Mitsubishi Electronics PE-8MYC, PE-15MYC, PE-20MYC manual Wiring Diagrams, PE-7MYC-EU Standard

Page 49

WIRING DIAGRAMS

PE-7MYC-EU (STANDARD)

Power supply,

3Phase

TB1

 

 

52C

51C

 

380

415Volt,

50Hertz

 

 

 

L1

 

RED

 

 

 

 

 

RED

 

 

 

 

 

L2

RED

WHITE

WHITE

 

 

 

 

 

 

 

MC

 

 

 

L3

 

BLACK

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51F2

 

PU-7MYC1-EU

CIRCUIT BREAKER

 

 

 

RED

1C4 RED

(FIELD SUPPLY) 100A N BLUE

F3(3.15A)

WHITE

2

WHITE

 

 

 

 

 

 

BLACK

3

MF2

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

1

RED

 

 

 

PE

 

 

 

2

WHITE

 

 

 

 

 

 

 

3

MF3

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

49C

 

C5

 

 

 

 

 

 

52C

 

 

 

 

 

 

 

 

51F2

 

 

 

 

 

 

 

 

 

 

TB5

 

 

 

 

 

 

63H

 

15

 

 

 

 

 

 

 

GRAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51C

 

 

 

 

 

 

 

 

CZ2

 

CZ2

 

 

 

 

 

 

CH

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

CZ

CR2

 

 

Power supply, Single Phase

TB2

220

240Volt, 50Hertz

L

 

 

PE-7MYC-EU

CIRCUIT BREAKER

 

(FIELD SUPPLY) 15A

N

 

 

PE

 

52C

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

CZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JUMPER

 

 

 

 

 

 

 

52F

 

 

51F1

TB4

 

 

TB4

1 C1 RED

 

RED

 

 

 

 

 

5

Hi

 

6

2

5 C1

 

 

 

 

 

 

 

 

 

BROWN MF1 6

C

 

 

 

 

 

 

 

Low

7

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

SW2(FIELD SUPPLY)

4

BLUE

 

RED F1 (3.15A)

 

GRAY

TB4

1

 

 

 

52F

 

 

 

 

 

 

 

 

SWITCH BOX

 

 

 

 

 

CZ1

 

 

 

 

 

 

(FIELD SUPPLY)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F2

 

 

 

 

 

 

 

 

TB3 15

 

51F1

 

 

 

 

 

 

 

 

 

 

 

 

(3.15A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

C3

 

 

 

 

23WA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

26L

 

 

 

 

 

 

 

 

 

 

 

 

C3

Tr

 

 

 

SW1

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FZ

 

 

 

 

 

 

 

 

 

CZ2

 

 

AC

AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

24V

 

2

3

 

 

 

 

 

 

 

30FZ

240V

 

TB4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR1

 

CZ1

 

 

 

 

 

 

 

 

 

52F

 

 

 

 

 

 

 

 

 

14

 

30

 

 

 

FZ

 

 

 

 

 

 

 

FZ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

BLUE

 

 

GRAY

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor motor

 

 

 

Fan motor (indoor)

 

 

 

Fan motor (outdoor)

 

 

 

Contactor (compressor)

 

 

 

Contactor (fan I/D)

TB1

5

 

Terminal block

 

 

 

Crankcase heater

F1

3

 

Fuse (3.15A)

 

 

 

Transformer

 

 

 

Internal thermostat (compressor)

 

 

 

Over current relay (compressor)

 

 

 

Over current relay(fanI/D,O/D)

 

 

 

High-pressure switch

26L

 

 

Thermostat (freeze protection)

 

 

 

Auxiliary relay (fan)

CZ1, 2

Auxiliary relay (compressor)

30CZ, FZ

Auxiliary relay (check)

 

 

 

Switch (on)

 

 

 

Switch (Fan Hi-Low)

 

 

 

Thermostat (room temp.)

C

 

 

Run capacitor

C1, 3 ~ 5

Connector

CR1, 2

Surge killer

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting. 4.Not specified color of wire is brown.

5.Please remove the jumper wire (Mark) in the above diagram if you use the Switch <SW2> at local.

If the Switch <SW2> is not used, the Fan motor (indoor) drives at high speed.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current, Over current relays <51C>, <51F1,2> are installed. Therefore, do not change factory set value of Over current relays.

Option controller connection.

Symbol

No.

Function

PAC-204RC (Option)

terminal no.

 

 

 

 

1

Power (Active)

24VAC(L)

TB4

2

Cooling operation

COMP

3

Fan operation

FAN HI

 

4

Power (Neutral)

24VAC(N)

- 48 -

Image 49
Contents Data Book Contents For correct installation Safety for USEDo not wash the unit with water Indoor unit Complete Line UPOutdoor unit Descriptions FeaturesTypical Installation Example Mechanical Specifications10 M Y C MODEL-DESIGNATION BreakdownPE-7~20MYC Cooling only SpecificationsPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump PE-7~20MYC-EU Electrical DataHeating PEH-5,7,8MYA-EUPEH-10,15,20MYA-EU Model Selection With actual examples Selection ProcedureCalculation of net capacity Efficiency CalculationCooling Capacity Standard Air Flow Capacity TablesFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU Use for low ambient cooling parts PEH-8MYA-EUPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU Combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Cooling Operation RangePEH-5MYA-EU FAN PerformancePE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-20MYC-EU PEH-20MYA-EU PE-15MYC-EU PEH-15MYA-EUPulley outside dimensions are shown below Unit mm Position mesurement Sound DataIndoor units Outdoor unitsPEH-5 Outline DimensionsPEH-7,8 PEH-15 PEH-1028.6 DRAINRc HOLES26Flange HOLES28 PEH-20PUH-7,8,10 Upper blow PUH-5Holes Holes 2-ø15 Ø19.053/4PU-15 PUH-8,10 Side blowØ15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 Cable Entry 44 Holes 2-ø15PUH-15,20 PU-20Ø28.61-1/8 Ø15.885/8 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply PE-7MYC-EU Standard Wiring DiagramsInternal thermostat indoor fan PE-8,10MYC-EU StandardOver current relayfanI/D,O/D PE-15MYC-EU Standard TB1 PE-20MYC-EU StandardPE-7MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fan PE-8,10MYC-EU Special Order Anti Short Cycle TimerPE-15MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor PE-20MYC-EU Special Order Anti Short Cycle TimerPE-7MYC-EU Special Order LOW Ambient Cooling 23C Ambient temperature52F1 Contactor fan I/D 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relays PE-15MYC-EU Special Order LOW Ambient CoolingAuxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D MF2 PEH-5MYA-EU StandardThermostat defrost PEH-7MYA-EU StandardWay valve Option controller connectionC1~7 PEH-8,10MYA-EU StandardCR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat PEH-8,10MYA-EU CR1 Surge killer Timer Anti short cyclePEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling MF2 Fan motor outdoor PEH-8,10MYA-EU Special Order LOW Ambient Cooling52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26LPEH-15,20MYA-EU Special Order LOW Ambient Cooling 63H1,2 High-pressure switch 26L1,251F1~5 PE-7,8,10MYC-EU Electrical Operation Flow ChartsPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PE-7,8,10,15,20MYC-EU Refrigerant SchematicsPEH-5,7,8,10,15,20MYA-EU PE-7,8,10MYC-EU PE-15,20MYC-EU Safety & Control DevicesPEH-7,8,10MYA-EU Special Order Service refYear PE-7,8,1015,20MYC-EU Physical DataIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Space required around unit Indoor unit InstallationOutdoor unit Ceiling Over Service-panelOver 500 Over Service Panel PU-15 At a single installationOver Service-panel Preparation before installing Indoor unitOver Service-panel 500 Outdoor unit Installation of the unit Indoor unitNut Washer Nut M10 WasherLifting method Duct constructionCase of Brazing type Piping connectionPipe assy Valve knobThrow away Fig By-pass tube Flange assy Extension pipe Extension pipe Use the attached new packing FigGood example Bad example Evacuation Airtight testAdditional refrigerant charge Drain piping Arrangement such as terminal block in control box Electric wiringControl module of outdoor unit PUH-5, 8 Power supply wires Terminal block for connection wiresControl module of outdoor unit PUH-7, 8 Control module of outdoor unit PU-20Method for connecting electric wire 50A Protection switch60A Selection of other capacities should beBefore starting the Trial run Putting condition of the belt=4.5mm Flexion loadW 1.4 2.2kg Check points for operation Instructions for USEOutlet grille Ceiling Ceiling Obstacle blocking air outletFingermarks Neutral Grease MaintenanceAdhesive Isopropyl Paste AlcoholWhen the air conditioner is not to be used for a long time When beginning to use air conditioner againTransfer of installation Transferring work, and constructionMaintenance and inspection Place for installationRegarding electric work Conseration of the noiseAt cooling, water which places to cooling piping Trouble shootingDisplay section HOW to Operate Option PAC-204RCBefore starting operation On / OFF Start an operationRoom temperature adjustment To change room temperature Selecting operation When selecting operationFor fan For coolingDays timer key Time settingTimer Hold/Resume key Clock keyError Display Trouble shootingOutdoor Unit Specification GuidelinesMemo Data Book PE,PEH Mitsubishi Electric Corporation