LG Electronics LSC183VMA service manual Re-air purging

Page 38

1) Re-air purging

(Re-installation)

Indoor unit

Liquid side

 

Closed

Outdoor unit

2-Way valve

Gas side

Closed

3-Way valve

Gas cylinder

Lo

R22

OPEN

CLOSE

• Procedure

(1)Confirm that both the 2-way valve and the 3- way valve are set to the closed position.

(2)Connect the charge set and a gas cylinder to the service port of the 3-way valve.

Leave the valve on the gas cylinder closed.

(3)Air purging.

Open the valves on the gas cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.

After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.

(4)Check for gas leakage.

Check the flare connections for gas leakage.

(5)Discharge the refrigerant.

Close the valve on the gas cylinder and discharge the refrigerant until the gauge indicates 3 to 5 kg/cm2g.

(6)Disconnect the charge set and the gas cylinder, and set the 2-way and 3-way valves to the open position.

Be sure to use a hexagonal wrench to operate the valve stems.

(7)Mount the valve stem nuts and the service port nut.

Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.

Be sure to check for gas leakage.

* CAUTION:

Do not leak the gas in the air during Air Purging.

-38-

Image 38
Contents Room Air Conditioner Contents Details of 2003 LG Model Name Code Type Code of Model MeaningFunctions Indoor UnitTemperature Setting Operation ON/OFF Operation Mode SelectionRoom, Temperature Checking Setting the Time or Timer Timer SelectionProduct References LSC183VMAIndoor Unit DimensionsIndoor Unit Outdoor Unit 18K Gas sideRefrigeration Cycle Diagram Cooling Only ModelsWiring Diagram 18K Cooling Only ModelsOperation Details Cooling Mode OperationHealthy Dehumidification Mode Heating Mode Operation Defrost ControlFuzzy Operation for Cooling Fuzzy Operation C/O ModelFuzzy Operation H/P Model Fuzzy Operation for Dehumidification On-Timer OperationAirflow Speed Selection Fuzzy Operation for HeatingSleep Timer Operation Off-Timer OperationOff-Timer ↔ On-Timer Operation Chaos Swing ModeForced Operation Jet Cool Mode Operation H/P ModelRemote Control Operation Mode Test operationSelf-diagnosis Function Compressor on IndicatorDisplay Function Heating ModelSelect the best location InstallationInstallation of indoor, Outdoor unit Piping length and elevationCover pipe and cover side remove Preparing work for InstallationOpen panel front Drain hose junctionHow to fix installation plate Connection of piping Indoor Flaring Work and Connection of PipingFlaring work Indoor unit installation Wrap the insulation material around the connecting portionConnection of the pipes-Outdoor Installation Information For right piping Good caseBad case For right piping. Follow the instruction belowConnecting The Cable Between Indoor Unit and Outdoor Unit Connection of the cableConnection method of the connecting cableExample For strand wiringForm the piping Checking the Drainage and forming the pipingsChecking the drainage To check the drainageCircuit Breaker Use a circuit breaker or time delay fuse Connect the cable to the indoor unitAir purging with vacuum pump Air PurgingAir purging PreparationEvacuation Finishing the jobPanel Front Assembly Drive three screwsTest Running Prepare remote controlPump Down Procedure Settlement of outdoor unitName and Function-Remote Control OperationTo remove the Grille from the Chassis To remove the Control BoxTo remove the Motor To remove the EvaporatorBefore removing the Turbo Fan Way, 3-way Valve Way Valve Liquid SideCheck for gas leakage ProcedureAir purging Purge the air from the systemSet the 2-way valve to the closed position Pumping downAir purging of the charge hose Re-air purging Balance refrigerant of the 2-way, 3-way valves Gas leakageEvacuation All amount of refrigerant leakedConnect the charge hose to the charging cylinder Gas ChargingAfter Evacuation Purge the air from the charge hoseCycle Troubleshooting Guide Trouble analysisYES Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive When Indoor Fan does not operate Check connecting condition of the CN-MOTOR ConnectorWhen Vertical Louver does not operate When a comunication error occurs Phenomena in case of connecting error Indoor UnitOutdoor Unit Indoor Fan Speed Voltage of Connectors according toNo. of pins Electronic Control Device Main PWB ASSYIndoor UnitMain PWB ASSYOutdoor Unit ModelDisplay PWB Assembly Indoor Unit SUB PCB ASMOutdoor Unit MicomExploded View and Replacement Parts List Parts Listindoor Location Description Remarks LSC183VMAOutdoor unit18K W0CZZParts Listoutdoor Location Description QTY Remarks LSC183VMAMemo Memo August