3. Connecting The Cable Between Indoor Unit and Outdoor Unit

1) Connection of the cable

1.

Remove the cover control from the unit

 

by loosening the 3 screws.

2.

Dismount caps on the conduit panel.

Wiring Diagram

Connecting cable(Low voltage) b

3.

Temporarily mount the conduit tubes on

 

the conduit panel.

4.

Properly connect both the power supply

 

and low voltage lines to the

 

corresponding terminals on the terminal

 

block.

5.

Ground the unit in accordance with local

 

codes.

6.

Be sure to size each wire allowing

 

several inches longer than the required

 

length for wiring.

Indoor Unit

Outdoor Unit

Terminal

Terminal

(4P)

(6P)

1

 

1

2

 

2

3

 

3

4

 

4

 

L1* 5

 

L2

6

G

*L1 is neutral for 115V models.

Power supply a

To branch circuit

Ground

7. Use lock nuts to secure the conduit

tubes.

NOTE

Connector trade size for this unit is 1/2". Refer to "How to connect wiring to the terminals" for instructions on connecting depending on the wire type you are using.

WARNING

NOTE

1.

shows field wiring.

2.Separately wire the high and low voltage line.

3.Use heat-proof electrical wiring capable of withstanding temperatures up to 167° F.

4.Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit.

(For example, Type SJO-WA)

Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).

Every wire must be connected firmly.

No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.

Power Supply

Model

Power source

AWG(MIN.)

Fuse or breaker

 

 

Capacity

 

 

18K

1ø , 208/230V

14

18

20A

 

 

 

 

 

Outdoor unit

Terminal block

Over 5mm (2")

Cover control

Conduit panel

Connecting cable

Power supply cord

-24-

Image 24
Contents Room Air Conditioner Contents Details of 2003 LG Model Name Code Type Code of Model MeaningFunctions Indoor UnitOperation ON/OFF Operation Mode Selection Room, Temperature CheckingTemperature Setting Setting the Time or Timer Timer SelectionProduct References LSC183VMADimensions Indoor UnitIndoor Unit Outdoor Unit 18K Gas sideRefrigeration Cycle Diagram Cooling Only ModelsWiring Diagram 18K Cooling Only ModelsCooling Mode Operation Healthy Dehumidification ModeOperation Details Heating Mode Operation Defrost ControlFuzzy Operation C/O Model Fuzzy Operation H/P ModelFuzzy Operation for Cooling On-Timer Operation Airflow Speed SelectionFuzzy Operation for Dehumidification Fuzzy Operation for HeatingOff-Timer Operation Off-Timer ↔ On-Timer OperationSleep Timer Operation Chaos Swing ModeJet Cool Mode Operation H/P Model Remote Control Operation ModeForced Operation Test operationCompressor on Indicator Display FunctionSelf-diagnosis Function Heating ModelInstallation Installation of indoor, Outdoor unitSelect the best location Piping length and elevationPreparing work for Installation Open panel frontCover pipe and cover side remove Drain hose junctionHow to fix installation plate Flaring Work and Connection of Piping Flaring workConnection of piping Indoor Indoor unit installation Wrap the insulation material around the connecting portionInstallation Information For right piping Good case Bad caseConnection of the pipes-Outdoor For right piping. Follow the instruction belowConnecting The Cable Between Indoor Unit and Outdoor Unit Connection of the cableConnection method of the connecting cableExample For strand wiringChecking the Drainage and forming the pipings Checking the drainageForm the piping To check the drainageCircuit Breaker Use a circuit breaker or time delay fuse Connect the cable to the indoor unitAir Purging Air purgingAir purging with vacuum pump PreparationEvacuation Finishing the jobPanel Front Assembly Drive three screwsPrepare remote control Pump Down ProcedureTest Running Settlement of outdoor unitName and Function-Remote Control OperationTo remove the Grille from the Chassis To remove the Control BoxTo remove the Evaporator Before removing the Turbo FanTo remove the Motor Way, 3-way Valve Way Valve Liquid SideProcedure Air purgingCheck for gas leakage Purge the air from the systemPumping down Air purging of the charge hoseSet the 2-way valve to the closed position Re-air purging Balance refrigerant of the 2-way, 3-way valves Gas leakageEvacuation All amount of refrigerant leakedGas Charging After EvacuationConnect the charge hose to the charging cylinder Purge the air from the charge hoseCycle Troubleshooting Guide Trouble analysisYES Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive When Indoor Fan does not operate Check connecting condition of the CN-MOTOR ConnectorWhen Vertical Louver does not operate When a comunication error occurs Phenomena in case of connecting error Indoor UnitOutdoor Unit Voltage of Connectors according to No. of pinsIndoor Fan Speed Electronic Control Device Main PWB ASSYIndoor UnitMain PWB ASSYOutdoor Unit ModelDisplay PWB Assembly Indoor Unit SUB PCB ASMOutdoor Unit MicomExploded View and Replacement Parts List Parts Listindoor Location Description Remarks LSC183VMAOutdoor unit18K W0CZZParts Listoutdoor Location Description QTY Remarks LSC183VMAMemo Memo August