commissioning
Test function and combustion analysis
The boiler has two pressure taps to measure the combustion gas temperature, the combustive air and the concentrations of O2 and CO2 on the outside of the flue gas header.
To access these pressure taps, unscrew the screw which holds the blanking cover and its seal together.
50
Only a 2.5 key must be used
|
|
|
| Minimum gas flow combustion analysis |
|
| |||||
|
|
|
| Activate the test function at minimum power in either heating or | |||||||
|
|
|
| domestic hot water production. |
|
|
|
| |||
|
|
|
| Wait for the boiler to stabilise before carrying out the combustion | |||||||
|
|
|
| analyses. Check the CO2 value according to the table above. |
| ||||||
|
|
|
| Important: do not remove silencer 17 |
|
|
| ||||
Checking the gas setting |
|
| N.B. When the combustion chamber is open, the CO2 value drops | ||||||||
To carry out analyses of combustion, the test function must be | by 0.3%. |
|
|
|
|
|
| ||||
If the values taken differ from the table, adjust the gas valve following | |||||||||||
activated. |
|
|
| ||||||||
|
|
| the procedure described below. |
|
|
|
| ||||
|
|
|
|
|
|
|
| ||||
Maximum gas flow combustion analysis |
| To adjust the CO2 value, remove cap, adjust the CO2 content to ± 0.2 by | |||||||||
Activate the test function at the maximum heating power, pushing | turning setting screw 51 (4 mm allen key) |
|
|
| |||||||
for 5 seconds the RESET until the yellow led 9 blinks (also 60°C led is | - unscrew to lower the CO2 value |
|
|
| |||||||
lit to indicate that Chimney is at max. CH absolute) The rotate the CH | - tighten to increase the CO2 value |
|
| ||||||||
knob to the min., intermediate position or max position it’s possible | Set the content by turning the screw about a 1/4 of a turn then wait | ||||||||||
to switch between min, max CH absolute and max DHW power | after each change for approximately 1 minute for the CO2 value to | ||||||||||
(respectively the 40°C, 60°C and 80°C are lit to indicate the power | stabilise, then repeat. |
|
|
|
|
| |||||
level. |
|
|
| Once the settings and analyses are complete, exit test mode by | |||||||
The function is automatically deactivated after 10 minutes or by | pressing Reset and reposition the blanking cover and its seal correctly. | ||||||||||
pressing the RESET button. |
|
|
|
|
|
|
|
|
| ||
Wait for the boiler to stabilise before carrying out the combustion |
|
|
|
|
|
|
| ||||
analyses. Check the CO2 value according to the table below. |
|
|
|
|
|
|
| ||||
Important: do not remove silencer 17 |
|
|
|
|
|
|
|
|
| ||
N.B. When the front combustion chamber panel is open, the CO2 |
|
|
|
|
|
|
| ||||
value drops by 0.3%. |
|
|
|
|
|
|
|
|
| ||
CO2 | 24 | 30 | 38 |
|
|
|
|
|
|
| |
maximum |
| CO2 (%) |
|
|
|
|
|
|
|
| |
minimum |
|
|
|
|
|
|
|
|
| ||
G20 | 9.0 ± 0.2 | 9.0 ± 0.2 | 9.4 ± 0.2 |
|
|
|
|
|
|
| |
G31 | 10.7 ± 0.2 | 10.0 ± 0.2 | 10.6 ± 0.2 |
|
|
|
|
|
|
| |
If the values taken differ from the table, adjust |
|
|
| Only a 4 key must be used | |||||||
|
|
|
|
|
|
|
| ||||
the gas valve following the procedure described |
|
|
|
|
|
|
|
| |||
below. |
|
|
|
|
| 24 |
| 30 |
| 38 | |
Adjust the CO2 | content to ± 0.2 by turning | Gas setting |
|
|
|
| |||||
| G20 | G31 | G20 | G31 | G20 | G31 | |||||
setting screw 50 (2.5 mm allen key) |
|
|
| ||||||||
| lower Wobbe index |
|
|
|
|
|
|
| |||
- tighten to lower the CO2 value |
| 45.67 | 70.69 | 45.67 | 70.69 | 45.67 | 70.69 | ||||
15°C, 1013 mbar) (MJ/m3) | |||||||||||
- unscrew to increase the CO2 value | NO | 3.80 | NO | 4.50 | NO | 5.25 | |||||
Set the content by turning the screw about a | gas valve restrictor(ø) |
| |||||||||
1/4 of a turn then wait after each change for | gas flow max/min | max D.H.W | 2.65 | 1.94 | 3.17 | 2.33 | 4.02 | 2.95 | |||
approximately 1 minute for the CO2 value to | (15°C, 1013 mbar) | max C.H. | 2.33 | 1.71 | 2.96 | 2.17 | 3.28 | 2.41 | |||
stabilise, then repeat. |
| (nat - m3/h) (GPL - kg/h) min | 0.58 | 0.43 | 0.69 | 0.50 | 0.79 | 0.58 | |||
|
|
|
31