Crown Boiler KSZ075, KSZ150, KSZ125, KSZ200, KSZ175, KSZ120, KSZ065, KSZ090, KSZ100 2526

Page 26

TABLE 3a: BECKETT BURNER CONFIGURATION AND SETUP DATA

BOILER MODEL

KSZ065

KSZ075

KSZ100

KSZ090

KSZ125

KSZ150

KSZ120

KSZ175

KSZ200

 

 

 

 

 

 

 

 

 

 

BURNER MODEL

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AIR TUBE COMBO.

70MMAQ

70MMAQ

70MMAQ

70MMAQ

70MDAQ

70MDAQ

70MLAQ

70MLAQ

70MLAQ

HEAD TYPE

L1

L1

L1

L1

V1

V1

V1

V1

V1

STATIC PLATE

3 3/8

3 3/8

3 3/8

3 3/8

2 3/4

2 3/4

NONE

NONE

NONE

LOW FIRING RATE

BECKETT

BECKETT

NONE

NONE

NONE

NONE

NONE

NONE

NONE

BAFFLE

#3708

#3708

 

 

 

 

 

 

 

INSERTION LENGTH

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

PITCH ANGLE

2

2

2

2

2

2

2

2

2

STANDARD

HAGO

HAGO

HAGO

DEL.

HAGO

HAGO

HAGO

HAGO

HAGO

NOZZLE

0.55/60B

0.65/60B

0.85/60B

0.75/60B

1.00/60B

1.25/60B

0.90/60B

1.35/45B

1.50/45B

ALTERNATE

DEL.

DEL.

DEL.

HAGO

DEL.

DEL.

DEL.

DEL.

DEL.

NOZZLE

0.55/60W

0.65/60W

0.85/60W

0.75/60B

1.00/60B

1.25/60B

0.90/60B

1.35/45B

1.50/45B

PUMP PRESS (psi)

140

140

140

140

140

140

175

175

175

HEAD SETTING

NA

NA

NA

NA

0

0

0

3

4

STARTING:

 

 

 

 

 

 

 

 

 

SHUTTER SETTING

1

10

5

7

10

10

8

6

8

BAND SETTING

1

2

2

0

0.5

6

1

6

4

DRAFT OVER FIRE

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

(in w.c.)

 

 

 

 

 

 

 

 

 

MAX. SMOKE

#1

#1

#1

#1

#1

#1

#1

#1

#1

(bacharach scale)

 

 

 

 

 

 

 

 

 

FLUE CO2 (%)

 

 

 

 

 

 

 

 

 

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

MAX

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

PREPURGE

 

 

15 SECONDS

 

 

 

None

 

IGNITION MODE

 

 

 

INTERUPTED

 

 

 

TABLE 3b: CARLIN BURNER CONFIGURATION AND SETUP DATA

 

KSZ065

KSZ075

KSZ100

KSZ090

KSZ125

KSZ150

KSZ120

KSZ175

KSZ200

 

 

 

 

 

 

 

 

 

 

BURNER MODEL

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-2HP

 

STANDARD

DEL.

HAGO

HAGO

DEL.

DEL.

HAGO

HAGO

DEL.

 

NOZZLE

0.55/70B

0.60/60ES

0.85/60B

0.75/60A

1.00/60A

1.25/60B

1.00/60B

1.50/60A

 

PUMP PRESS (psi)

150

150

150

150

150

150

150

150

 

HEAD BAR

0.50

0.60-0.65

0.85-1.00

0.75

0.85-1.00

1.10-1.25

0.85-1.00

1.50

 

STARTING

 

 

 

 

 

 

 

 

 

BAND SETTING

0.55

0.60

0.75

0.75

1.00-1.10

1.25-1.35

0.90

1.75

 

DRAFT OVER FIRE

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

 

(in w.c.)

 

 

 

 

 

 

 

 

 

 

MAX. SMOKE

#1

#1

#1

#1

#1

#1

#1

#1

 

(bacharach scale)

 

 

 

 

 

 

 

 

 

 

FLUE CO2 (%)

 

 

 

 

 

 

 

 

 

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

 

MAX

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

 

PREPURGE

 

 

 

 

NONE

 

 

 

 

IGNITION MODE

 

 

 

INTERRUPTED

 

 

 

2526

Image 26
Contents Crown Table of Contents Product DescriptionIII Before Installing General SpecificationsIV Locating the Boiler Air for Combustion and VentilationSide View For Buildings of Other than Unusually Tight Construction Boiler Installed in Confined Space ALL AIR from Inside ALL AIR from OUTDOORS, Using Openings Into Boiler Room Page VI Venting 109Minimum Recommended Breeching Chimney Size 1110VII System Piping 1211Piping Installation 1312Viii Indirect & Tankless Water Heater Piping Tanklessheaterpiping 1615 TanklessheaterpipingIX Fuel Line Piping 17161817 TWO-PIPE Gravity Feed System1918 Wiring 2019Indirect Water Heater Field Wiring 2120Feeder WIRINGMCDONNELL&MILLER#67LWCO 2322XI Start-up and Checkout 24232425 2526 XII Service and Maintenance 27262827 Tankless Heater Maintenance 2928Avoid Breathing Fiber Particulates and Dust 3029Installation Notes And Service Log 31303231 KEY # Description QTY. orPage 3433 KEY # DescriptionPage Rev 9