Mitsubishi Electronics PE-8MYC Installation, Space required around unit Indoor unit, Outdoor unit

Page 88

INSTALLATION

1. Space required around unit.

Indoor unit

Dimension of the unit and space necessary for sevicing.

PEH-5 PE(H)-7, 8, 10

 

 

200

 

 

730

530

 

 

 

380

B

180

 

 

A

 

928 100 500 428

Ceiling access panel

 

A

B

PEH - 5

1560

1000

PE(H) - 7, 8

1880

1320

PE(H) - 10

2080

1520

PE(H)-15,20

 

200

946

746

400

B

200

 

A

 

100

 

1206

706

 

500

Ceiling access panel

 

A

B

PE(H) - 15

2187

1587

PE(H) - 20

2490

1890

Outdoor unit

Secure enough space necessary for servicing, installing, and for proper function of the unit. To prevent short-cycling, remove obstacles as much as possible.

PUH-5, 8, 10 (Side blow)

(1) At a single installation

Service panel

Inlet surface

150 over

Inlet surface

500 over

150 over

 

 

Inlet

 

surface

Service panel

Outlet surface

 

300 over

150 over

Inlet surface

Outlet surface

With the inlet surface facing a wall.

(2) Relation of unit when many set up unit.

With the outlet surface facing a wall.

 

 

 

300

 

 

 

over

500 over

500 over

500 over

500 over

Please set the unit that the inlet air and the outlet air are not influenced.

- 87 -

Image 88
Contents Data Book Contents Safety for USE For correct installationDo not wash the unit with water Indoor unit Complete Line UPOutdoor unit Features DescriptionsMechanical Specifications Typical Installation ExampleMODEL-DESIGNATION Breakdown 10 M Y CSpecifications PE-7~20MYC Cooling onlyPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump Electrical Data PE-7~20MYC-EUPEH-5,7,8MYA-EU HeatingPEH-10,15,20MYA-EU Selection Procedure Model Selection With actual examplesEfficiency Calculation Calculation of net capacityCooling Capacity Standard Air Flow Capacity TablesFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU PEH-8MYA-EU Use for low ambient cooling partsPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EU Combined with PUH-8MYE-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Operation Range CoolingFAN Performance PEH-5MYA-EUPE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-15MYC-EU PEH-15MYA-EU PE-20MYC-EU PEH-20MYA-EUPulley outside dimensions are shown below Unit mm Sound Data Position mesurementIndoor units Outdoor unitsPEH-5 Outline DimensionsPEH-7,8 PEH-10 PEH-1528.6 DRAINRc HOLES26PEH-20 Flange HOLES28PUH-5 PUH-7,8,10 Upper blowHoles Holes 2-ø15 Ø19.053/4PUH-8,10 Side blow PU-15Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 Cable Entry 44 Holes 2-ø15PU-20 PUH-15,20Ø28.61-1/8 Ø15.885/8 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply Wiring Diagrams PE-7MYC-EU StandardInternal thermostat indoor fan PE-8,10MYC-EU StandardOver current relayfanI/D,O/D PE-15MYC-EU Standard PE-20MYC-EU Standard TB1PE-7MYC-EU Special Order Anti Short Cycle Timer PE-8,10MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fanPE-15MYC-EU Special Order Anti Short Cycle Timer PE-20MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor23C Ambient temperature PE-7MYC-EU Special Order LOW Ambient Cooling52F1 Contactor fan I/D 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling PE-15MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relaysAuxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D PEH-5MYA-EU Standard MF2PEH-7MYA-EU Standard Thermostat defrostWay valve Option controller connectionC1~7 PEH-8,10MYA-EU StandardCR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat CR1 Surge killer Timer Anti short cycle PEH-8,10MYA-EUPEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling PEH-8,10MYA-EU Special Order LOW Ambient Cooling MF2 Fan motor outdoor52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26LPEH-15,20MYA-EU Special Order LOW Ambient Cooling 63H1,2 High-pressure switch 26L1,251F1~5 PE-7,8,10MYC-EU Electrical Operation Flow ChartsPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PE-7,8,10,15,20MYC-EU Refrigerant SchematicsPEH-5,7,8,10,15,20MYA-EU Safety & Control Devices PE-7,8,10MYC-EU PE-15,20MYC-EUPEH-7,8,10MYA-EU Special Order Service refYear Physical Data PE-7,8,1015,20MYC-EUIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Space required around unit Indoor unit InstallationOutdoor unit Ceiling Over Service-panelOver 500 PU-15 At a single installation Over Service PanelOver Service-panel Preparation before installing Indoor unitOver Service-panel 500 Installation of the unit Indoor unit Outdoor unitNut Washer Nut M10 WasherDuct construction Lifting methodPiping connection Case of Brazing typeValve knob Pipe assyThrow away Fig By-pass tube Flange assy Extension pipe Extension pipe Use the attached new packing FigGood example Bad example Evacuation Airtight testAdditional refrigerant charge Drain piping Arrangement such as terminal block in control box Electric wiringControl module of outdoor unit PUH-5, 8 Terminal block for connection wires Power supply wiresControl module of outdoor unit PUH-7, 8 Control module of outdoor unit PU-20Method for connecting electric wire Protection switch 50A60A Selection of other capacities should beBefore starting the Trial run Putting condition of the belt=4.5mm Flexion loadW 1.4 2.2kg Instructions for USE Check points for operationOutlet grille Ceiling Ceiling Obstacle blocking air outletMaintenance Fingermarks Neutral GreaseAdhesive Isopropyl Paste AlcoholWhen beginning to use air conditioner again When the air conditioner is not to be used for a long timeTransfer of installation Transferring work, and constructionPlace for installation Maintenance and inspectionRegarding electric work Conseration of the noiseTrouble shooting At cooling, water which places to cooling pipingHOW to Operate Option PAC-204RC Display sectionBefore starting operation On / OFF Start an operationSelecting operation When selecting operation Room temperature adjustment To change room temperatureFor fan For coolingTime setting Days timer keyTimer Hold/Resume key Clock keyTrouble shooting Error DisplaySpecification Guidelines Outdoor UnitMemo Mitsubishi Electric Corporation Data Book PE,PEH