1. Air purging
Required tools : hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints, and gas leak detector.
The additional gas for air purging has been charged in the outdoor unit.
However, if the flare connections have not be done correctly and there gas leaks, a gas cylinder and the charge set will be needed.
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity, and could lead to a malfunction.
Indoor unit | Liquid side |
|
|
| |
| Open | Outdoor unit |
|
| |
| valve |
|
| Gas side |
|
| Clsed |
|
|
| |
| valve |
|
Service port nut:
Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
*CAUTION : Do not leak the gas in the air during Air purging.
• Procedure
(1)Recheck the piping connections.
(2)Open the valve stem of the
–Be sure to use a hexagonal wrench to operate the valve stem.
(3)Check for gas leakage.
–Check the flare connections for gas leakage.
(4)Purge the air from the system.
–Set the
–Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute. Repeat this three times.
(5)Use torque wrench to tighten the service port nut to a torque of 1.8kg.cm.
(6)Set the
(7)Mount the valve stem nuts to the
(8)Check for gas leakage.
–At this time, especially check for gas leakage from the
Caution
If gas leakage are discovered in step (3) above, take the following mesures :
If the gas leaks stop when the piping connections are tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.