STRAIGHT OUT HORIZONTAL FLUE SYSTEM Figure 1.7 shows straight out horizontal flue systems approved for use on this model.

H

H

MIN. RUN

MAX. RUN

13.1" (331mm)

24" (610mm)

H

 

FIGURE 1.7 Straight Out Horizontal Flueing

ELBOWS

The flue systems installed on this gas heater may also include one (1), two (2), or three (3) 90 - degree elbow assemblies.

Figures 1.8 through 1.14 and their corresponding tables show examples of flue configurations using elbows. The relationships of vertical rise to horizon- tal run in flue configurations using elbows MUST be strictly adhered to.

V

 

H

 

1´ MIN. (0.30 M)

2´ MAX. (0.61 M)

2´ MIN. (0.61

M)

4´ MAX. (1.22 M)

3´ MIN. (0.91

M)

6´ MAX. (1.83

M)

4´ MIN. (1.22

M)

8´ MAX. (2.44

M)

24´ MAX. (7.32 M)

8´ MAX. (2.44

M)

 

 

 

 

V

H

FIGURE 1.8 Flueing with One 90° Elbow

ONE (1) 90-DEGREE ELBOW

Figures 1.8 and 1.9 show an installation using one (1) 90-degree elbow. Dimension V is listed as MINIMUM vertical dimensions and dimension H is listed as corre- sponding MAXIMUM horizontal dimensions.

TWO (2) 90-DEGREE ELBOWS

Figures 1.10 and 1.11 show examples of possible in- stallations using two (2) 90-degree elbows. Dimension V is listed as MINIMUM vertical dimensions, dimen- sion H is listed as MAXIMUM beginning horizontal di- mensions, and dimension H+H1 is listed as correspond- ing TOTAL MAXIMUM horizontal dimensions.

THREE (3) 90-DEGREE ELBOWS

Figures 1.12 through 1.14 show examples of possible installations using three (3) 90-degree elbows. Dimen- sions V are listed MINIMUM first vertical dimensions and dimensions H are listed as beginning MAXIMUM horizontal dimensions. Dimensions H+H1 and H+H1+H2 are listed as TOTAL MAXIMUM horizontal dimensions. Dimensions V+V1 are listed as TOTAL MAXIMUM ver- tical dimensions.

Heat & Glo • 6000TRSI-AUC2078-900 Rev. G • 12/06

9

Image 9
Contents Model 6000TRSI-AUC Installation and Operation InstructionsHeat & Glo Quality Systems Table of Contents 476 686 31-5/8 803 174 126.9 Installation InstructionsRear Flue Top FlueClearance Requirements Framing the Heater Clearances n mm 10.97m Flue System Approvals and InstallationsElbows 13.1 331mm 24 610mmFlueing with One 90 Elbow +H 1 FT + H 1 FT 13 Flueing with three 90 elbows + H 1 FT Flueing with Three 3 90 ElbowsFlueing Out the Top Flue Flueing Out the Rear FlueAssembling Flue Components Install Support Brackets Flue Termination Must be Positioned SO That the Arrow is Pointing UP Connecting the GAS SupplyShock Risk Ignition System WiringBlower Fan Clearance to a mantelpiece is 12 inches 305mm. See Figure Mantel ClearancesTabs LOG Placement InstructionsHeat & Glo 6000TRSI-AUC 2078-900 Rev. G 12/06 Operating Instructions Installer TestingOperating Cautions Safety & Lighting Information For Your Safety Read Before Lighting InstructionsFAN Operation Power OutageServicing and Maintenance Parts Replacement Removal of Components for ServiceAdjustments and Replacement Parts Removal of Covers for ServicingInspect Maintenance Tasks Maintenance TasksElectronic Ignition System TroubleshootingAdjust the air shutter at the base of the burner 6000TRSI-AUC Log set assemblyGLA-6TRXI 6000TRSI-AUCHeat & GLO, a brand of Hearth & Home Technologies Inc Limited 10 Year WarrantyMelbourne