FIRELARM 2500 Operating Manual

2.5.3NAC trouble / silence

Notification appliance circuit:

An increase of current to approximately 3.5mA when not in alarm or a decrease in current to approximately 1.5mA on the notification appliance circuit will result in the following:

Operation of the bell trouble LED.

Operation of all system trouble indications (section 2.5.11 System trouble). Trouble zone number and name is displayed on the optional LCD.

A current in excess of 2.5 amps, when the panel is in the alarm condition will result in a bell trouble. This will require pressing to clear.

A problem in an audible or visual device may not be apparent when the panel is in a normal standby condition. If a notification device indicates a trouble condition when the panel is in an alarm condition, the problem must be located and corrected.

2.5.4Supervisory trouble

A decrease of current on the supervisory initiating device circuit to approximately 2mA will result in the following:

Operation of the supervisory trouble LED.

Operation of all system trouble indications (see section 2.5.11 System trouble). SUPERVISORY TROUBLE CONDITION is displayed on the optional LCD.

2.5.5Initiating zone trouble

An increase in current to a level between 7mA to 20mA or a decrease of current to below 3.0mA or

pressing for any initiating device circuit will result in the following:

Operation of the zone trouble LED.

Operation of all system trouble indications (see section 2.5.11 System trouble). Trouble zone number and name is displayed on the optional LCD.

When the circuits are operated in the Style D (Class A) mode any trouble condition will require pressing to restore the panel to normal after the fault has been removed.

2.5.6

2.5.7Initiating circuit alarm

An increase of current on any alarm initiating device circuit to approximately 20mA or greater will result in the following (if all the associated touchpad settings are in the normal standby condition).

Operation of the audible or visual devices on the notification appliance circuit. Operation of the zone alarm LED.

Operation of the auxiliary alarm contacts. Operation of the buzzer for alarm (steady tone).

Reverse the voltage polarity of the remote alarm (RA) circuit. Alarm zone number and name is displayed on the optional LCD.

2-4

Image 12
Contents Operating Manual CPG #2561255 Firelarm 2500 Operating Manual Warranty Overview CPG #2561255 Firelarm 2500 Operating ManualMaintenance System features OverviewGeneral description Specifications Electrical specificationsHousing ZdactService use NFPA-72 Listings and approvalsCPG #2561255 IRE L ARM 2500 Operating Manual Operation TouchpadPrimary Primary Function Description Contents Silence and reset operation Normal Standby Condition6 … Initiating circuit alarm NAC trouble / silenceSupervisory trouble Initiating zone troubleAuxiliary power output conditions Battery power conditionsAC power conditions System troubleCPG #2561255 IRE L ARM 2500 Operating Manual Installation Safety message to installersNfpa and UL installation requirements Requirements for Central Station Fire Alarm Systems Installing the cabinet and optional bezelWiring Zonal Digital Alarm Communicator Transmitter optional ZdactBattery size requirements Using the Calculation Table TableCurrent Requirements Motherboard Device Wiring Diagram Notification Appliance Circuits ConnectionsCPG #2561255 IRE L ARM 2500 Operating Manual Configuration and Programming Selecting connected device options DIP switches1 B1 Strobe device 2 B1 Temporal patternProgram configuration of the panel Setup ZONES? Order of charactersZdact configuration Setup ZDACT?AC Delay HR Password settings Number KeysMaintenance Auto Reset feature One-man testInspection and Test procedure Testing the control panelTesting the Remote Annunciator Appendix A. Optional Accessories Key Function Control When ActiveRemote Annunciator with Liquid Crystal Display 2500-RALCD Electrical ConnectionsZonal Digital Alarm Communicator Transmitter 2500-ZDACT Figure A-2. Zdact MountingStyle Z Class a Module for NAC circuits CAM Transient Protected Built in 5.1K END of Line ResistorMaster Box Module Model MBM Figure A-5. MBMInstallation MBMCPG #2561255 IRE L ARM 2500 Operating Manual Appendix B. Smoke Detector Compatibility ESL MAX. NO. of Detectors PER Zone isContents Appendix C. NAC Compatibility Contents Replacement Parts Model No Description Stock No Appendix D. Ordering InformationBase Components Model No Description Stock No Options Model No Description Stock NoContents Appendix E. Quick Reference Operating Instructions FireLarm Contents