■Jet Cool Mode Operation (H/P Model)
•While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
•In the Jet Cool mode, the indoor fan is operated at
•In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
•When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
•During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at extremely high speed for 60 minutes setting the room temp. automatically to 30°C.
■Forced Operation
•Operation procedures when the remote control can't be used.
•The operation will be started if the power button is pressed.
•If you want to stop operation,
| Cooling Model |
| Heat pump Model |
|
|
|
|
| |
|
| Room Temp. ≥ 24°C | 21°C ≤ Room Temp. < 24°C | Room Temp. < 21°C |
|
|
|
|
|
Operating mode | Cooling | Cooling | Healthy Dehumidification | Heating |
|
|
|
|
|
Indoor FAN Speed | High | High | High | High |
|
|
|
|
|
Setting Temperature | 22°C | 22°C | 23°C | 24°C |
|
|
|
|
|
•While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
■Test operation
•During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem- perature and resets in 18±1 minutes.
•During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.
•If you want to stop the operation,
■Auto restart
•In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.
■Remote Control Operation Mode
•When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control.
■Protection of the evaporator pipe from frosting
•If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool- ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
•When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
■Buzzer Sounding Operation
•When the
•When the
•When a key is input by the remote control while the slide switch on the main unit of the appliance is on the forced operation position, the error sound