Hearth and Home Technologies COLBAY-FS-B owner manual Gas Pressures Gas Connection

Page 24

B. Gas Pressures

C. Gas Connection

Proper input pressures required for optimum appliance per- formance, gas line sizing requirements need to be followed from NFPA54.

WARNING

Fire Risk. Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

NOTE: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI Z223.1. Instal- lation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter.)

NOTE: A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 inch (13mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

WARNING

Verify inlet pressures.

High pressure may cause overfire condition.

Low pressure may cause explosion.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

WARNING

Gas Leak Risk.

Support control when attaching pipe to prevent bending gas line.

Pressure requirements for appliance are shown in the table below.

PRESSURE

NG

LP

Minimum Inlet Pressure

4.5 inches w.c.

11.0 inches w.c.

Maximum Inlet Pressure

7.0 inches w.c.

14.0 inches w.c.

Manifold Pressure on “HI”

3.5 inches w.c.

10.0 inches w.c.

If the pressure is not sufficient, ensure:

1)the piping used is large enough.

2)the supply regulator is adequately adjusted.

3)that the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

NOTE: The gap between the supply piping and gas access hole may be plugged with non-combustible insulation to prevent cold air infiltration.

Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.

Before making the gas connection, ensure that the appliance you are installing is designed for the type of gas being supplied. This information can be found on the Ratings Label under the appliance. If the appliance has been converted to propane (LP), the valve cover should have a label stating that the unit has been converted to propane.

Connect the gas line at the 3/8 in. (9.5mm) pipe connector on the valve at the back of appliance. We recommend connecting the appliance with an approved flex gas line. If flex gas lines are not approved in your area, you must connect a hard pipe to the gas hookup.

You must supply a manual shut-off valve in a visible location within 3 feet (914mm) of the appliance.

Page 24

Quadra-Fire • Columbia Bay • 250-5195 Rev. K

10/08

Image 24
Contents What to do if you smell gas COLBAY-FS-BDo not Discard this Manual Do DiscardnotSerial Number Barcode Model Name Test Lab Report NoTable of Contents 1Listing and Code Approvals Requirements for the Commonwealth of Massachusetts BELOW. Keep Clear of ALL ObstructionsManufacturer Requirements Design & Installation Considerations Getting StartedInspect Appliance & Components Tools and Supplies NeededAppliance Location and Clearances Selecting Appliance LocationClearances 4Termination Locations Vent Termination Minimum ClearancesAlcove Applications Vent Information Venting ComponentsUse of Elbows Measuring StandardsHow to Use the Vent Graph Venting GuidelinesVertical Distance From Appliance to To the 90 Elbow Horizontal Termination StepWallline Thimble Fold Strap Here Sheet Metal Screw Vertical Termination Direct Vent PipeStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Top Adapter Flex Pipe Sheet Metal Screws StepExisting Masonry Chimney Retro Connector Gas Information Fuel ConversionsConverting to LP Gas Valve Regulator Replacement Gas Pressures Gas Connection PressureCheck for GAS Leaks Recommendation for Wire Connecting to the ApplianceStanding Pilot Ignition System Wiring Electrical InformationThermopile GAS Pilot Ignitor Thermocouple Appliance Setup AccessoriesBrick Installation Door Crown Installation Remove Shipping MaterialsInstall NEW Brick SET Positioning the LogsGlass Door Replacement Mineral WoolBlower Installation BlackVertical Damper Adjustment Shutter AdjustmentOperating Instructions Before Lighting ApplianceControls For Your Safety Read Before Lighting Lighting ApplianceFrequently Asked Questions After Appliance is LitTroubleshooting Symptom Possible Cause Corrective ActionBe Placed in this Opening Maintaining and Servicing Your Appliance After servicingMaintenance Tasks Inspect Service and Maintenance Log Appliance Dimension Diagram Reference MaterialsVent Components Diagram SLP Series Vent ComponentsVent Components List MiscellaneousLog Set Assembly Part number list on followingAt Depot StockedPedestal Components StockedDepot Valve ComponentsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Serial Number Date Purchased Date Installed Dealer Telephone Columbia Bay Direct Vent Gas Appliance