(3)Indoor unit and remote controller.(OPTION:PAC-204RC) Connect the wires on the basis of the following wiring diagram.

PEH-5, PE(H)-7,8,10

 

 

 

 

GRAY

TB4

1

 

 

 

F2

 

24VAC(L)

 

 

 

(3.15A)

 

 

 

Tr

 

24VAC(N)

 

 

 

 

 

 

AC

AC24V

COMP1

 

FAN HI

 

 

 

 

220

 

 

TB4

2

3

240V

 

 

 

 

 

 

 

 

 

 

CZ1

FZ

 

GRAY

 

 

 

 

 

 

 

4

 

 

PE(H)-15,20

 

 

 

 

 

 

GRAY

TB3

1

 

 

 

 

F2

 

24VAC(L) COMP1

 

 

 

 

(3.15A)

 

 

 

 

Tr

 

24VAC(N)

 

 

 

AC

AC24V

 

COMP2

FAN HI

 

 

 

 

 

220

 

 

TB3

2

3

4

240V

 

 

 

 

 

 

 

 

 

 

 

CZ

CZ

FZ

 

 

 

1-1

1-2

 

 

GRAY

 

 

 

 

 

 

 

 

5

 

 

 

(4) Wiring example (For metal piping)

 

Power

Breaker

Over current

Earth cable

Control

 

 

cable

 

capacity

protection switch

wiring

 

 

 

 

 

 

 

PEH - 5

2.0mm2

15A

15A

2.0mm2 over

 

 

PE(H) - 7

2.0mm2

15A

15A

2.0mm 2 over

 

 

PE(H) - 8

2.0mm2

15A

15A

2.0mm 2 over

Cable or

 

 

 

 

 

 

 

 

 

 

wire of

 

PE(H) -10

2.0mm2

15A

15A

2.0mm 2over

0.75mm2

 

 

 

 

 

 

(24VDC)

 

PE(H) -15

2.0mm2

30A

30A

2.0mm 2 over

 

PE(H) -20

2.0mm 2

30A

30A

2.0mm 2 over

 

 

PUH - 5

8mm 2

 

50A

50A

8mm 2 over

 

 

PU(H) - 7

8mm 2

 

50A

50A

8mm 2 over

Cable or

The grounding wire must be of the same

 

 

 

 

 

 

 

 

 

diameter as the power cable wires.

PU(H) - 8

8mm

2

 

50A

50A

2

 

 

 

 

8mm over

wire of 2

Table above is an example.

 

 

 

 

 

 

2

 

 

 

2

 

PU(H) -10

14mm

60A

60A

14mm

over

0.75mm

The selection of other capacities should be

 

 

(24VDC)

PU(H) -15

14mm 2

100A

100A

14mm2 over

 

determined in accordance with the relevant

 

 

 

 

 

 

standards.

PU(H) -20

22mm 2

125A

125A

22mm2 over

 

(5) Selecting earth leakage breaker (NV)

To select NF or NV instead of a combination of Class B fuse switch use the following. In the case of Class B fuse rated 15A.

 

Fuse

Earth leakage breaker

 

(class B)

(with over-load protection)

 

 

 

 

 

PEH - 5

15A

NV30-CA

15A

30mA 0.1s or less

 

 

 

 

 

PE(H) - 7

15A

NV30-CA

15A

30mA 0.1s or less

PE(H) - 8

15A

NV30-CA

15A

30mA 0.1s or less

 

 

 

 

 

PE(H) - 10

15A

NV30-CA

15A

30mA 0.1s or less

 

 

 

 

 

PE(H) -15

30A

NV50-CP

30A

30mA 0.1s or less

 

 

 

 

 

PE(H) -20

30A

NV50-CP

30A

30mA 0.1s or less

PUH - 5

50A

NV50-CA

50A

100mA 0.1s or less

PU(H) - 7

50A

NV50-CA

50A

100mA 0.1s or less

PU(H) - 8

50A

NV50-CA

50A

100mA 0.1s or less

 

 

 

 

 

PU(H) - 10

60A

NV60-CA

60A

100mA 0.1s or less

 

 

 

 

 

PU(H) - 15

100A

NV100-CP

100A

100mA 0.1s or less

 

 

 

 

 

PU(H) - 20

125A

NV225-CP

125A

100mA 0.1s or less

NV is a product of

MITSUBISHI ELECTRIC. Table above is an example. The selection of other capacities should be determined in accordance with the relevant standards.

Note.

All electrical wiring must be comply with local electrical authority regulations.

- 101 -

Image 102
Contents Data Book Contents Safety for USE For correct installationDo not wash the unit with water Complete Line UP Indoor unitOutdoor unit Features DescriptionsMechanical Specifications Typical Installation ExampleMODEL-DESIGNATION Breakdown 10 M Y CSpecifications PE-7~20MYC Cooling onlyPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump Electrical Data PE-7~20MYC-EUPEH-5,7,8MYA-EU HeatingPEH-10,15,20MYA-EU Selection Procedure Model Selection With actual examplesEfficiency Calculation Calculation of net capacityCapacity Tables Cooling Capacity Standard Air FlowFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU PEH-8MYA-EU Use for low ambient cooling partsPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EU Combined with PUH-8MYE-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Operation Range CoolingPE-7MYC-EU PEH-7MYA-EU FAN PerformancePEH-5MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-15MYC-EU PEH-15MYA-EU PE-20MYC-EU PEH-20MYA-EUPulley outside dimensions are shown below Unit mm Indoor units Sound DataPosition mesurement Outdoor unitsOutline Dimensions PEH-5PEH-7,8 28.6 PEH-10PEH-15 DRAINRc HOLES26PEH-20 Flange HOLES28Holes PUH-5PUH-7,8,10 Upper blow Holes 2-ø15 Ø19.053/4Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 PUH-8,10 Side blowPU-15 Cable Entry 44 Holes 2-ø15Ø28.61-1/8 Ø15.885/8 PU-20PUH-15,20 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply Wiring Diagrams PE-7MYC-EU StandardPE-8,10MYC-EU Standard Internal thermostat indoor fanOver current relayfanI/D,O/D PE-15MYC-EU Standard PE-20MYC-EU Standard TB1PE-7MYC-EU Special Order Anti Short Cycle Timer PE-8,10MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fanPE-15MYC-EU Special Order Anti Short Cycle Timer PE-20MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor52F1 Contactor fan I/D 23C Ambient temperaturePE-7MYC-EU Special Order LOW Ambient Cooling 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling PE-15MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relaysPE-20MYC-EU Special Order LOW Ambient Cooling Auxiliary relay fanI/D30FZ Auxiliary relay fanI/D PEH-5MYA-EU Standard MF2Way valve PEH-7MYA-EU StandardThermostat defrost Option controller connectionPEH-8,10MYA-EU Standard C1~7CR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat CR1 Surge killer Timer Anti short cycle PEH-8,10MYA-EUPEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling 52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 PEH-8,10MYA-EU Special Order LOW Ambient CoolingMF2 Fan motor outdoor CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26L63H1,2 High-pressure switch 26L1,2 PEH-15,20MYA-EU Special Order LOW Ambient Cooling51F1~5 Electrical Operation Flow Charts PE-7,8,10MYC-EUPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU Refrigerant Schematics PE-7,8,10,15,20MYC-EUPEH-5,7,8,10,15,20MYA-EU Safety & Control Devices PE-7,8,10MYC-EU PE-15,20MYC-EUPEH-7,8,10MYA-EU Service ref Special OrderYear Physical Data PE-7,8,1015,20MYC-EUIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Installation Space required around unit Indoor unitOutdoor unit Service-panel Ceiling OverOver 500 PU-15 At a single installation Over Service PanelPreparation before installing Indoor unit Over Service-panelOver Service-panel 500 Nut Washer Installation of the unit Indoor unitOutdoor unit Nut M10 WasherDuct construction Lifting methodPiping connection Case of Brazing typeThrow away Fig By-pass tube Flange assy Extension pipe Valve knobPipe assy Extension pipe Use the attached new packing FigGood example Bad example Airtight test EvacuationAdditional refrigerant charge Drain piping Electric wiring Arrangement such as terminal block in control boxControl module of outdoor unit PUH-5, 8 Control module of outdoor unit PUH-7, 8 Terminal block for connection wiresPower supply wires Control module of outdoor unit PU-20Method for connecting electric wire 60A Protection switch50A Selection of other capacities should bePutting condition of the belt Before starting the Trial run=4.5mm Flexion loadW 1.4 2.2kg Outlet grille Instructions for USECheck points for operation Ceiling Ceiling Obstacle blocking air outletAdhesive Isopropyl MaintenanceFingermarks Neutral Grease Paste AlcoholTransfer of installation When beginning to use air conditioner againWhen the air conditioner is not to be used for a long time Transferring work, and constructionRegarding electric work Place for installationMaintenance and inspection Conseration of the noiseTrouble shooting At cooling, water which places to cooling pipingBefore starting operation HOW to Operate Option PAC-204RCDisplay section On / OFF Start an operationFor fan Selecting operation When selecting operationRoom temperature adjustment To change room temperature For coolingTimer Hold/Resume key Time settingDays timer key Clock keyTrouble shooting Error DisplaySpecification Guidelines Outdoor UnitMemo Mitsubishi Electric Corporation Data Book PE,PEH