Crown Boiler KSZ150, KSZ125, KSZ200, KSZ175, KSZ120, KSZ065, KSZ090 1817, TWO-PIPE Gravity Feed System

Page 18

c)TWO-PIPE GRAVITY SYSTEM (not recommended) - Used when a fuel oil storage tank is located above an oil burner fuel pump. See Figure 15. A vertical distance from top of the tank to center line of the pump (Dimension ‘H’) over 8 feet will result in a pump inlet pressure in excess of the 3-psi limit in NFPA-31. This type of system should be converted to a one-pipe gravity system, as doing so will result in lower inlet line flow and longer filter life.

d)TWO-PIPE LIFT SYSTEM - used when a fuel oil storage tank is located below an oil burner fuel pump suction port. See Figure 16. The vertical distance from bottom of the tank to center line of the pump (Dimension ‘H’) must not exceed that shown in the pump manufacturer’s instructions. Distance ‘H’ allowed is reduced by number of fittings, filters and valves installed in the line.

FIGURE 15: TWO-PIPE GRAVITY FEED SYSTEM

FIGURE 16: TWO-PIPE LIFT SYSTEM

1817

Image 18
Contents Crown Table of Contents Product DescriptionIII Before Installing General SpecificationsIV Locating the Boiler Air for Combustion and VentilationSide View For Buildings of Other than Unusually Tight Construction Boiler Installed in Confined Space ALL AIR from Inside ALL AIR from OUTDOORS, Using Openings Into Boiler Room Page VI Venting 109Minimum Recommended Breeching Chimney Size 1110VII System Piping 1211Piping Installation 1312Viii Indirect & Tankless Water Heater Piping Tanklessheaterpiping 1615 TanklessheaterpipingIX Fuel Line Piping 17161817 TWO-PIPE Gravity Feed System1918 Wiring 2019Indirect Water Heater Field Wiring 2120Feeder WIRINGMCDONNELL&MILLER#67LWCO 2322XI Start-up and Checkout 24232425 2526 XII Service and Maintenance 27262827 Tankless Heater Maintenance 2928Avoid Breathing Fiber Particulates and Dust 3029Installation Notes And Service Log 31303231 KEY # Description QTY. orPage 3433 KEY # DescriptionPage Rev 9