| FIRELARM 2500 Operating Manual | ||
| A.2 | Zonal Digital Alarm Communicator Transmitter | |||
| UL LISTED: For use with the FireLarm 2500 | ||||
Contents | Transient protected |
|
|
| |
Power requirements: |
|
|
| ||
|
|
|
| ||
|
| Input current |
|
|
|
|
| Standby: | 50mA | ||
|
| Alarm current: | 90mA max. | ||
| Part # |
|
|
| |
| The ZDACT is used for | ||||
1 | Digital Alarm Communicator Receiver (DACR) using either a primary or a secondary telephone line. Both | ||||
telephone lines are supervised; if one line is operational and the other is in trouble, a report is sent to the | |||||
| supervising station and the Line Fault trouble LED (D3) is illuminated for local indication. The Panel | ||||
2 | Supervisory trouble LED (D2) will illuminate if communication with the control panel is lost. The ZDACT | ||||
mounts directly on the FACP main board with earth ground lug screwed under standoff nut at top corner | |||||
post. Programming is done through the FACP with inputs for two phone numbers and a | |||||
| number. The transmission format is Security Industry Association (SIA) Level 1 and is compatible with | ||||
3 | the receivers listed below. The ZDACT will transmit a test call every 24 hours to the DACR. | ||||
Compatible SIA Level 1 Receivers | |||||
|
| Manufacturer |
| Model Number |
|
4 |
| Silent Knight |
| 9500 with 9810 Line card |
|
|
|
|
|
| |
5 |
|
|
|
|
|
A