3.2.5Requirements for Central Station Fire Alarm Systems
•Connect both phone lines to the optional ZDACT and OPLCD and program the telephone numbers for the reporting station.
•Set the AC trouble report delay from 6 to 12 hours.
3.3Installing the cabinet (and optional bezel)
Figure | Figure |
1
2
3
1.The FIRELARM 2500 unit may be surface mounted or
2.The unit should be mounted in a convenient location, approximately 4 feet from the floor where it will be accessible for testing and servicing.
Figure |
3. | The main circuit board module can be removed before |
|
|
|
|
|
|
|
|
|
|
|
| ||
| attempting to mount the cabinet. Disconnect the two wires of |
|
|
| |||
| the transformer from P2 on the main board. Remove the |
|
|
| |||
| eight Philips head screws and lock washers. Remove the |
|
|
| |||
| circuit board. |
|
|
| |||
4. | For |
|
|
| |||
| front edge protrudes 1" from the finished wall surface. |
|
|
|
|
|
|
|
|
|
|
|
|
| |
5. | After all conduits and wiring are in place and the wall surface |
|
|
|
|
|
|
| is completely finished, slide the trim bezel in place and |
|
|
|
|
|
|
| fasten with four |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|