Bradford-White Corp M430T, CX) Service Procedure RG-II, Thermocouple Testing and Replacement

Page 8

SERVICE PROCEDURE RG-II

Thermocouple Testing and Replacement

CLOSED CIRCUIT THERMOCOUPLE TESTING (White Rodgers Control)

Step 1. Closed circuit testing is the preferred method for testing thermocouple. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minuets. If the pilot will not stay lit, hold the pilot button (located on the combination thermostat/gas valve) down during this test

Step 2. Using a multimeter capable of measuring millivolts, connect one lead

using an alligator clip to the copper sheath of the thermocouple, use the second lead of the multi meter to probe the top terminal located at the back of the combination thermostat/gas valve.

Step 3. If meter reads 10 millivolts or higher, the thermocouple is OK. If reading is below 10 millivolts, replace the thermocouple.

Probe top terminal on back of combination

thermostat/gas valve

Alligator clip to copper sheath of thermocouple

CLOSED CIRCUIT THERMOCOUPLE TESTING (Robertshaw Control)

Step 1. Disconnect thermocouple from combination thermostat/gas valve.

Step 2. Connect a thermocouple adaptor

(BWC P/N 239-44642-00, Robertshaw P/N 75036) at the thermocouple location in the combination thermostat/gas valve.

Step 3. Reconnect thermocouple to adaptor. Make certain all connections are tight (finger tight plus ¼ turn)

Step 4 Using a multimeter capable of measuring millivolts, connect one alligator clip to the set screw of the adaptor, and the other alligator clip to copper portion of the thermocouple.

Step 5. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minuets. If the pilot will not stay lit, hold the red reset button (located on the combination thermostat/gas valve) down during this test

Step 6. If meter reads 13 millivolts or higher, the thermocouple is OK. If reading is below 13 millivolts replace the thermocouple.

9

Image 8
Contents MI60T*FBN,CX M2XR504T*FBN,CX M2C504T*FBN,CX 50T65FBN,CX MI30T*FBN,CX M430T*FBN,CXMI50L*FBN,CX M1XR403S*FBN,CX MI504S*FBN,CX M1XR504T*FBN,CX Table of Contents Bradford White Defender Safety System IntroductionTroubleshooting Chart Flammable Vapor Ignition Resistant Water HeatersService Procedure RG-I Proceed to Inner Door Gasket Replacement ProcedureFollowed exactly, a fire or explosion may result causing If the information in these instructions is notInstallation of Inner Door With Gasket Replace outer jacket burner access door Service Procedure RG-II Thermocouple Testing and ReplacementClosed Circuit Thermocouple Testing White Rodgers Control Closed Circuit Thermocouple Testing Robertshaw ControlOpen Circuit Thermocouple Testing Thermocouple ReplacementService Procedure RG-III Pilot Assembly Inspection, Cleaning and ReplacementPiezo IGNITER, Electrode Testing and Replacement Service Procedure RG-IVPiezo Igniter, Electrode Testing and Replacement Service Procedure RG-V Combination Thermostat/Gas Valve Testing ReplacementCombination Thermostat/Gas Valve Testing and Replacement Line PressureMagnet Assembly Testing Robertshaw Control Thermocouple TestingMagnet Assembly Testing White Rodgers Control ECO Energy Cut Off Testing Combination THERMOSTAT/GAS Valve ReplacementWrench Boss Personal injury or death Explosion causing property damageSeal breach may result in a fire or Cast Iron Burner Adjustment Service Procedure RG-VIMain Burner Inspection, Adjustment Cleaning and Replacement Feedline Burner Cleaning Resettable Thermal Switch Continuity Testing Service Procedure RG-VIIResetting Thermal Switch Testing and Replacement Resettable Thermal Switch Replacement Over Tighten ScrewsScreenLok Flame Arrestor Cleaning Service Procedure RG-VIIIScreenLok Flame Arrestor Cleaning DIP Tube Inspection and Replacement Service Procedure RG-IXDip Tube and Anode Inspection and Replacement Anode Inspection and Replacement Parts List Page Page Fax/215-641-1612