Burnham 81433101R16-1/10 manual Pre-Installation

Page 6

I. Pre-Installation

A. INSPECT SHIPMENT carefully for any signs of damage.

1.ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition.

2.ANY CLAIMS for damage or shortage in shipment must be filed immediately against the carrier by the consignee. No claims for variances from, or shortage in orders, will be allowed by the manufacturer unless presented within sixty (60) days after receipt of goods.

B. LOCATE BOILER in front of final position before removing crate. See Figure 1. Boiler's approximate shipping weight is 325 pounds.

1.LOCATE so that vent pipe will be short and direct. Refer to Section V. A., General Venting Guidelines.

2.BOILER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR. Boiler cannot be installed on carpeting.

3.FOR BASEMENT INSTALLATION, provide a solid base, such as concrete, if floor is not level, or if water may be encountered on floor around boiler.

4.PROVIDE SERVICE CLEARANCE of at least 24” at front of boiler for servicing.

5.For minimum clearances to combustible materials, see Figure 2.

C. PROVIDE COMBUSTION AIR SUPPLY to accommodate proper combustion of oil. Local and national codes may apply and should be referenced.

1.In unconfined spaces (basement) in buildings of conventional frame, brick, or stone construction, infiltration normally is adequate to provide air for combustion. An unconfined space is a space whose volume is greater than or equal to 50 cubic feet per 1000 BTUH of the combined input of all air consuming appliances in the space.

2.In a confined space, combustion air may be ducted directly from the outdoors to the burner. Refer to Section IV for installation of air intake duct to the burner.

D. VENTILATION AIR must be provided to maintain the ambient temperature at safe limits. Local and national codes may apply and should be referenced.

1.In unconfined spaces (basement) in buildings of conventional frame, brick, or stone construction, infiltration normally is adequate to provide air for ventilation.

2.In confined spaces (closet, etc.) two permanent openings, one near the top of the enclosure and one near the bottom, shall be provided. Each opening shall have a free area of not less than 1 sq. inch per

1000 BTUH of the total input of all appliances in the space.

E. Do not install boiler where gasoline or other flammable vapors or liquids, or sources of hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.

Image 6
Contents Ledv Series 81433101R16-1/10 Price $3.00Important Information Read Carefully Page Table of Contents Water Content 6.1 gallons Pre-Installation II. Unpack Boiler Do not drop boiler. Do not bump boiler jacketAgainst floor Minimum Clearances to Combustible Materials III. Water Piping and Trim Page Page IV. Venting / Air Intake Piping General GuidelinesVent Pipe Part Numbers Intake Terminal LocationVent Installation Vent Connector, Assembled Air Intake Installation Direct Vent only See Figure Page Electrical and Sequence of Operations ElectricalSequence of Operations Beckett Burner Schematic Wiring Diagram Page VI. Oil Piping GeneralSingle-pipe Oil Lines Two-Pipe Installation Two-Pipe Oil LinesVII. System Start-up Always Inspect Installation Before Starting BurnerAdjusting Settings Ii. DisplayControl Operating Characteristics LED Error CodesBurner START-UP Check / Adjust OIL Pressure Riello BF Burner SettingsInstall Pressure Gauge Remove Test Plug in Flue CollarHints on Combustion Simulate flame failure Simulate power failureTest Controls Simulate ignition failurePage Section Viii Service and Cleaning Firetubes and Combustion ChamberBurner Low water cutoff if so equipped Avoid Breathing Fiber Particulates and Dust IX. Repair Parts Ledv Boiler Trim & ControlsLedv Boiler Jacket & Insulation Ledv Bare Boiler Assembly PartsRepair KitVent Beckett Afii Oil Burner Repair Part Beckett Afii Burner Replacement Parts Service Record Wiring of Typical Lwco Low Water Cut Off Lwco on Hot Water BoilersLwco Location Limited Warranty

81433101R16-1/10 specifications

The Burnham 81433101R16-1/10 is a highly regarded component within the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its reliability and performance. This specific part is designed to enhance the efficiency of heating systems, making it an essential component for both residential and commercial applications.

One of the standout features of the Burnham 81433101R16-1/10 is its durable construction. Made with high-quality materials, this product is built to withstand the rigors of continuous operation in various environmental conditions. Its robust design ensures a longer lifespan, reducing the need for frequent replacements and maintenance, which ultimately saves on operational costs.

The Burnham 81433101R16-1/10 incorporates advanced technology to optimize energy usage. This part is engineered for high efficiency, meaning that it works to convert a maximum amount of energy into heat with minimal waste. The integration of cutting-edge technology ensures that users experience significant energy savings, which not only helps in reducing utility bills but also contributes positively to environmental sustainability.

In terms of compatibility, the Burnham 81433101R16-1/10 is designed to work seamlessly with various heating systems. This makes it a versatile choice for technicians and homeowners alike, as it can be easily integrated without extensive modifications. The ease of installation is another appealing characteristic, allowing for quicker setups that minimize downtime.

Furthermore, this component prioritizes safety, featuring built-in mechanisms that help prevent overheating and other potential hazards. This focus on safety reassures users that their heating systems can operate efficiently without compromising the well-being of their households or properties.

The Burnham 81433101R16-1/10 is also known for its user-friendly design. Technicians find that maintenance and inspection processes are straightforward, allowing for easy access to components for troubleshooting or routine checks. This practical feature enhances user satisfaction and simplifies operational management.

Overall, the Burnham 81433101R16-1/10 exemplifies a commitment to quality, efficiency, and safety in HVAC applications. Its combination of durability, advanced technology, and versatile compatibility makes it a valuable choice for anyone looking to enhance their heating system's performance. By opting for the Burnham 81433101R16-1/10, users can enjoy efficient heating solutions that meet their needs for comfort and energy conservation.