LG Electronics LSC183VMA service manual When Vertical Louver does not operate

Page 47

6.When Vertical Louver does not operate.

Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.

If the regular torque is detected when rotating the Vertical Louver with hands Normal

Check the connecting condition of CN-U/D, CN-L/R Connector

Check the soldering condition(on PWB) of CN-U/D, CN-L/R Connector

Check the operating circuit of the Vertical Louver

Confirm that there is DC +12V between pin(RED) of CN-U/D, CN-L/R and GND.

Confirm that there is a soldering short at following terminals.

-Between 62 , 61 , 60 and 59 of MICOM

-Between 57 , 56 , 55 and 54 of MICOM

-Between 51 , 50 , 49 and 48 of MICOM

- Between 1 , 2 , 3 , 4 and 5 of CN-U/D, CN-L/R

If there are no problems after above checks

Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver

- 47 -

Image 47
Contents Room Air Conditioner Contents Code Type Code of Model Meaning Details of 2003 LG Model NameIndoor Unit FunctionsSetting the Time or Timer Timer Selection Operation ON/OFF Operation Mode SelectionRoom, Temperature Checking Temperature SettingLSC183VMA Product ReferencesIndoor Unit DimensionsIndoor Unit Gas side Outdoor Unit 18KCooling Only Models Refrigeration Cycle Diagram18K Cooling Only Models Wiring DiagramOperation Details Cooling Mode OperationHealthy Dehumidification Mode Defrost Control Heating Mode OperationFuzzy Operation for Cooling Fuzzy Operation C/O ModelFuzzy Operation H/P Model Fuzzy Operation for Heating On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationChaos Swing Mode Off-Timer OperationOff-Timer ↔ On-Timer Operation Sleep Timer OperationTest operation Jet Cool Mode Operation H/P ModelRemote Control Operation Mode Forced OperationHeating Model Compressor on IndicatorDisplay Function Self-diagnosis FunctionPiping length and elevation InstallationInstallation of indoor, Outdoor unit Select the best locationDrain hose junction Preparing work for InstallationOpen panel front Cover pipe and cover side removeHow to fix installation plate Connection of piping Indoor Flaring Work and Connection of PipingFlaring work Wrap the insulation material around the connecting portion Indoor unit installationFor right piping. Follow the instruction below Installation Information For right piping Good caseBad case Connection of the pipes-OutdoorConnection of the cable Connecting The Cable Between Indoor Unit and Outdoor UnitFor strand wiring Connection method of the connecting cableExampleTo check the drainage Checking the Drainage and forming the pipingsChecking the drainage Form the pipingConnect the cable to the indoor unit Circuit Breaker Use a circuit breaker or time delay fusePreparation Air PurgingAir purging Air purging with vacuum pumpFinishing the job EvacuationDrive three screws Panel Front AssemblySettlement of outdoor unit Prepare remote controlPump Down Procedure Test RunningOperation Name and Function-Remote ControlTo remove the Control Box To remove the Grille from the ChassisTo remove the Motor To remove the EvaporatorBefore removing the Turbo Fan Way Valve Liquid Side Way, 3-way ValvePurge the air from the system ProcedureAir purging Check for gas leakageSet the 2-way valve to the closed position Pumping downAir purging of the charge hose Re-air purging Gas leakage Balance refrigerant of the 2-way, 3-way valvesAll amount of refrigerant leaked EvacuationPurge the air from the charge hose Gas ChargingAfter Evacuation Connect the charge hose to the charging cylinderTrouble analysis Cycle Troubleshooting GuideYES Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive Check connecting condition of the CN-MOTOR Connector When Indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Indoor Fan Speed Voltage of Connectors according toNo. of pins Main PWB ASSYIndoor Unit Electronic Control DeviceModel Main PWB ASSYOutdoor UnitDisplay PWB Assembly SUB PCB ASM Indoor UnitMicom Outdoor UnitExploded View and Replacement Parts List Location Description Remarks LSC183VMA Parts ListindoorW0CZZ Outdoor unit18KLocation Description QTY Remarks LSC183VMA Parts ListoutdoorMemo Memo August