LG Electronics LSC183VMA Off-Timer Operation, Off-Timer ↔ On-Timer Operation, Chaos Swing Mode

Page 15

Off-Timer Operation

When the set time is reached after the time is input by the remote control, the appliance stops operating.

The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.

If the appliance is on pause at the time set by the timer, the pause continues.

Off-Timer On-Timer Operation

When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.

Sleep Timer Operation

When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli- ance operation, the operation of the appliance stops.

While the appliance is on pause, the sleep timer mode cannot be input.

While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.

When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.

When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.

Chaos Swing Mode

By the Chaos Swing key input, the louvers vane automatically operate with the Chaos Swing or they are fixed to the desired direction.

While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

< Cooling Mode >

< Heating Mode >

CLOSED

OPEN

CLOSED

OPEN

Jet Cool Mode Operation (C/O Model)

If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.

In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C

When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.

During the JET COOL function at any moment, the A/C starts to blow the cool air with side louvers closed at extremely high speed for 30 minutes setting the room temp. automatically to 18°C.

-15-

Image 15
Contents Room Air Conditioner Contents Code Type Code of Model Meaning Details of 2003 LG Model NameIndoor Unit FunctionsSetting the Time or Timer Timer Selection Operation ON/OFF Operation Mode SelectionRoom, Temperature Checking Temperature SettingLSC183VMA Product ReferencesDimensions Indoor UnitIndoor Unit Gas side Outdoor Unit 18KCooling Only Models Refrigeration Cycle Diagram18K Cooling Only Models Wiring DiagramCooling Mode Operation Healthy Dehumidification ModeOperation Details Defrost Control Heating Mode OperationFuzzy Operation C/O Model Fuzzy Operation H/P ModelFuzzy Operation for Cooling Fuzzy Operation for Heating On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationChaos Swing Mode Off-Timer OperationOff-Timer ↔ On-Timer Operation Sleep Timer OperationTest operation Jet Cool Mode Operation H/P ModelRemote Control Operation Mode Forced OperationHeating Model Compressor on IndicatorDisplay Function Self-diagnosis FunctionPiping length and elevation InstallationInstallation of indoor, Outdoor unit Select the best locationDrain hose junction Preparing work for InstallationOpen panel front Cover pipe and cover side removeHow to fix installation plate Flaring Work and Connection of Piping Flaring workConnection of piping Indoor Wrap the insulation material around the connecting portion Indoor unit installationFor right piping. Follow the instruction below Installation Information For right piping Good caseBad case Connection of the pipes-OutdoorConnection of the cable Connecting The Cable Between Indoor Unit and Outdoor UnitFor strand wiring Connection method of the connecting cableExampleTo check the drainage Checking the Drainage and forming the pipingsChecking the drainage Form the pipingConnect the cable to the indoor unit Circuit Breaker Use a circuit breaker or time delay fusePreparation Air PurgingAir purging Air purging with vacuum pumpFinishing the job EvacuationDrive three screws Panel Front AssemblySettlement of outdoor unit Prepare remote controlPump Down Procedure Test RunningOperation Name and Function-Remote ControlTo remove the Control Box To remove the Grille from the ChassisTo remove the Evaporator Before removing the Turbo FanTo remove the Motor Way Valve Liquid Side Way, 3-way ValvePurge the air from the system ProcedureAir purging Check for gas leakagePumping down Air purging of the charge hoseSet the 2-way valve to the closed position Re-air purging Gas leakage Balance refrigerant of the 2-way, 3-way valvesAll amount of refrigerant leaked EvacuationPurge the air from the charge hose Gas ChargingAfter Evacuation Connect the charge hose to the charging cylinderTrouble analysis Cycle Troubleshooting GuideYES Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive Check connecting condition of the CN-MOTOR Connector When Indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Voltage of Connectors according to No. of pinsIndoor Fan Speed Main PWB ASSYIndoor Unit Electronic Control DeviceModel Main PWB ASSYOutdoor UnitDisplay PWB Assembly SUB PCB ASM Indoor UnitMicom Outdoor UnitExploded View and Replacement Parts List Location Description Remarks LSC183VMA Parts ListindoorW0CZZ Outdoor unit18KLocation Description QTY Remarks LSC183VMA Parts ListoutdoorMemo Memo August