Status PointsTable U Hot Surface Igniter OnOutdoor Reset Function Selections Optional on Heating Boilers OnlyMultiple Appliance Installations Efficiency Optimized with Time EqualizationSingly Terminated FTT Network Bus Topology Specifications Interfacing Multiple AppliancesTable W Wire Termination for E-Bus Connection Additional Components Used to Interface Multiple AppliancesHigh Water Temperature Limit Control Typical Building Management System DiagramService Parts HOT Surface Ignition SystemIgnition Module Lockout Functions Ignition and Control Timings Diagnostic Status IndicationTable Y Table ZBurner OPERATION/DIAGNOSTIC LIGHTS, Resets and SwitchesIndicator Table AACombustion AIR Blower Combustion Air Blower and Transition ChamberTable BB Condensate ManagementSystem Optional Condensate Drain Location On RearCondensate Testing Condensate Trap InstallationReplenishing the Neutralizer Install Condensate Trap Lighting InstructionsTo Turn OFF GAS to Appliance Ignition System CheckoutSequence of Operation Heat Transfer ProcessMaintenance End of SequenceBurner Removal and Cleaning Burner MaintenanceBurner Cleaning Procedure Location of Primary Heat ExchangerSecondary Heat Exchanger Inspection Lubrication Freeze Protection Water Treatment Heating Boiler InstallationsFreeze Protection for a Heating Boiler System If Required Water Connections Heating Boilers onlyBoiler Circulator Pump Limitations Primary Loop Circulator Pump SpecificationsPiping Lengths Circulator Pump OperationMinimum Boiler Water Temperatures PRIMARY/SECONDARY Boiler PipingMaximum Flow for Heating Boiler Boiler Temperature Rise Chart Table DDTable CC Btu/hr Input Maximum FlowTEMPERATURE/PRESSURE Gauge Typical Heating Boiler InstallationsPlacing the Boiler Operation Installation with a Chilled Water System Boiler Operating Temperature ControlBoiler Operation Water Velocity Control Typical Water Heater Piping with Storage TankTable EE Table FFMaximum Flow Rate Btu/hr Input Water Chemistry Piping Multiple Unit Installations Single Water Heater Piping with Two Storage TanksHeat Exchanger Table GGPump Operation Common ManifoldThermostat Settings Table HHOptional Relief Valve Thermal ExpansionCathodic Protection Ladder Diagram PWM Wiring Diagram
Related manuals
Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 56 pages 36.01 Kb Manual 56 pages 40.75 Kb

000, 000 through 2, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.