CPG CPG #2561255 Maintenance, Auto Reset feature One-man test, Inspection and Test procedure

Page 29

CPG #2561255

FIRELARM 2500 Operating Manual

5 Maintenance

Most modern control units do not require periodic adjustment or field repair other than replacement of a module or printed circuit board assembly. Defective printed circuit board assemblies or modules can best be serviced at the manufacturer’s plant or at their authorized service facility. Where the control unit uses printed circuit boards, care should be taken to clean off excessive dust. The boards should be maintained clean and dry to ensure proper operation.

5.1Auto Reset feature (One-man test)

This function only works when the panel is in the standby mode. Pressing sets the panel into one-

man test mode. When a zone goes into alarm, the audible circuits are pulsed ½ second for identification of the zone; i.e. zone 1 has one pulse, zone 2 has two pulses, etc. After the zone number is pulsed, the panel automatically resets the zones by cycling power. After 15 minutes of no activity, the panel provides

5 pulses on the NAC and goes back into standby condition. Pressing again (no pulses with this exit) returns the panel to standby condition.

5.2Inspection and Test procedure

5.2.1Testing the control panel

Notify the building occupants, the fire department and/or receiving station personnel before and after testing is performed. Notify the fire department and/or other receiving station personnel if alarm,

supervisory, and/or trouble signals are transmitted. (Transmissions may be inhibited by pressing .)

In addition to the testing procedures described below, the FireLarm 2500 system and all of its associated protective signaling adjuncts should be inspected and tested in accordance with the NFPA-72 National Fire Alarm Code and any requirements of the Authority Having Jurisdiction.

1.Notify the proper building personnel so audible and/or visual signals can be viewed as a test by building occupants.

2. Press

. This will cause all audible and visual indicators on the panel and the NAC outputs to

come on. Releasing

will restore the panel to the condition it was in prior to operation of this

touchpad.

 

 

3.Press each . This will result in a trouble condition and operate all indicators as described in section 2.5.5 Initiating Zone Trouble. Repressing will restore all indicators to normal.

4.Momentarily open each of the following circuits. Observe that each of these results in a trouble condition and appropriate indicators operate as described in the section for the particular circuit that is faulted. (See section 2.5.5 Initiating Zone Trouble)

Each initiating device zone (there is a brief delay when these circuits are in the Style D (Class A) mode.

Supervisory circuit.

Notification appliance circuit

5.Momentarily shunt each of the circuits listed in the previous step (except the supervisory circuit) with 4.7K ohm resistor and again observe that a trouble condition is generated for each test. Use 1.5K ohm for the supervisory circuit.

6.Turn off the AC power at the circuit breaker panel. The green AC-ON indicator will be extinguished. Observe that all the trouble indications occur that are described in section 2.5.10 AC power conditions.

5

A

B

C

D

E

5-1

Image 29
Contents Operating Manual CPG #2561255 Firelarm 2500 Operating Manual Warranty CPG #2561255 Firelarm 2500 Operating Manual OverviewMaintenance General description System featuresOverview Electrical specifications SpecificationsHousing ZdactListings and approvals Service use NFPA-72CPG #2561255 IRE L ARM 2500 Operating Manual Primary Primary Function Description OperationTouchpad Contents Normal Standby Condition Silence and reset operationNAC trouble / silence 6 … Initiating circuit alarmSupervisory trouble Initiating zone troubleBattery power conditions Auxiliary power output conditionsAC power conditions System troubleCPG #2561255 IRE L ARM 2500 Operating Manual Nfpa and UL installation requirements InstallationSafety message to installers Installing the cabinet and optional bezel Requirements for Central Station Fire Alarm SystemsZonal Digital Alarm Communicator Transmitter optional Zdact WiringBattery size requirements Using the Calculation Table TableCurrent Requirements Motherboard Device Wiring Notification Appliance Circuits Connections DiagramCPG #2561255 IRE L ARM 2500 Operating Manual Selecting connected device options DIP switches Configuration and Programming1 B1 Strobe device 2 B1 Temporal patternProgram configuration of the panel Order of characters Setup ZONES?Setup ZDACT? Zdact configurationAC Delay HR Number Keys Password settingsAuto Reset feature One-man test MaintenanceInspection and Test procedure Testing the control panelTesting the Remote Annunciator Key Function Control When Active Appendix A. Optional AccessoriesRemote Annunciator with Liquid Crystal Display 2500-RALCD Electrical ConnectionsFigure A-2. Zdact Mounting Zonal Digital Alarm Communicator Transmitter 2500-ZDACTTransient Protected Built in 5.1K END of Line Resistor Style Z Class a Module for NAC circuits CAMFigure A-5. MBM Master Box Module Model MBMMBM InstallationCPG #2561255 IRE L ARM 2500 Operating Manual ESL MAX. NO. of Detectors PER Zone is Appendix B. Smoke Detector CompatibilityContents Appendix C. NAC Compatibility Contents Appendix D. Ordering Information Replacement Parts Model No Description Stock NoBase Components Model No Description Stock No Options Model No Description Stock NoContents Appendix E. Quick Reference Operating Instructions FireLarm Contents