Cycle Troubleshooting Guide

1. Trouble analysis

1. Check temperature difference between intake and discharge air and operating current.

Temp. Difference

Operating Current

Temp. difference

:approx. 0°F

All amount of refrigerant leaked out.

Current

:less than 80% of

Check refrigeration cycle.

 

rated current

 

 

 

 

Refrigerant leakage

 

 

Temp. difference

:approx. 8°C(14°F)

Current

:less than 80% of

Clog of refrigeration cycle

 

rated current

Defective compressor

 

 

 

 

 

 

Temp. difference

:less than 8°C(14°F)

 

Current

:less than 80% of

Excessive amount of refrigerant

 

rated current

 

 

 

 

 

 

 

Temp. difference

:over 8°C(14°F)

Normal

 

 

 

Notice:

Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure

Temperature

 

 

(Compared with the

(Compared with the

Cause of Trouble

Description

normal value)

normal value)

 

 

 

 

 

 

 

High

Defective compressor

Current is low.

 

Defective 4-way reversing valve

Higher

 

 

 

 

 

Normal

Excessive amount of refrigerant

High pressure does not quickly

 

 

rise at the beginning of operation.

 

 

 

 

 

 

 

 

 

Insufficient amount of

Current is low.

Lower

Higher

refrigerant(Leakage)

 

 

 

Clogging

Current is low.

 

 

 

 

Notice:

1.The suction pressure is usually 4.5~5.0 kg/cm2G at normal condition.

2.The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.

- 42 -

Image 42
Contents Room Air Conditioner Contents Details of 2003 LG Model Name Code Type Code of Model MeaningFunctions Indoor UnitTemperature Setting Operation ON/OFF Operation Mode SelectionRoom, Temperature Checking Setting the Time or Timer Timer SelectionProduct References LSC183VMADimensions Indoor UnitIndoor Unit Outdoor Unit 18K Gas sideRefrigeration Cycle Diagram Cooling Only ModelsWiring Diagram 18K Cooling Only ModelsCooling Mode Operation Healthy Dehumidification ModeOperation Details Heating Mode Operation Defrost ControlFuzzy Operation C/O Model Fuzzy Operation H/P ModelFuzzy Operation for Cooling Fuzzy Operation for Dehumidification On-Timer OperationAirflow Speed Selection Fuzzy Operation for HeatingSleep Timer Operation Off-Timer OperationOff-Timer ↔ On-Timer Operation Chaos Swing ModeForced Operation Jet Cool Mode Operation H/P ModelRemote Control Operation Mode Test operationSelf-diagnosis Function Compressor on IndicatorDisplay Function Heating ModelSelect the best location InstallationInstallation of indoor, Outdoor unit Piping length and elevationCover pipe and cover side remove Preparing work for InstallationOpen panel front Drain hose junctionHow to fix installation plate Flaring Work and Connection of Piping Flaring workConnection of piping Indoor Indoor unit installation Wrap the insulation material around the connecting portionConnection of the pipes-Outdoor Installation Information For right piping Good caseBad case For right piping. Follow the instruction belowConnecting The Cable Between Indoor Unit and Outdoor Unit Connection of the cableConnection method of the connecting cableExample For strand wiringForm the piping Checking the Drainage and forming the pipingsChecking the drainage To check the drainageCircuit Breaker Use a circuit breaker or time delay fuse Connect the cable to the indoor unitAir purging with vacuum pump Air PurgingAir purging PreparationEvacuation Finishing the jobPanel Front Assembly Drive three screwsTest Running Prepare remote controlPump Down Procedure Settlement of outdoor unitName and Function-Remote Control OperationTo remove the Grille from the Chassis To remove the Control BoxTo remove the Evaporator Before removing the Turbo FanTo remove the Motor Way, 3-way Valve Way Valve Liquid SideCheck for gas leakage ProcedureAir purging Purge the air from the systemPumping down Air purging of the charge hoseSet the 2-way valve to the closed position Re-air purging Balance refrigerant of the 2-way, 3-way valves Gas leakageEvacuation All amount of refrigerant leakedConnect the charge hose to the charging cylinder Gas ChargingAfter Evacuation Purge the air from the charge hoseCycle Troubleshooting Guide Trouble analysisYES Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive When Indoor Fan does not operate Check connecting condition of the CN-MOTOR ConnectorWhen Vertical Louver does not operate When a comunication error occurs Phenomena in case of connecting error Indoor UnitOutdoor Unit Voltage of Connectors according to No. of pinsIndoor Fan Speed Electronic Control Device Main PWB ASSYIndoor UnitMain PWB ASSYOutdoor Unit ModelDisplay PWB Assembly Indoor Unit SUB PCB ASMOutdoor Unit MicomExploded View and Replacement Parts List Parts Listindoor Location Description Remarks LSC183VMAOutdoor unit18K W0CZZParts Listoutdoor Location Description QTY Remarks LSC183VMAMemo Memo August