Location of a Sidewall Air Inlet Cap

Installation, location and clearance requirements for the sidewall air inlet cap in an Intelli-Vent application are the same as the installation, location and clearance requirements for the sidewall air inlet cap in the Horizontal Direct Vent section of the venting instructions.

The sidewall combustion air inlet cap and the rooftop flue gas outlet are located in different pressure zones in an Intelli-Vent system.

Combustion air supplied from outdoors must be free of contaminants (see Combustion and Ventilation Air). To prevent recirculation of flue products in to the combustion air inlet, follow all instructions in this section.

Incorrect installation and/or location of the air inlet cap can allow the discharge of flue products to be drawn into the combustion process on the heater. This can result in incomplete combustion and potentially hazardous levels of carbon monoxide in the flue products. This will cause operational problems with the heater and possible spillage of flue products that can cause personal injury, death or property damage.

HORIZONTAL INTELLI-VENT WITH

VERTICAL COMBUSTION AIR

The Intelli-Vent system requires the installation of an additional pipe to supply combustion air from outdoors directly to the appliance.

In cold climates, the use of type “B” double wall vent pipe or an insulated single wall pipe is recommended to prevent moisture in the cool incoming air from condensing and leaking from the inlet pipe.

Termination point for the flue products must follow the clearance requirements in the Horizontal Sidewall Vent Termination section of the Category IV Venting.

CAUTION￿

Appliances that are shut down or will not operate may experience freezing due to convective airflow in the air inlet pipe connected to the appliance.

The flue and air inlet duct sizes for a Horizontal Intelli-Vent Installation with Rooftop Combustion Air Inlet are listed by unit size. The sidewall vent cap must be purchased from the appliance manufacturer as a vent kit.

Intelli-Vent systems are installed with a Category IV flue and a separate combustion air pipe to the outdoors. The Horizontal Intelli-Vent system terminates the flue at the sidewall and air inlet at the rooftop. The flue outlet and combustion air intake terminate in different pressure zones.

12" MIN.

FIG. 29 Horizontal Intelli-Vent Installation - Rooftop Combustion Air Inlet

TABLE - I

 

 

 

 

Air Inlet

 

Sidewall

Input

 

Flue

 

Pipe

 

Vent

Btu/hr

 

Size

 

Size

 

Cap Kit

 

 

 

 

 

 

 

1,500,000

 

6"

 

6"

 

SVK3026

___________

 

___________

 

___________

 

____________

1,700,000

 

7"

 

7"*

 

SVK3027

___________

 

___________

 

___________

 

____________

2,000,000

 

8"

 

8"

 

SVK3028

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Piping from the appliance to the air inlet cap may be either 7" or 8" connecting to an 8" sidewall cap provided in the kit.

Follow all requirements in the General Category IV Venting sections for proper installation and of venting flue products horizontally to the outdoors. All other general installation requirements must be followed.

20

Image 20
Contents IFB/IFW-i&s-05 WarrantySpecial Instructions To Owner Table of Contents Checking Equipment Do notWhat to do if YOU Smell GAS Owner WarningInstallation Procedure Location of Unit Recommended Service ClearancesTable a Clearances from Combustible ConstructionCombustion Air Direct from Outside Table B Minimum Recommended CombustionAIR Supply to Mechanical Room 500 in2 3226 cm2 667 in2 4303 cm2 000 in2 12,903 cm2Construction AIR Filter Construction Air FilterConstruction AIR Filter Kits Table C VentingTable D Category IV Flue Pipe SizesCategory IV Positive Pressure Venting System Category IV VentingCategory IV Flue Pipe Materials Venting Guidelines for a Category IV VentExceed a maximum of 100 equivalent feet 30.5 m in length Drain Tee InstallationGeneral Category IV Vent Termination Clearances Masonry Chimney Installations Vertical Venting TerminationsSidewall Venting Terminations Table ESidewall Vent Cap Kits Sidewall VentLocation of a Sidewall Vent Termination Direct Vent INTELLI-VENT SystemsTable F Direct Vent and Intelli-Vent Flue Air Inlet Pipe SizesAir Inlet Length of Air Inlet PipeVertical Direct Vent Systems Combined Combustion Air Inlet PointsMultiple Vertical Direct Vent Installations Horizontal Direct VentLocation of a Sidewall Air Inlet Cap Sidewall Combustion AIR InletTable G Multiple Horizontal Direct Vent Installations These areTable H Combined Air Inlet PointsMaximum Length of an Intelli-Vent System Air Inlet Sidewall Input Flue Pipe Btu/hr SizeHorizontal INTELLI-VENT with Vertical Combustion AIR Air Inlet Sidewall Input Flue PipeBtu/hr Size Cap Kit 500,000 SVK3026Vertical Combustion Horizontal INTELLI-VENT AIR Inlet Location of a Rooftop Air Inlet CapTable J GAS Supply GAS Pressure Test Table KGAS Connection Table LRecommended Gas Pipe Size Single Appliance Installations Multiple Appliance Installations Gas Pipe Size ChartTable M Table NGAS Manifold Pressure Adjustment Install Piping to ControlGAS Piping Checking GAS Supply PressureChecking Manifold GAS Pressure Water Connections Water ConnectionsMinimum Pipe Size Requirements Secondary Heat Exchanger Primary Heat ExchangerInlet and Outlet Connections Integral Bypass Bypass Valve SynchronizationBypass Piping Assembly Integral CirculatorOptional Intermittent Pump Operation Bypass Initial Set-up of Maximum Water FlowMinimum Water Temperatures Btu/hr Input Temperature RiseTable P Bypass OperationWater Flow Switch Table QLOW Water Cutoff GAS Train and ControlsRelief Valve Diaphragm GAS Valve Ratio GAS ValveJacket Assembly Electrical ConnectionsAccess to Components and Controls Front Control Panel LocationsVariable Frequency Drive Transformer and Relay LocationsExcel High GAS Pressure Switch LOW GAS Pressure Switch OptionalLOW AIR Pressure Switch Be used as a diagnostic indicator Temperature Adjustment Default Values Pre-programmed in the ExcelTable S To Activate the Manual OverridePassword Function Configuring Command DisplayTable T Display Default Values Accessing the SIX Changeable Points from Command DisplayCalculated Set Point Total Run TimeSet Point Temp Sequencing TypeCommand Display Data Screen Status Points Table UStatus Point Operational Modes Hot Surface Igniter OnOutdoor Reset Function Selections Optional on Heating Boilers OnlyMultiple Appliance Installations Efficiency Optimized with Time EqualizationTable W Singly Terminated FTT Network Bus Topology SpecificationsInterfacing Multiple Appliances Wire Termination for E-Bus Connection Additional Components Used to Interface Multiple AppliancesHigh Water Temperature Limit Control Typical Building Management System DiagramIgnition Module Lockout Functions Service PartsHOT Surface Ignition System Diagnostic Status Indication Table YIgnition and Control Timings Table ZOPERATION/DIAGNOSTIC LIGHTS, Resets and Switches IndicatorBurner Table AACombustion AIR Blower Combustion Air Blower and Transition ChamberCondensate Management System OptionalTable BB Condensate Drain Location On RearReplenishing the Neutralizer Condensate TestingCondensate Trap Installation Install Condensate Trap Lighting InstructionsTo Turn OFF GAS to Appliance Ignition System CheckoutSequence of Operation Heat Transfer ProcessMaintenance End of SequenceBurner Removal and Cleaning Burner MaintenanceBurner Cleaning Procedure Location of Primary Heat ExchangerSecondary Heat Exchanger Inspection Lubrication Freeze Protection Heating Boiler Installations Freeze Protection for a Heating Boiler System If RequiredWater Treatment Water Connections Heating Boilers onlyPrimary Loop Circulator Pump Specifications Piping LengthsBoiler Circulator Pump Limitations Circulator Pump OperationMinimum Boiler Water Temperatures PRIMARY/SECONDARY Boiler PipingBoiler Temperature Rise Chart Table DD Table CCMaximum Flow for Heating Boiler Btu/hr Input Maximum FlowPlacing the Boiler Operation TEMPERATURE/PRESSURE GaugeTypical Heating Boiler Installations Boiler Operation Installation with a Chilled Water SystemBoiler Operating Temperature Control Water Velocity Control Typical Water Heater Piping with Storage TankMaximum Flow Rate Btu/hr Input Table EETable FF Water Chemistry Piping Multiple Unit Installations Single Water Heater Piping with Two Storage TanksTable GG Pump OperationHeat Exchanger Common ManifoldThermostat Settings Table HHCathodic Protection Optional Relief ValveThermal Expansion Ladder Diagram PWM Wiring Diagram
Related manuals
Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 56 pages 36.01 Kb Manual 56 pages 40.75 Kb

000, 000 through 2, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.