Burnham 81433101R16-1/10 manual Hints on Combustion

Page 26

b.For adjustment, locate oil pressure adjusting screw and turn screw to obtain oil pressure specified.

10.ADJUST AIR SETTING on burner for alight orange colored flame. Flame should be solid and compact.

Use smoke tester and adjust air for a minimum smoke (not to exceed #1) with a minimum excess air. Make final check using suitable instrumentation to obtain CO2 of 11.5% to 12%. These settings will assure a safe and efficient operating condition. If flame appears stringy instead of solid fire, try another nozzle of the same type.

11.TURN "OFF" BURNER BY OPENING SERVICE SWITCH. Remove pressure gauge. Install gauge port plug and tighten. Re-start burner.

12.HINTS ON COMBUSTION

a.NOZZLES — Although the nozzle is a relatively inexpensive device, its function is critical to the successful operation of the oil burner. The selection of the nozzle supplied with the LEDV boiler is the result of extensive testing to obtain the best flame shape and efficient combustion.

Other brands of the same spray angle and spray pattern may be used but may not perform at the expected level of CO2 and smoke. Nozzles are delicate and should be protected from dirt and abuse. Nozzles are mass-produced and can vary from sample to sample. For all of those reasons a spare nozzle is a desirable item for a serviceman to have.

b.FLAME SHAPE — Looking into the combustion chamber through the flame plug hole, the flame should appear straight with no sparklers rolling up toward the top of the chamber. If the flame drags to the right or left, sends sparklers upward or makes wet spots on the rear door insulation piece, the nozzle should be replaced. If the condition persists look for fuel leaks, air leaks, water or dirt in the fuel as described below.

c.FUEL LEAKS — Any fuel leak between the pump and the nozzle will be detrimental to good combustion results. Look for wet surfaces in the air tube, under the transformer, and around the air inlet. Any such leaks should be repaired as they may cause erratic burning of the fuel and in the extreme case may become a fire hazard.

d.AIR LEAKS — Any such leaks should be repaired, as they may cause erratic burning of the fuel and in extreme cases may become a fire hazard.

There are many possible causes of air leaks in oil lines such as:

i. Fitting leaks due to mis-flared tubing or damaged fitting.

ii. Fuel line leak due to crushed or bent tubing.

iii.Filter connection leaks.

iv.Tank connection leaks.

There are various test kits available to trace air leaks, such as electronic sight glasses. Follow the manufacturers' instructions to find air leaks.

The following actions can eliminate air leaks:

i. Bleed pump as detailed in System Start-Up Section of this manual.

ii. Replace flare fittings.

iii. Replace oil supply line.

iv. Repair oil filter leaks.

v.Replace or repair tank fittings.

e.GASKET LEAKS — If 11.5 to 12.5% CO2 with

a#1 smoke cannot be obtained in the breeching, look for air leaks around the flue collar. Such air leaks will cause a lower CO2 reading in the breeching. The smaller the firing rate the greater effect an air leak can have on CO2 readings.

f.DIRT — A fuel filter is a good investment.

Accidental accumulation of dirt in the fuel system can clog the nozzle or nozzle strainer and produce a poor spray pattern from the nozzle.

The smaller the firing rate, the smaller the slots become in the nozzle and the more prone to plugging it becomes with the same amount of dirt.

g.WATER — Water in the fuel in large amounts will stall the fuel pump. Water in the fuel in smaller amounts will cause excessive wear on the pump, but more importantly water doesn’t burn. It chills the flame and causes smoke and unburned fuel to pass out of the combustion chamber and clog the flueways of the boiler.

h.COLD OIL — If the oil temperature approaching the fuel pump is 40°F or lower poor combustion or delayed ignition may result. Cold oil is harder to atomize at the nozzle. Thus, the spray droplets get larger and the flame shape gets longer. An outside fuel tank that is above grade or has fuel lines in a shallow bury is a good candidate for cold oil. The best solution is to bury the tank and lines deep enough to keep the oil above 40°F.

i.HIGH ALTITUDE INSTALLATIONS — Air settings must be increased at higher altitudes. Use instruments and set for 11.5 to 12.5% CO2.

j.START-UP NOISE — Late ignition is the cause of start-up noises. If it occurs recheck for electrode settings, flame shape, air or water in the fuel lines.

k.SHUT DOWN NOISE — If the flame runs out of air before it runs out of fuel, an after burn with noise may occur. That may be the result

26

Image 26
Contents Ledv Series 81433101R16-1/10 Price $3.00Important Information Read Carefully Page Table of Contents Water Content 6.1 gallons Pre-Installation Against floor II. Unpack BoilerDo not drop boiler. Do not bump boiler jacket Minimum Clearances to Combustible Materials III. Water Piping and Trim Page Page IV. Venting / Air Intake Piping General GuidelinesVent Pipe Part Numbers Intake Terminal LocationVent Installation Vent Connector, Assembled Air Intake Installation Direct Vent only See Figure Page Sequence of Operations Electrical and Sequence of OperationsElectrical Beckett Burner Schematic Wiring Diagram Page Single-pipe Oil Lines VI. Oil PipingGeneral Two-Pipe Installation Two-Pipe Oil LinesVII. System Start-up Always Inspect Installation Before Starting BurnerAdjusting Settings Ii. DisplayBurner START-UP Control Operating CharacteristicsLED Error Codes Check / Adjust OIL Pressure Riello BF Burner SettingsInstall Pressure Gauge Remove Test Plug in Flue CollarHints on Combustion Simulate flame failure Simulate power failureTest Controls Simulate ignition failurePage Burner Section Viii Service and CleaningFiretubes and Combustion Chamber Low water cutoff if so equipped Avoid Breathing Fiber Particulates and Dust IX. Repair Parts Ledv Boiler Trim & ControlsLedv Boiler Jacket & Insulation Ledv Bare Boiler Assembly PartsRepair KitVent Beckett Afii Oil Burner Repair Part Beckett Afii Burner Replacement Parts Service Record Lwco Location Wiring of Typical LwcoLow Water Cut Off Lwco on Hot Water Boilers Limited Warranty

81433101R16-1/10 specifications

The Burnham 81433101R16-1/10 is a highly regarded component within the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its reliability and performance. This specific part is designed to enhance the efficiency of heating systems, making it an essential component for both residential and commercial applications.

One of the standout features of the Burnham 81433101R16-1/10 is its durable construction. Made with high-quality materials, this product is built to withstand the rigors of continuous operation in various environmental conditions. Its robust design ensures a longer lifespan, reducing the need for frequent replacements and maintenance, which ultimately saves on operational costs.

The Burnham 81433101R16-1/10 incorporates advanced technology to optimize energy usage. This part is engineered for high efficiency, meaning that it works to convert a maximum amount of energy into heat with minimal waste. The integration of cutting-edge technology ensures that users experience significant energy savings, which not only helps in reducing utility bills but also contributes positively to environmental sustainability.

In terms of compatibility, the Burnham 81433101R16-1/10 is designed to work seamlessly with various heating systems. This makes it a versatile choice for technicians and homeowners alike, as it can be easily integrated without extensive modifications. The ease of installation is another appealing characteristic, allowing for quicker setups that minimize downtime.

Furthermore, this component prioritizes safety, featuring built-in mechanisms that help prevent overheating and other potential hazards. This focus on safety reassures users that their heating systems can operate efficiently without compromising the well-being of their households or properties.

The Burnham 81433101R16-1/10 is also known for its user-friendly design. Technicians find that maintenance and inspection processes are straightforward, allowing for easy access to components for troubleshooting or routine checks. This practical feature enhances user satisfaction and simplifies operational management.

Overall, the Burnham 81433101R16-1/10 exemplifies a commitment to quality, efficiency, and safety in HVAC applications. Its combination of durability, advanced technology, and versatile compatibility makes it a valuable choice for anyone looking to enhance their heating system's performance. By opting for the Burnham 81433101R16-1/10, users can enjoy efficient heating solutions that meet their needs for comfort and energy conservation.