CPG #2561255 | FIRELARM 2500 Operating Manual |
Contents
1
4.1.3Reverse polarity circuits configuration
This panel is equipped with two polarity
If trouble signals are to be transmitted to the alarm location or if only the remote alarm circuit is used, place the
When the remote alarm output is programmed to transmit a trouble condition, the control panel is not suitable for remote station protected premises service where separate transmission circuits are required for fire, supervisory, and trouble signals. This should not be done unless approved by the Authority Having Jurisdiction
4.1.4Annunciator disconnect
2 | Place the ANNUNC DISC switch in the “on” position (right side of the switch) when you wish to ignore | |
commands sent from the remote annunciator or when an annunciator is not connected. | ||
3 | 4.1.5 | Waterflow detectors |
Place the WATERFLOW switch in the “on” position (right side of the switch) for all zones that are to be | ||
| used with waterflow detectors. The SILENCE and ZONE DISABLE keypads can not be used for zones | |
4 | configured for waterflow. Instead, the panel must be reset to silence the alarm notification device. | |
4.1.6 | Alarm verification | |
| Place the VERIFY switch in the “on” position (right side of the switch) to place a zone in the alarm | |
| verification mode. | |
| This mode should only be used with smoke detectors that do not include an alarm verification feature. | |
| When a smoke detector operates on a zone that has been selected for alarm verification, the panel will | |
| not immediately go into an alarm condition. | |
| Power will be removed for a period of 6 to 8 seconds, which will reset the detector. Power is then | |
| reapplied, but alarms are inhibited for the next 3 to 6 seconds. | |
| If any detector operates within the following confirmation period of approximately 120 seconds, an alarm | |
| condition will result. | |
| 4.1.7 | Style D (Class A) operation |
| Any initiating device zone (except the supervisory zone) can be operated in a Style D (Class A) mode. | |
| To place a zone in the Style D (Class A) mode, place the CLASS A switch in the “on” position (right side | |
| of the switch). Zones that are selected to be Style D (Class A) require a four wire, double loop, | |
| configuration. This permits detection of an alarm condition from any detector on the zone when a single | |
| open fault is present. | |
| 4.2 | Program configuration of the panel |
| The optional LCD is used to display system status during operation, show a description of each zone, | |
| and allows configuration of the optional ZDACT. The prompts and possible key presses for configuring |
the control panel are shown below to help with configuration. Words in BOLD ALL CAPS print appear in the LCD.
An LCD display is required for programming the panel. If you do not have an LCD output, see Appendix C for ordering optional LCD (Model OPLCD) or remote annunciator (Model RALCD).