Page 43

2.Product does not operate at all.

(* Refer to Electronic Control Device drawing and Schematic diagram.)

Turn off Main Power

(After 10 seconds)

Turn on Main Power

Does "beeping" sound is made from the Indoor Unit?

NO

Check the voltage of power(About AC 208V/AC230V, 60Hz)

Main power's voltage

Voltage applied to the unit

Connecting method of Indoor/Outdoor connecting cable

Check PWB Ass'y(Outdoor unit)

-Fuse

-Pattern damage

-Varistor(ZNRI)

Check the connection housing for contacting

Connector related to CN-POWER

Connector related to CN-FAN

Connector contacting of Outdoor Fan/Compressor

Display PWB Ass'y Check

Connector related to CN-DC/DC

YES

Primarily, the operating condition of Micom is OK.

Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector(including connecting cable of Indoor/Outdoor Unit)

PCB Board Operation Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Items

 

 

 

Content

 

 

 

Remedy

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Power Transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

- Input Voltage

 

 

- About AC208V/230V±10% - Check the power voltage

 

 

 

• Replace Trans

 

 

 

- Output Voltage

 

 

- About AC17±3V

 

 

 

 

 

 

 

• IC2(7812) Output

 

 

• DC +12V

 

 

 

• Replace IC2

 

 

 

(Indoor/Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

• IC3(7805) Output

 

 

• DC +5V

 

 

 

• Replace IC3

 

 

 

(Indoor/Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

• IC4(KIA7036, Reset IC)

 

 

• Voltage of Outdoor unit Micom No. 8,

 

 

 

• Replace faulty parts

 

 

 

OSC01B(4MHz)

 

 

Voltage of Indoor unit Micom No. 43 and soldering

 

 

 

 

 

 

 

(Indoor/Outdoor unit)

 

 

condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 43 -

Image 43
Contents Room Air Conditioner Contents Code Type Code of Model Meaning Details of 2003 LG Model NameIndoor Unit FunctionsSetting the Time or Timer Timer Selection Operation ON/OFF Operation Mode SelectionRoom, Temperature Checking Temperature SettingLSC183VMA Product ReferencesIndoor Unit DimensionsIndoor Unit Gas side Outdoor Unit 18KCooling Only Models Refrigeration Cycle Diagram18K Cooling Only Models Wiring DiagramHealthy Dehumidification Mode Cooling Mode OperationOperation Details Defrost Control Heating Mode OperationFuzzy Operation H/P Model Fuzzy Operation C/O ModelFuzzy Operation for Cooling Fuzzy Operation for Heating On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationChaos Swing Mode Off-Timer OperationOff-Timer ↔ On-Timer Operation Sleep Timer OperationTest operation Jet Cool Mode Operation H/P ModelRemote Control Operation Mode Forced OperationHeating Model Compressor on IndicatorDisplay Function Self-diagnosis FunctionPiping length and elevation InstallationInstallation of indoor, Outdoor unit Select the best locationDrain hose junction Preparing work for InstallationOpen panel front Cover pipe and cover side removeHow to fix installation plate Flaring work Flaring Work and Connection of PipingConnection of piping Indoor Wrap the insulation material around the connecting portion Indoor unit installationFor right piping. Follow the instruction below Installation Information For right piping Good caseBad case Connection of the pipes-OutdoorConnection of the cable Connecting The Cable Between Indoor Unit and Outdoor UnitFor strand wiring Connection method of the connecting cableExampleTo check the drainage Checking the Drainage and forming the pipingsChecking the drainage Form the pipingConnect the cable to the indoor unit Circuit Breaker Use a circuit breaker or time delay fusePreparation Air PurgingAir purging Air purging with vacuum pumpFinishing the job EvacuationDrive three screws Panel Front AssemblySettlement of outdoor unit Prepare remote controlPump Down Procedure Test RunningOperation Name and Function-Remote ControlTo remove the Control Box To remove the Grille from the ChassisBefore removing the Turbo Fan To remove the EvaporatorTo remove the Motor Way Valve Liquid Side Way, 3-way ValvePurge the air from the system ProcedureAir purging Check for gas leakageAir purging of the charge hose Pumping downSet the 2-way valve to the closed position Re-air purging Gas leakage Balance refrigerant of the 2-way, 3-way valvesAll amount of refrigerant leaked EvacuationPurge the air from the charge hose Gas ChargingAfter Evacuation Connect the charge hose to the charging cylinderTrouble analysis Cycle Troubleshooting GuideYES Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive Check connecting condition of the CN-MOTOR Connector When Indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit No. of pins Voltage of Connectors according toIndoor Fan Speed Main PWB ASSYIndoor Unit Electronic Control DeviceModel Main PWB ASSYOutdoor UnitDisplay PWB Assembly SUB PCB ASM Indoor UnitMicom Outdoor UnitExploded View and Replacement Parts List Location Description Remarks LSC183VMA Parts ListindoorW0CZZ Outdoor unit18KLocation Description QTY Remarks LSC183VMA Parts ListoutdoorMemo Memo August