VIII INDIRECT & TANKLESS WATER HEATER PIPING
INDIRECT WATER HEATER PIPING
All KSZ series boilers are equipped with tappings to permit the connection of a Crown
1)Circulator - Mount the circulator as shown in Figure 12A. The circulator should be located as low and as close to the boiler as practical. Do not install valves, or other devices having a significant pressure drop, between the boiler and the circulator inlet. All piping between the boiler and the circulator inlet should be 1”, regardless of the size of the piping required in the rest of the system. See Figure 17 in Part X for wiring information.
2)“Y” Strainer - Install a “Y” strainer to prevent sediment from accumulating inside the indirect water heater.
3)Check Valve - Prevents gravity circulation through the indirect water heater when the boiler is responding to a call for heat.
4)Boiler Limit Control - Use a SPST
5)Valves and Unions - Install
FIGURE 12a: |