CPG CPG #2561255 manual Operation, Touchpad, Primary Primary Function Description

Page 9

CPG #2561255

FIRELARM 2500 Operating Manual

2 Operation

2.1Touchpad

The touchpad provides user control over the operation of the panel. It is readily accessible when the cover is open.

Figure 2-1. FireLarm 2500 Touchpad.

Primary

Primary Function Description

Function

 

Resets all alarm circuits if condition has been corrected, removes power from initiating device circuit and auxiliary power from smoke detectors for 7 seconds.

Disables notification appliance circuit and trouble buzzer. Silencing an alarm condition will cause bell trouble LED to flash. If both buzzer and NAC are on, the first press of ACK/SILENCE will silence the buzzer; the second press will silence the NAC.

 Silencing an alarm or trouble on one zone will not prevent a subsequent alarm or trouble from another zone.

Toggles one-man test mode. See section 5.1 Auto Reset.

Toggles reverse polarity circuits from generating alarm or trouble condition, causes system trouble and trouble at the supervising station

Turns on all indicators, alarm and trouble outputs.

Toggles ability for each zone to generate alarm condition. Disabled state causes zone trouble and system trouble. Does not function if configured for waterflow.

Scrolls through trouble conditions, if present. For configuration mode, scrolls through the character set when entering zone labels.

Pressing for 2 seconds will initiate a fire drill.

Used in configuration mode, for saving a configuration and various functions.

To begin program configuration and change the configuration mode.

Used in configuration mode; return to the previous screen.

Used in configuration mode, and various functions.

2

3

4

5

A

B

C

D

E

2-1

Image 9
Contents Operating Manual CPG #2561255 Firelarm 2500 Operating Manual Warranty CPG #2561255 Firelarm 2500 Operating Manual OverviewMaintenance System features OverviewGeneral description Electrical specifications SpecificationsHousing ZdactListings and approvals Service use NFPA-72CPG #2561255 IRE L ARM 2500 Operating Manual Operation TouchpadPrimary Primary Function Description Contents Normal Standby Condition Silence and reset operationNAC trouble / silence 6 … Initiating circuit alarmSupervisory trouble Initiating zone troubleBattery power conditions Auxiliary power output conditionsAC power conditions System troubleCPG #2561255 IRE L ARM 2500 Operating Manual Installation Safety message to installersNfpa and UL installation requirements Installing the cabinet and optional bezel Requirements for Central Station Fire Alarm SystemsZonal Digital Alarm Communicator Transmitter optional Zdact WiringBattery size requirements Using the Calculation Table TableCurrent Requirements Motherboard Device Wiring Notification Appliance Circuits Connections DiagramCPG #2561255 IRE L ARM 2500 Operating Manual Selecting connected device options DIP switches Configuration and Programming1 B1 Strobe device 2 B1 Temporal patternProgram configuration of the panel Order of characters Setup ZONES?Setup ZDACT? Zdact configurationAC Delay HR Number Keys Password settingsAuto Reset feature One-man test MaintenanceInspection and Test procedure Testing the control panelTesting the Remote Annunciator Key Function Control When Active Appendix A. Optional AccessoriesRemote Annunciator with Liquid Crystal Display 2500-RALCD Electrical ConnectionsFigure A-2. Zdact Mounting Zonal Digital Alarm Communicator Transmitter 2500-ZDACTTransient Protected Built in 5.1K END of Line Resistor Style Z Class a Module for NAC circuits CAMFigure A-5. MBM Master Box Module Model MBMMBM InstallationCPG #2561255 IRE L ARM 2500 Operating Manual ESL MAX. NO. of Detectors PER Zone is Appendix B. Smoke Detector CompatibilityContents Appendix C. NAC Compatibility Contents Appendix D. Ordering Information Replacement Parts Model No Description Stock NoBase Components Model No Description Stock No Options Model No Description Stock NoContents Appendix E. Quick Reference Operating Instructions FireLarm Contents