CPG CPG #2561255 manual Specifications, Electrical specifications, Housing, Zdact

Page 6

CPG #2561255

FIRELARM 2500 Operating Manual

1.3Specifications

1.3.1Electrical specifications

Contents

Primary (AC) power:

 

 

Accessory (battery) voltage

 

Control Unit Requirements:

 

Standby current

 

Alarm current

1

Output Ratings:

 

System alarm contacts

 

System trouble contacts

 

4-wire smoke detector power

 

Auxiliary power

 

Max ripple voltage

 

Optional Accessories:

 

Remote annunciator RALCD

 

Max number per panel

 

Style Z (Class A) Module (CAM)

 

ZDACT

 

 

Notification Appliance Circuit (Bells): **

 

Current, nominal

 

Max short circuit current

 

Normal supervisory current￿

 

End of line resistance

 

Initiating Device Circuits (Zones):

 

Smoke capacity (24VDC)†

 

Standby voltage

 

Max ripple voltage

 

Max short circuit current

 

Normal standby current

 

Alarm current threshold

 

Max impedance for alarm

 

End of line resistance

 

Max. line resistance

 

Supervisory Initiating Circuit:††

 

Max voltage

 

Max short circuit current

 

Max circuit resistance

 

Normal supervisory current

 

Trouble current

 

End of line resistance

 

Reverse Polarity Outputs:†††￿ Max

 

voltage ￿

Max line current

120VAC, 60 Hz, 1.5A max 24VDC; (charging current, 1.0A)

110mA, 24VDC (not including auxiliary devices and modules)￿200mA, 24VDC (not including auxiliary devices and modules)

SPDT, 2A, 30VDC, 0.6 power factor SPDT, 2A, 30VDC, 0.6 power factor

24VDC, .5A power limited, regulated, resetable*** 24VDC, .5A power limited, regulated, resistive load, non- resetable***

500mV (4-wire smoke and aux. power circuits)

Power limited,100mA, 24VDC per unit, (see Appendix A) 2

0mA standby, 25mA alarm (see Appendix A) 90mA max in alarm (See Appendix A)

24VDC, 2.0A (max) ***, power limited 2.5A, power limited

2.7mA

5.1K ohms

25 detectors, 0.1mA type; 20 detectors, 0.12mA type

27.5VDC (max) to 16 VDC (min) 500mV

60mA, power limited 4.5mA

approx. 20mA 1.5K ohms 5.1K ohms 100 ohms

27.5 VDC

10mA, power limited

100ohms

3.5mA

2mA (low trouble) 5mA (supervisory) 5.1K ohms

24VDC

15mA



*All terminals are capable of up to #12 AWG wire.

**Use any UL listed polarized notification appliances rated 24VDC.

***Total system current for auxiliary device powered by the panel not to exceed 2.5 amps. This includes NAC power, auxiliary power, reverse polarity outputs, four wire detector power, and remote annunciator. The latter three are 0.5A max combined.

Max load: 2.5mA. Use only detectors that are listed in compatibility list. †† Use supervisory devices with normally open contacts.

††† Power limited

1.3.2Housing

Type 18-gauge sheet steel with hinged, removable, locked door.

1-2

Image 6
Contents Operating Manual CPG #2561255 Firelarm 2500 Operating Manual Warranty Overview CPG #2561255 Firelarm 2500 Operating ManualMaintenance System features OverviewGeneral description Housing SpecificationsElectrical specifications ZdactService use NFPA-72 Listings and approvalsCPG #2561255 IRE L ARM 2500 Operating Manual Operation TouchpadPrimary Primary Function Description Contents Silence and reset operation Normal Standby ConditionSupervisory trouble 6 … Initiating circuit alarmNAC trouble / silence Initiating zone troubleAC power conditions Auxiliary power output conditionsBattery power conditions System troubleCPG #2561255 IRE L ARM 2500 Operating Manual Installation Safety message to installersNfpa and UL installation requirements Requirements for Central Station Fire Alarm Systems Installing the cabinet and optional bezelBattery size requirements WiringZonal Digital Alarm Communicator Transmitter optional Zdact Using the Calculation Table TableCurrent Requirements Motherboard Device Wiring Diagram Notification Appliance Circuits ConnectionsCPG #2561255 IRE L ARM 2500 Operating Manual 1 B1 Strobe device Configuration and ProgrammingSelecting connected device options DIP switches 2 B1 Temporal patternProgram configuration of the panel Setup ZONES? Order of charactersZdact configuration Setup ZDACT?AC Delay HR Password settings Number KeysInspection and Test procedure MaintenanceAuto Reset feature One-man test Testing the control panelTesting the Remote Annunciator Remote Annunciator with Liquid Crystal Display 2500-RALCD Appendix A. Optional AccessoriesKey Function Control When Active Electrical ConnectionsZonal Digital Alarm Communicator Transmitter 2500-ZDACT Figure A-2. Zdact MountingStyle Z Class a Module for NAC circuits CAM Transient Protected Built in 5.1K END of Line ResistorMaster Box Module Model MBM Figure A-5. MBMInstallation MBMCPG #2561255 IRE L ARM 2500 Operating Manual Appendix B. Smoke Detector Compatibility ESL MAX. NO. of Detectors PER Zone isContents Appendix C. NAC Compatibility Contents Base Components Model No Description Stock No Replacement Parts Model No Description Stock NoAppendix D. Ordering Information Options Model No Description Stock NoContents Appendix E. Quick Reference Operating Instructions FireLarm Contents