C.FLUE SYSTEM APPROVALS AND INSTALLATIONS
MODEL FLUE TERMINATION APPROVALS
6000TRSI-AUC DVP-TRAP2, DVP-TVHW
TABLE 1
This model is approved to use
Figures 1.7 through 1.14 show the flue systems ap- proved for these models. Approved flue system compo- nents are labeled for identification. NO OTHER FLUE SYSTEMS OR COMPONENTS MAY BE USED. De- tailed installation instructions are included with each flue termination kit and should be used in conjunction with this manual.
WARNING: THIS GAS APPLIANCE AND FLUE AS- SEMBLY MUST BE FLUED DIRECTLY TO THE OUT- SIDE AND MUST NEVER BE ATTACHED TO A CHIM- NEY SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE. EACH GAS APPLIANCE MUST USE A SEPARATE FLUE
CAUTION: UNDER NO CONDITION SHOULD COM- BUSTIBLE MATERIAL BE CLOSER THAN 3 INCHES (2 1/2 INCHES AT WALL FIRESTOPS) FROM THE TOP OF THE 8 INCH PIPE OR 1- INCH TO THE SIDES AND THE BOTTOM FOR HORIZONTAL SECTIONS OF THIS FLUE SYSTEM. VERTICAL SECTIONS OF THIS SYSTEM REQUIRE A MINIMUM OF 1 INCH CLEARANCE TO COMBUSTIBLE MATERIALS ALL AROUND THE 8 INCH PIPE.
For alternative installations, other than depicted, con- tact your dealer for further information.
Refer to Figure 1.4 for required clearances to flue ter- minals.
VERTICAL FLUE RESTRICTOR
If the heater installation requires a vertical flue exceed- ing 4.5m above the unit with no horizontal flue or el- bows a vertical flue restrictor must be installed (see
Figure 1.5). |
RESTRICTOR |
PLATE |
FIGURE 1.5 |
STRAIGHT UP VERTICAL FLUE SYSTEM
Figure 1.6 shows straight up vertical flue system ap- proved for use on this model.
CAP |
V |
MAX. RUN |
36 FT. |
(10.97m) |
FIGURE 1.6 |
8 | Heat & Glo • |