CPG CPG #2561255 manual Zonal Digital Alarm Communicator Transmitter 2500-ZDACT

Page 32

 

CPG #2561255

 

FIRELARM 2500 Operating Manual

 

A.2

Zonal Digital Alarm Communicator Transmitter (2500-ZDACT)

 

UL LISTED: For use with the FireLarm 2500

Contents

Transient protected

 

 

 

Power requirements:

 

 

 

 

 

 

 

 

 

Input current

 

 

 

 

 

Standby:

50mA

 

 

Alarm current:

90mA max.

 

Part # 2500-ZDACT:

 

 

 

 

The ZDACT is used for off-premises monitoring of the fire alarm control panel. Signals are sent to a

1

Digital Alarm Communicator Receiver (DACR) using either a primary or a secondary telephone line. Both

telephone lines are supervised; if one line is operational and the other is in trouble, a report is sent to the

 

supervising station and the Line Fault trouble LED (D3) is illuminated for local indication. The Panel

2

Supervisory trouble LED (D2) will illuminate if communication with the control panel is lost. The ZDACT

mounts directly on the FACP main board with earth ground lug screwed under standoff nut at top corner

post. Programming is done through the FACP with inputs for two phone numbers and a 4-digit account

 

number. The transmission format is Security Industry Association (SIA) Level 1 and is compatible with

3

the receivers listed below. The ZDACT will transmit a test call every 24 hours to the DACR.

Compatible SIA Level 1 Receivers

 

 

Manufacturer

 

Model Number

 

4

 

Silent Knight

 

9500 with 9810 Line card

 

 

 

 

 

 

5

 

 

 

 

 

A

Figure A-2. ZDACT Mounting.

A-2

Image 32
Contents Operating Manual CPG #2561255 Firelarm 2500 Operating Manual Warranty Overview CPG #2561255 Firelarm 2500 Operating ManualMaintenance General description System featuresOverview Specifications Electrical specificationsHousing ZdactService use NFPA-72 Listings and approvalsCPG #2561255 IRE L ARM 2500 Operating Manual Primary Primary Function Description OperationTouchpad Contents Silence and reset operation Normal Standby Condition6 … Initiating circuit alarm NAC trouble / silenceSupervisory trouble Initiating zone troubleAuxiliary power output conditions Battery power conditionsAC power conditions System troubleCPG #2561255 IRE L ARM 2500 Operating Manual Nfpa and UL installation requirements InstallationSafety message to installers Requirements for Central Station Fire Alarm Systems Installing the cabinet and optional bezelWiring Zonal Digital Alarm Communicator Transmitter optional ZdactBattery size requirements Using the Calculation Table TableCurrent Requirements Motherboard Device Wiring Diagram Notification Appliance Circuits ConnectionsCPG #2561255 IRE L ARM 2500 Operating Manual Configuration and Programming Selecting connected device options DIP switches1 B1 Strobe device 2 B1 Temporal patternProgram configuration of the panel Setup ZONES? Order of charactersZdact configuration Setup ZDACT?AC Delay HR Password settings Number KeysMaintenance Auto Reset feature One-man testInspection and Test procedure Testing the control panelTesting the Remote Annunciator Appendix A. Optional Accessories Key Function Control When ActiveRemote Annunciator with Liquid Crystal Display 2500-RALCD Electrical ConnectionsZonal Digital Alarm Communicator Transmitter 2500-ZDACT Figure A-2. Zdact MountingStyle Z Class a Module for NAC circuits CAM Transient Protected Built in 5.1K END of Line ResistorMaster Box Module Model MBM Figure A-5. MBMInstallation MBMCPG #2561255 IRE L ARM 2500 Operating Manual Appendix B. Smoke Detector Compatibility ESL MAX. NO. of Detectors PER Zone isContents Appendix C. NAC Compatibility Contents Replacement Parts Model No Description Stock No Appendix D. Ordering InformationBase Components Model No Description Stock No Options Model No Description Stock NoContents Appendix E. Quick Reference Operating Instructions FireLarm Contents