Mitsubishi Electronics PEH-20MYA, PE-8MYC, PE-15MYC, PE-20MYC, PE-10MYC Good example Bad example

Page 96
Remove the cover (grommet) attached sheet metal at exit of heat exchanger pipe of indoor unit before connecting the local piping.
(This cover is protect the pipe from sheet metal edge at unit transportation.)
Please insulate liquid pipe & gas pipe (two places for each) with an insulated pipe of the attachment after connecting piping.
When the outdoor unit is higher.
B
When the outdoor unit is lower.
Install the unit where the refrigerant piping is shortest, the difference between the indoor unit and outdoor unit is smallest.
As pipes purchased in the market may contain dust, below them off with dry inlet gas.
Take care not to allow dust and water content to enter the piping during pipe processing or installing.
Minimize the number of bends, and make the bending
radius as long as possible. Always observe the restriction(allowable length, height
difference, pipe diameter) on the refrigerant piping. For soldering & brazing, use high-quality materials.
Never purge air with a refrigerant. Always use a vacuum pump for purging.
Provide proper insulation to the piping . Insufficient insulation cause poor cooling/heating performance or condensation drip, leading to unexpected trouble.
Do not insulate gas or low pressure pipe and liquid or high pressure pipe together.
For the connection of the refrigerant piping, leave the valve of the outdoor unit fully closed (as set before shipment), and no operate it until the connection between the indoor/outdoor units and refrigerant piping, refrigerant leak test and evacuation work have been completed. The maximum permissible values are shown below.
A
4. Refrigerant piping.
Extension piping and installation parts are field supply. Perform the work only after carefully reading the appropriate instructions.

Good example

 

 

 

Bad example

 

Insulating material

 

Finishing tape

 

Insulating material

Finishing tape

 

 

Liquid pipe

 

 

 

 

Liquid pipe

Gas pipe

 

Electric wire

 

 

Gas pipe

Electric wire

 

 

 

PEH-5

PE(H)-7

PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20

Dimension

A (m)

20

20

20

20

20

20

Dimension

B (m)

30

30

30

30

30

30

Number of bends

15

15

15

15

15

15

Total piping length (m)

50

50

50

50

50

50

Piping

Liquid pipe (mm)

12.7

15.88

15.88

15.88

2x15.88

2x15.88

size

Gas pipe (mm)

19.05

25.4

25.4

28.6

2x25.4

2x28.6

- 95 -

Image 96
Contents Data Book Contents Safety for USE For correct installationDo not wash the unit with water Complete Line UP Indoor unitOutdoor unit Features DescriptionsMechanical Specifications Typical Installation ExampleMODEL-DESIGNATION Breakdown 10 M Y CSpecifications PE-7~20MYC Cooling onlyPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump Electrical Data PE-7~20MYC-EUPEH-5,7,8MYA-EU HeatingPEH-10,15,20MYA-EU Selection Procedure Model Selection With actual examplesEfficiency Calculation Calculation of net capacityCapacity Tables Cooling Capacity Standard Air FlowFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU PEH-8MYA-EU Use for low ambient cooling partsPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EU Combined with PUH-8MYE-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Operation Range CoolingFAN Performance PEH-5MYA-EUPE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-15MYC-EU PEH-15MYA-EU PE-20MYC-EU PEH-20MYA-EUPulley outside dimensions are shown below Unit mm Sound Data Position mesurementIndoor units Outdoor unitsOutline Dimensions PEH-5PEH-7,8 PEH-10 PEH-1528.6 DRAINRc HOLES26PEH-20 Flange HOLES28PUH-5 PUH-7,8,10 Upper blowHoles Holes 2-ø15 Ø19.053/4PUH-8,10 Side blow PU-15Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 Cable Entry 44 Holes 2-ø15PU-20 PUH-15,20Ø28.61-1/8 Ø15.885/8 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply Wiring Diagrams PE-7MYC-EU StandardPE-8,10MYC-EU Standard Internal thermostat indoor fanOver current relayfanI/D,O/D PE-15MYC-EU Standard PE-20MYC-EU Standard TB1PE-7MYC-EU Special Order Anti Short Cycle Timer PE-8,10MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fanPE-15MYC-EU Special Order Anti Short Cycle Timer PE-20MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor23C Ambient temperature PE-7MYC-EU Special Order LOW Ambient Cooling52F1 Contactor fan I/D 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling PE-15MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relaysPE-20MYC-EU Special Order LOW Ambient Cooling Auxiliary relay fanI/D30FZ Auxiliary relay fanI/D PEH-5MYA-EU Standard MF2PEH-7MYA-EU Standard Thermostat defrostWay valve Option controller connectionPEH-8,10MYA-EU Standard C1~7CR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat CR1 Surge killer Timer Anti short cycle PEH-8,10MYA-EUPEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling PEH-8,10MYA-EU Special Order LOW Ambient Cooling MF2 Fan motor outdoor52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26L63H1,2 High-pressure switch 26L1,2 PEH-15,20MYA-EU Special Order LOW Ambient Cooling51F1~5 Electrical Operation Flow Charts PE-7,8,10MYC-EUPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU Refrigerant Schematics PE-7,8,10,15,20MYC-EUPEH-5,7,8,10,15,20MYA-EU Safety & Control Devices PE-7,8,10MYC-EU PE-15,20MYC-EUPEH-7,8,10MYA-EU Service ref Special OrderYear Physical Data PE-7,8,1015,20MYC-EUIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Installation Space required around unit Indoor unitOutdoor unit Service-panel Ceiling OverOver 500 PU-15 At a single installation Over Service PanelPreparation before installing Indoor unit Over Service-panelOver Service-panel 500 Installation of the unit Indoor unit Outdoor unitNut Washer Nut M10 WasherDuct construction Lifting methodPiping connection Case of Brazing typeValve knob Pipe assyThrow away Fig By-pass tube Flange assy Extension pipe Extension pipe Use the attached new packing FigGood example Bad example Airtight test EvacuationAdditional refrigerant charge Drain piping Electric wiring Arrangement such as terminal block in control boxControl module of outdoor unit PUH-5, 8 Terminal block for connection wires Power supply wiresControl module of outdoor unit PUH-7, 8 Control module of outdoor unit PU-20Method for connecting electric wire Protection switch 50A60A Selection of other capacities should bePutting condition of the belt Before starting the Trial run=4.5mm Flexion loadW 1.4 2.2kg Instructions for USE Check points for operationOutlet grille Ceiling Ceiling Obstacle blocking air outletMaintenance Fingermarks Neutral GreaseAdhesive Isopropyl Paste AlcoholWhen beginning to use air conditioner again When the air conditioner is not to be used for a long timeTransfer of installation Transferring work, and constructionPlace for installation Maintenance and inspectionRegarding electric work Conseration of the noiseTrouble shooting At cooling, water which places to cooling pipingHOW to Operate Option PAC-204RC Display sectionBefore starting operation On / OFF Start an operationSelecting operation When selecting operation Room temperature adjustment To change room temperatureFor fan For coolingTime setting Days timer keyTimer Hold/Resume key Clock keyTrouble shooting Error DisplaySpecification Guidelines Outdoor UnitMemo Mitsubishi Electric Corporation Data Book PE,PEH