Burnham 81433101R16-1/10 Control Operating Characteristics, LED Error Codes, Burner START-UP

Page 24

After approximately 60 seconds without any key pressed, the display will enter a dim display mode. To return to the bright display mode, simply press any key.

2.Control Operating Characteristics

The L7248/L7224 can be in any three (3) operational states: Normal, High-Limit and Error. The controller moves back and forth from High- Limit to Normal state as part of normal operation.

The controller will enter the Error state when there is an abnormal condition. The operating states are:

a.Normal: Boiler temperature has gone below the high limit setting (minus the differential) and has not exceeded the high limit setting.

b.High-Limit: Boiler temperature has gone above the high limit setting and has not dropped below the high limit setting (minus the differential).

c.Error: The controller has detected an error condition (e.g., open sensor) and has shut down the burner output. The controller continues to monitor the system and automatically restarts if the error condition clears. See Table 4.

Table 4: LED Error Codes

Error Code

Cause/Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCom™ wiring.

Err3

Hardware fault’ replace control.

d.Low-Limit: Boiler temperature has gone below the low limit setting (minus the low limit differential) and has not gone above the low limit setting.

e.The operating sequence for L7248/L7224 is described below and shown in Table 5.

The switching action in the L7248/L7224 control has one setting, the high limit, see Figure 14. The switching relay is controlled by the low voltage room thermostat. On a call for heat, the relay contacts make to complete the line voltage circulator circuit and also the burner circuit if the boiler water temperature is below the high limit

Table 6: Beckett AFII Burner

Table 5: L7248/L7224 Controller

Operating Sequence

Action

System Response

 

 

Thermostat

Circulator starts.

calls for

Boiler temperature is checked. Burner

heat

restarts when the water temperature is

 

below high limit setting.

 

 

Boiler

Burner is turned off. Burner restarts when

exceeds the

the water temperature drops below the

high limit

high limit setting minus the differential.

 

 

Thermostat

Circulator and burner turn off.

is satisfied

 

 

 

Error

If an error condition is detected, all outputs

condition

are shut down. Burner is off. Control

 

continues to function and restarts when

 

error is corrected.

 

During the error check sequence, the

 

system checks for drift in the sensor and

 

corrosion in the connections.

 

 

setting. The high limit switch shuts off the burner if boiler water temperature exceeds the high limit setting. The circulator will continue to operate as long as the thermostat is calling for heat. The high limit automatically resets after the water temperature drops past the setpoint and through the differential.

F. BURNER START-UP

WARNING

Do not attempt to start the burner when excess oil has accumulated in the chamber, when boiler is full of vapor or when combustion chamber is very hot.

1.VERIFY burner settings.

a.Refer to Table 6 for Beckett Burner Settings. Refer to Table 6A for Riello BF Burner Settings.

b.Check electrodes to comply with dimensions shown in Figure 20A. For adjustment, loosen the electrode clamp screw and slide/rotate electrodes as needed. Securely re-tighten the clamp screw when finished.

Boiler

Firing Rate

Burner

Air Tube

Delavan

 

Settings

 

 

 

 

Model

(GPH)

Model

Combination

Nozzle

Air

Head

Pump Pressure

 

 

 

 

 

(stop screw)

(PSIG)

 

 

 

 

 

 

LEDV1

0.60

AFII 85

HLX50HD

0.50 x 70°B

2.5

#2

140

 

 

 

 

 

 

 

 

LEDV2

1.00

AFII 150

HLX50HE

0.85 x 60°B

3.5

#3

140

 

 

 

 

 

 

 

 

LEDV3

1.25

AFII 150

HLX50HE

1.00 x 60°B

4.0

#5

140

 

 

 

 

 

 

 

 

24

Image 24
Contents Ledv Series 81433101R16-1/10 Price $3.00Important Information Read Carefully Page Table of Contents Water Content 6.1 gallons Pre-Installation II. Unpack Boiler Do not drop boiler. Do not bump boiler jacketAgainst floor Minimum Clearances to Combustible Materials III. Water Piping and Trim Page Page IV. Venting / Air Intake Piping General GuidelinesVent Pipe Part Numbers Intake Terminal LocationVent Installation Vent Connector, Assembled Air Intake Installation Direct Vent only See Figure Page Electrical and Sequence of Operations ElectricalSequence of Operations Beckett Burner Schematic Wiring Diagram Page VI. Oil Piping General Single-pipe Oil Lines Two-Pipe Installation Two-Pipe Oil LinesAlways Inspect Installation Before Starting Burner Adjusting SettingsVII. System Start-up Ii. DisplayControl Operating Characteristics LED Error CodesBurner START-UP Riello BF Burner Settings Install Pressure GaugeCheck / Adjust OIL Pressure Remove Test Plug in Flue CollarHints on Combustion Simulate power failure Test ControlsSimulate flame failure Simulate ignition failurePage Section Viii Service and Cleaning Firetubes and Combustion ChamberBurner Low water cutoff if so equipped Avoid Breathing Fiber Particulates and Dust IX. Repair Parts Ledv Boiler Trim & ControlsLedv Boiler Jacket & Insulation Ledv Bare Boiler Assembly PartsRepair KitVent Beckett Afii Oil Burner Repair Part Beckett Afii Burner Replacement Parts Service Record Wiring of Typical Lwco Low Water Cut Off Lwco on Hot Water BoilersLwco Location Limited Warranty