Hearth and Home Technologies COLBAY-FS-B owner manual Wallline Thimble

Page 13

CENTER OF

HOLE

CENTER

LINE

CENTER

WALLLINE

THIMBLE

Figure 5.5

NOTE:

(1)Installation requires a minimum of 6 in. (152mm) horizontal run of vent with a 1/4 in. (6mm) rise run towards the termination. Each 1 ft. (305mm) of horizontal venting must include a 1/4 in. (6mm) rise. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a house or structure fire.

(2)The location of the horizontal termination cap on an exterior wall must meet all local and national building codes, and must not be easily blocked or obstructed, see Figure 4.4 on page 9.

(3)For installations requiring a vertical rise on the exterior of the building, the HHT RHVK snorkel kit (Part #844- 8921) is available with a 14 in. (356mm) and a 36 in. (914mm) tall snorkel termination cap. Follow the same installation procedures as used for standard horizontal terminations. If the snorkel termination must be installed below grade (i.e. basement application), proper drainage must be provided to prevent water from entering the snorkel termination. Do not backfill around snorkel termination.

Step 4.

Position the horizontal termination cap in the center of the 10 in. x 10 in. (254mm x 254mm) square hole and run a bead of non-hardening mastic around its outside edges, so as to make a seal between it and the wall, attach termination cap to the exterior wall with the four wood screws provided. The arrow on the vent cap should be pointing up (Figure 5.6)

WOOD

SCREW

PART HHW2 PART

HOT 841-0670 (Preferred)

WALL THIMBLE

Figure 5.6

NOTES:

(1)The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

(2)Termination cap HHW2 (Part #841-0670) is highly recommended on a building with vinyl siding, as the vinyl siding standoff is built in. The pilot hole will be 2 in. (51mm) closer to the bottom of the square than the top. Using a framing square, draw a 14 in. x 14 in. (356mm x 356mm) square around the pilot hole in the siding. See Figure 5.7.

8 in.

 

(203mm)

 

 

7 in.

 

(178mm)

7 in.

6 in.

(178mm)

 

(152mm)

Figure 5.7

(NOTE: If you are installing termination cap HHW2, the pipe will be off center on the flashing). Ensure that proper clearances to combustible materials are maintained. If you are using an approved termination cap other than HHW2 (part #841-0670) on a building with vinyl siding, a vinyl siding standoff should be installed between the vent cap and the exterior wall (Figure 5.8, on the next page). Attach the vinyl siding standoff to the horizontal vent termination. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. Vent terminal shall not be recessed into a wall or siding. Remove siding from the area where the standoff will be located..

10/08

Quadra-Fire • Columbia Bay • 250-5195 Rev. K

Page 13

Image 13
Contents COLBAY-FS-B What to do if you smell gasDo not Discard this Manual Do DiscardnotModel Name Test Lab Report No Serial Number BarcodeTable of Contents 1Listing and Code Approvals BELOW. Keep Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsManufacturer Requirements Getting Started Design & Installation ConsiderationsInspect Appliance & Components Tools and Supplies NeededSelecting Appliance Location Appliance Location and ClearancesClearances Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Venting Components Vent InformationUse of Elbows Measuring StandardsVenting Guidelines How to Use the Vent GraphVertical Distance From Appliance to To the 90 Elbow Step Horizontal TerminationWallline Thimble Fold Strap Here Sheet Metal Screw Direct Vent Pipe Vertical TerminationStep Twist-lock the vent cap and seal Cathedral Ceiling Top Adapter Flex Pipe Sheet Metal Screws Step Class a Metal ChimneyExisting Masonry Chimney Retro Connector Fuel Conversions Gas InformationConverting to LP Gas Valve Regulator Replacement Pressure Gas Pressures Gas ConnectionCheck for GAS Leaks Connecting to the Appliance Recommendation for WireStanding Pilot Ignition System Wiring Electrical InformationThermopile GAS Pilot Ignitor Thermocouple Accessories Appliance SetupBrick Installation Door Crown Installation Remove Shipping MaterialsPositioning the Logs Install NEW Brick SETMineral Wool Glass Door ReplacementBlack Blower InstallationShutter Adjustment Vertical Damper AdjustmentBefore Lighting Appliance Operating InstructionsControls Lighting Appliance For Your Safety Read Before LightingAfter Appliance is Lit Frequently Asked QuestionsSymptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing Your ApplianceMaintenance Tasks Inspect Service and Maintenance Log Reference Materials Appliance Dimension DiagramSLP Series Vent Components Vent Components DiagramMiscellaneous Vent Components ListPart number list on following Log Set AssemblyStocked At DepotStocked Pedestal ComponentsDepot Valve ComponentsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Columbia Bay Direct Vent Gas Appliance Serial Number Date Purchased Date Installed Dealer Telephone