3)Make sure that the boiler is correctly sized. Use an industry accepted sizing method such as the I=B=R Installation Guide for Residential Hydronic Heating Systems and I=B=R Heat Loss Calculation Guide (Pub. #H21 or #H22) published by the Hydronics Institute in Berkeley Heights, NJ.
4)In some cases, boilers installed at altitudes above 2000ft may require a different burner configuration from that at sea level. Consult the local Crown representative for more information.
IV Locating the Boiler
1)Clearances:
•Observe the minimum clearances shown below. Except as noted, these clearances apply to all combustible construction, as well as noncombustible walls, ceilings and doors. Also see Figure 2.
Front – 24”
Left Side – 6” (24” for Boilers Equipped with Float Type Low Water
Right Side – 6” (24” for Boilers Equipped with Tankless Heaters)
Rear – 6” (24” for boilers connected to indirect water heaters)
Top – 6”
Single Wall Chimney Connector (to combustible construction) - 18”
•A 24” service clearance from the jacket is recommended from the top of the boiler. This clearance may be reduced to that shown above; however, servicing the boiler will become increasingly difficult as this clearance is reduced.
•A 24” service clearance is required on the left side of KSZ series boilers equipped with float type low water cut- offs. This is to facilitate low water
2)If listed Type L vent is used, follow vent pipe manufacturer recommendations for minimum clearances.
3)Do not install this boiler directly on a combustible surface. Where it is desired to install the KSZ over a
4)Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.
V Air for Combustion and Ventilation
Sufficient fresh air must be supplied for combustion and ventilation. Provisions for combustion and ventilation air for oil burning equipment must be made in accordance with Section 1.5, Air for Combustion and Ventilation, in the latest edition of Installation of Oil Burning Equipment (ANSI/NFPA 31).
To ensure an adequate supply of air for combustion, ventilation and flue gas dilution, start by determining whether the boiler is to be installed in a building of unusually tight construction. A building of unusually tight construction is defined as having all of the following features:
•Walls and ceilings exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed.
•Weather stripping has been added on openable windows and doors.
•Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between
43