Lochinvar 1, 000 through 2 warranty Masonry Chimney Installations, Vertical Venting Terminations

Page 11

the tee. The drain tubing must have a trap provided by a 4" (10.2 cm)-diameter circular trap loop in the drain tubing. Prime the trap loop by pouring a small quantity of water into the drain hose before assembly to the vent. Secure the trap loop in position with nylon wire ties. Use caution not to collapse or restrict the condensate drain line with the nylon wire ties. The condensate drain must be routed to the condensate neutralization system or a suitable drain for disposal of condensate that may occur in the Category IV vent system. Refer to the condensate drain installation instructions as supplied by the manufacturer of the vent material. Ensure that the drain from the condensate tee is not exposed to freezing temperatures. See “Freeze Protection” for more information.

MASONRY CHIMNEY

INSTALLATIONS

A standard masonry chimney must NOT be used to vent the products of combustion from the flue of a Category IV, positive pressure appliance. If a masonry chimney is to be used, the chimney MUST use a sealed, metallic, corrosion resistant liner system to vent flue products from this high efficiency appliance. Sealed, metallic, corrosion resistant liner systems (single wall, double-wall, or flexible or rigid metallic liners) must be rated for use with a high efficiency Category IV, positive pressure vent system. Corrosion resistant chimney liner systems are typically made from a high grade of corrosion resistant stainless steel such as AL 29-4C. The corrosion resistant liner must be properly sized and fully sealed throughout the entire length if the flue is contained within the masonry chimney. Both the top and the bottom of the masonry chimney must be capped and sealed to provide a dead air space around the sealed corrosion resistant metallic liner. Consult with local code officials to determine code requirements or the advisability of using a masonry chimney with a sealed corrosion resistant liner system.

CAUTION￿

Venting of a high efficiency Category IV appliance into a masonry chimney without a sealed stainless steel liner can result in operational and safety problems. Any breaks, leaks or damage to the masonry flue/tile will allow spillage of the positive pressure flue products from the chimney. These flue products can easily escape into an occupied living space causing a health hazard. If there is any doubt about the condition of a masonry chimney, or its acceptability for use after insertion of a corrosion resistant liner system, consult with local code officials.

VERTICAL VENTING

TERMINATIONS

Follow all General Category IV Vent Termination Clearances.

 

10' OR LESS

 

2' MIN

RIDGE

3' MIN

 

 

CHIMNEY

FIG. 13 Vent Termination from Peaked Roof - 10 Feet or Less from Ridge

MORE THAN 10'

10'

RIDGE

2' MIN

3' MIN

CHIMNEY

FIG. 14 Vent Termination from Peaked Roof - 10 Feet or More from Ridge

The vent terminal should be vertical and exhaust outside the build- ing at least 2 feet (0.61 m) above the highest point of the roof within a 10 foot (3.05 m) radius of the termination.

The vertical termination must be a minimum of 3 feet (0.91 m) above the point of exit.

11

Image 11
Contents IFB/IFW-i&s-05 WarrantySpecial Instructions To Owner Table of Contents Owner Warning Checking EquipmentDo not What to do if YOU Smell GASClearances from Combustible Construction Installation Procedure Location of UnitRecommended Service Clearances Table aCombustion Air Direct from Outside 500 in2 3226 cm2 667 in2 4303 cm2 000 in2 12,903 cm2 Table BMinimum Recommended Combustion AIR Supply to Mechanical RoomConstruction Air Filter Construction AIR FilterCategory IV Flue Pipe Sizes Construction AIR Filter Kits Table CVenting Table DVenting Guidelines for a Category IV Vent Category IV Positive Pressure Venting SystemCategory IV Venting Category IV Flue Pipe MaterialsExceed a maximum of 100 equivalent feet 30.5 m in length Drain Tee InstallationGeneral Category IV Vent Termination Clearances Vertical Venting Terminations Masonry Chimney InstallationsSidewall Vent Sidewall Venting TerminationsTable E Sidewall Vent Cap KitsDirect Vent INTELLI-VENT Systems Location of a Sidewall Vent TerminationLength of Air Inlet Pipe Table FDirect Vent and Intelli-Vent Flue Air Inlet Pipe Sizes Air InletCombined Combustion Air Inlet Points Vertical Direct Vent SystemsHorizontal Direct Vent Multiple Vertical Direct Vent InstallationsLocation of a Sidewall Air Inlet Cap Sidewall Combustion AIR InletTable G These are Multiple Horizontal Direct Vent InstallationsAir Inlet Sidewall Input Flue Pipe Btu/hr Size Table HCombined Air Inlet Points Maximum Length of an Intelli-Vent System500,000 SVK3026 Horizontal INTELLI-VENT with Vertical Combustion AIRAir Inlet Sidewall Input Flue Pipe Btu/hr Size Cap KitLocation of a Rooftop Air Inlet Cap Vertical Combustion Horizontal INTELLI-VENT AIR InletTable J Table L GAS Supply GAS Pressure TestTable K GAS ConnectionTable N Recommended Gas Pipe Size Single Appliance InstallationsMultiple Appliance Installations Gas Pipe Size Chart Table MChecking GAS Supply Pressure GAS Manifold Pressure AdjustmentInstall Piping to Control GAS PipingChecking Manifold GAS Pressure Water Connections Water ConnectionsMinimum Pipe Size Requirements Secondary Heat Exchanger Primary Heat ExchangerInlet and Outlet Connections Bypass Valve Synchronization Integral BypassBypass Initial Set-up of Maximum Water Flow Bypass Piping AssemblyIntegral Circulator Optional Intermittent Pump OperationBypass Operation Minimum Water TemperaturesBtu/hr Input Temperature Rise Table PGAS Train and Controls Water Flow SwitchTable Q LOW Water CutoffDiaphragm GAS Valve Ratio GAS Valve Relief ValveElectrical Connections Jacket AssemblyFront Control Panel Locations Access to Components and ControlsTransformer and Relay Locations Variable Frequency DriveExcel High GAS Pressure Switch LOW GAS Pressure Switch OptionalLOW AIR Pressure Switch Be used as a diagnostic indicator To Activate the Manual Override Temperature AdjustmentDefault Values Pre-programmed in the Excel Table SAccessing the SIX Changeable Points from Command Display Password FunctionConfiguring Command Display Table T Display Default ValuesSequencing Type Calculated Set PointTotal Run Time Set Point TempCommand Display Data Screen Hot Surface Igniter On Status PointsTable U Status Point Operational ModesOptional on Heating Boilers Only Outdoor Reset Function SelectionsEfficiency Optimized with Time Equalization Multiple Appliance InstallationsTable W Singly Terminated FTT Network Bus Topology SpecificationsInterfacing Multiple Appliances Additional Components Used to Interface Multiple Appliances Wire Termination for E-Bus ConnectionTypical Building Management System Diagram High Water Temperature Limit ControlIgnition Module Lockout Functions Service PartsHOT Surface Ignition System Table Z Diagnostic Status IndicationTable Y Ignition and Control TimingsTable AA OPERATION/DIAGNOSTIC LIGHTS, Resets and SwitchesIndicator BurnerCombustion Air Blower and Transition Chamber Combustion AIR BlowerCondensate Drain Location On Rear Condensate ManagementSystem Optional Table BBReplenishing the Neutralizer Condensate TestingCondensate Trap Installation Lighting Instructions Install Condensate TrapIgnition System Checkout To Turn OFF GAS to ApplianceHeat Transfer Process Sequence of OperationEnd of Sequence MaintenanceBurner Maintenance Burner Removal and CleaningLocation of Primary Heat Exchanger Burner Cleaning ProcedureSecondary Heat Exchanger Inspection Lubrication Freeze Protection Water Connections Heating Boilers only Heating Boiler InstallationsFreeze Protection for a Heating Boiler System If Required Water TreatmentCirculator Pump Operation Primary Loop Circulator Pump SpecificationsPiping Lengths Boiler Circulator Pump LimitationsPRIMARY/SECONDARY Boiler Piping Minimum Boiler Water TemperaturesBtu/hr Input Maximum Flow Boiler Temperature Rise Chart Table DDTable CC Maximum Flow for Heating BoilerPlacing the Boiler Operation TEMPERATURE/PRESSURE GaugeTypical Heating Boiler Installations Boiler Operation Installation with a Chilled Water SystemBoiler Operating Temperature Control Typical Water Heater Piping with Storage Tank Water Velocity ControlMaximum Flow Rate Btu/hr Input Table EETable FF Water Chemistry Single Water Heater Piping with Two Storage Tanks Piping Multiple Unit InstallationsCommon Manifold Table GGPump Operation Heat ExchangerTable HH Thermostat SettingsCathodic Protection Optional Relief ValveThermal Expansion Ladder Diagram PWM Wiring Diagram
Related manuals
Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 56 pages 36.01 Kb Manual 56 pages 40.75 Kb

000, 000 through 2, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.