Lochinvar 000 through 2, 1 warranty Lighting Instructions, Install Condensate Trap

Page 55

￿WARNING

Use a level to ensure that the condensate trap is level on its base. Failure to keep the condensate trap level can result in the spillage of flue products from the condensate trap.

Failure to follow this warning could result in product damage or improper operation, personal injury, or death.

NOTE:

Use materials approved by the authority having jurisdiction. In the absence of other authority, PVC and CPVC pipe must comply with ASTM D1785 or D2845. Cement and primer must comply with ASME D2564 or F493. For Canada use CSA or ULC certified PVC or CPVC pipe, fittings, and cement.

13.Slope the condensate line down and away from the appliance into a drain or condensate neutralizing filter. Do not expose the condensate line to freezing temperatures.

NOTE:

The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manner, the blocked drain safety switch will prevent the appliance from firing.

FIG. 73 Install Condensate Trap

LIGHTING INSTRUCTIONS

FOR YOUR SAFETY,

READ BEFORE

OPERATING

WARNING￿

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A.This appliance does not have a pilot. It is equipped with an ignition device which automati- cally lights the burner. Do not try to light the burner by hand.

B.BEFORE OPERATING, smell around the appliance area for gas. Be sure to smell next to the

floor

because

some

gas

is

heavier

than

air and

will

settle

to the

floor.

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbors phone.

Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to turn the gas control handle. Never use tools. If the handle will not turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the boiler. The

possible

damage to

a

flooded appliance can

be extensive

and

present

numerous

safety

hazards.

Any

appliance

that

has been

under

water must be replaced.

55

Image 55
Contents Special Instructions To Owner WarrantyIFB/IFW-i&s-05 Table of Contents Owner Warning Checking EquipmentDo not What to do if YOU Smell GASClearances from Combustible Construction Installation Procedure Location of UnitRecommended Service Clearances Table aCombustion Air Direct from Outside 500 in2 3226 cm2 667 in2 4303 cm2 000 in2 12,903 cm2 Table BMinimum Recommended Combustion AIR Supply to Mechanical RoomConstruction Air Filter Construction AIR FilterCategory IV Flue Pipe Sizes Construction AIR Filter Kits Table CVenting Table DVenting Guidelines for a Category IV Vent Category IV Positive Pressure Venting SystemCategory IV Venting Category IV Flue Pipe MaterialsGeneral Category IV Vent Termination Clearances Drain Tee InstallationExceed a maximum of 100 equivalent feet 30.5 m in length Vertical Venting Terminations Masonry Chimney InstallationsSidewall Vent Sidewall Venting TerminationsTable E Sidewall Vent Cap KitsDirect Vent INTELLI-VENT Systems Location of a Sidewall Vent TerminationLength of Air Inlet Pipe Table FDirect Vent and Intelli-Vent Flue Air Inlet Pipe Sizes Air InletCombined Combustion Air Inlet Points Vertical Direct Vent SystemsHorizontal Direct Vent Multiple Vertical Direct Vent InstallationsTable G Sidewall Combustion AIR InletLocation of a Sidewall Air Inlet Cap These are Multiple Horizontal Direct Vent InstallationsAir Inlet Sidewall Input Flue Pipe Btu/hr Size Table HCombined Air Inlet Points Maximum Length of an Intelli-Vent System500,000 SVK3026 Horizontal INTELLI-VENT with Vertical Combustion AIRAir Inlet Sidewall Input Flue Pipe Btu/hr Size Cap KitLocation of a Rooftop Air Inlet Cap Vertical Combustion Horizontal INTELLI-VENT AIR InletTable J Table L GAS Supply GAS Pressure TestTable K GAS ConnectionTable N Recommended Gas Pipe Size Single Appliance InstallationsMultiple Appliance Installations Gas Pipe Size Chart Table MChecking GAS Supply Pressure GAS Manifold Pressure AdjustmentInstall Piping to Control GAS PipingChecking Manifold GAS Pressure Water Connections Water ConnectionsInlet and Outlet Connections Secondary Heat Exchanger Primary Heat ExchangerMinimum Pipe Size Requirements Bypass Valve Synchronization Integral BypassBypass Initial Set-up of Maximum Water Flow Bypass Piping AssemblyIntegral Circulator Optional Intermittent Pump OperationBypass Operation Minimum Water TemperaturesBtu/hr Input Temperature Rise Table PGAS Train and Controls Water Flow SwitchTable Q LOW Water CutoffDiaphragm GAS Valve Ratio GAS Valve Relief ValveElectrical Connections Jacket AssemblyFront Control Panel Locations Access to Components and ControlsTransformer and Relay Locations Variable Frequency DriveLOW AIR Pressure Switch High GAS Pressure Switch LOW GAS Pressure Switch OptionalExcel Be used as a diagnostic indicator To Activate the Manual Override Temperature AdjustmentDefault Values Pre-programmed in the Excel Table SAccessing the SIX Changeable Points from Command Display Password FunctionConfiguring Command Display Table T Display Default ValuesSequencing Type Calculated Set PointTotal Run Time Set Point TempCommand Display Data Screen Hot Surface Igniter On Status PointsTable U Status Point Operational ModesOptional on Heating Boilers Only Outdoor Reset Function SelectionsEfficiency Optimized with Time Equalization Multiple Appliance InstallationsInterfacing Multiple Appliances Singly Terminated FTT Network Bus Topology SpecificationsTable W Additional Components Used to Interface Multiple Appliances Wire Termination for E-Bus ConnectionTypical Building Management System Diagram High Water Temperature Limit ControlHOT Surface Ignition System Service PartsIgnition Module Lockout Functions Table Z Diagnostic Status IndicationTable Y Ignition and Control TimingsTable AA OPERATION/DIAGNOSTIC LIGHTS, Resets and SwitchesIndicator BurnerCombustion Air Blower and Transition Chamber Combustion AIR BlowerCondensate Drain Location On Rear Condensate ManagementSystem Optional Table BBCondensate Trap Installation Condensate TestingReplenishing the Neutralizer Lighting Instructions Install Condensate TrapIgnition System Checkout To Turn OFF GAS to ApplianceHeat Transfer Process Sequence of OperationEnd of Sequence MaintenanceBurner Maintenance Burner Removal and CleaningLocation of Primary Heat Exchanger Burner Cleaning ProcedureSecondary Heat Exchanger Inspection Lubrication Freeze Protection Water Connections Heating Boilers only Heating Boiler InstallationsFreeze Protection for a Heating Boiler System If Required Water TreatmentCirculator Pump Operation Primary Loop Circulator Pump SpecificationsPiping Lengths Boiler Circulator Pump LimitationsPRIMARY/SECONDARY Boiler Piping Minimum Boiler Water TemperaturesBtu/hr Input Maximum Flow Boiler Temperature Rise Chart Table DDTable CC Maximum Flow for Heating BoilerTypical Heating Boiler Installations TEMPERATURE/PRESSURE GaugePlacing the Boiler Operation Boiler Operating Temperature Control Installation with a Chilled Water SystemBoiler Operation Typical Water Heater Piping with Storage Tank Water Velocity ControlTable FF Table EEMaximum Flow Rate Btu/hr Input Water Chemistry Single Water Heater Piping with Two Storage Tanks Piping Multiple Unit InstallationsCommon Manifold Table GGPump Operation Heat ExchangerTable HH Thermostat SettingsThermal Expansion Optional Relief ValveCathodic Protection Ladder Diagram PWM Wiring Diagram
Related manuals
Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 56 pages 36.01 Kb Manual 56 pages 40.75 Kb

000, 000 through 2, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.