CPG CPG #2561255 manual Notification Appliance Circuits Connections, Diagram

Page 21

CPG #2561255

FIRELARM 2500 Operating Manual

3.8Notification Appliance Circuits Connections

The control panel has two Style Y (Class B) notification appliance circuits which can be upgraded to Style Z (class A) by the addition of a model CAM (Class A Module). One module is required for each circuit that is to be upgraded. See Appendix A for more information.

The￿￿￿￿￿￿￿￿￿notification￿￿￿￿￿￿￿appliance￿￿￿￿circuits￿￿￿￿￿are ￿￿￿￿￿￿￿power limited,￿￿￿￿ regulated 24 VDC rated at 2.0 amperes max each. (Total system current￿not to exceed 2.5 A.)

￿￿￿￿￿￿￿￿ ￿ ￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿

 

Figure 3-7. Wire Routing

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Diagram

￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Notes for Figure 3-7:

1.Power inputs (not power limited). Wire wrap to standoff for strain relief.

2.Battery leads (not power limited).

3.Use left hand knockouts for non-power limited wiring.

4.Use right hand knockouts for power limited wiring.

5.Connect earth ground to corner of main board using a #6 ring terminal or wire and ring provided.

6.All wiring must be wire-wrapped to a standoff or other mechanically secure location.

All field-installed wiring connected to this panel must maintain a spacing of ¼ inch between all power-limited conductors and all electrical light, power, Class 1, or non-power limited conductors.

3

4

5

A

B

C

D

E

3-7

Image 21
Contents Operating Manual CPG #2561255 Firelarm 2500 Operating Manual Warranty CPG #2561255 Firelarm 2500 Operating Manual OverviewMaintenance System features OverviewGeneral description Electrical specifications SpecificationsHousing ZdactListings and approvals Service use NFPA-72CPG #2561255 IRE L ARM 2500 Operating Manual Operation TouchpadPrimary Primary Function Description Contents Normal Standby Condition Silence and reset operationNAC trouble / silence 6 … Initiating circuit alarmSupervisory trouble Initiating zone troubleBattery power conditions Auxiliary power output conditionsAC power conditions System troubleCPG #2561255 IRE L ARM 2500 Operating Manual Installation Safety message to installersNfpa and UL installation requirements Installing the cabinet and optional bezel Requirements for Central Station Fire Alarm SystemsZonal Digital Alarm Communicator Transmitter optional Zdact WiringBattery size requirements Using the Calculation Table TableCurrent Requirements Motherboard Device Wiring Notification Appliance Circuits Connections DiagramCPG #2561255 IRE L ARM 2500 Operating Manual Selecting connected device options DIP switches Configuration and Programming1 B1 Strobe device 2 B1 Temporal patternProgram configuration of the panel Order of characters Setup ZONES?Setup ZDACT? Zdact configurationAC Delay HR Number Keys Password settingsAuto Reset feature One-man test MaintenanceInspection and Test procedure Testing the control panelTesting the Remote Annunciator Key Function Control When Active Appendix A. Optional AccessoriesRemote Annunciator with Liquid Crystal Display 2500-RALCD Electrical ConnectionsFigure A-2. Zdact Mounting Zonal Digital Alarm Communicator Transmitter 2500-ZDACTTransient Protected Built in 5.1K END of Line Resistor Style Z Class a Module for NAC circuits CAMFigure A-5. MBM Master Box Module Model MBMMBM InstallationCPG #2561255 IRE L ARM 2500 Operating Manual ESL MAX. NO. of Detectors PER Zone is Appendix B. Smoke Detector CompatibilityContents Appendix C. NAC Compatibility Contents Appendix D. Ordering Information Replacement Parts Model No Description Stock NoBase Components Model No Description Stock No Options Model No Description Stock NoContents Appendix E. Quick Reference Operating Instructions FireLarm Contents