Mitsubishi Electronics PEH-10MYA manual Selection Procedure, Model Selection With actual examples

Page 15
65 70 75 77 80

SELECTION PROCEDURE

1. Model Selection (With actual examples)

First step, to select the approximate model:

Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.

Second step, to select the model:

To select the model, the following conditions must be known:

(1)Total cooling load or sensible cooling load

(2)Indoor conditioned temperature (WB*1, DB)

(3)Designed outdoor temperature (DB)*2

(4)Designed air flow

(5)Designed external static pressure (= Wind pressure loss of air duct)*3

Notes:

*1. The correct WB is required since it has a serious effect on the capacity.

*2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest temperature during an air conditioning time frame is the "designed outdoor temperature". However, it is recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from the calculation to avoid selection of an excessively large capacity model.

*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance is used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced during actual operation causing the generation of high operating sounds and carry-over of condensed water.

(Step-1) Confirmation of operation range

Confirm that the conditions given above for the model to be selected are within the

operation range listed on Page 36.

(Step-2) Calculation of actual air flow, external static pressure, and fan motor input

Based on the designed air flow and external static pressure, obtain the actual air flow, actual external static pressure, and fan motor power input from the fan performance table for the model selected. For an explanation of how to use the fan performance table, see the following examples.

Example: PE-8MYC, 50Hz

Example 1. (To operate with values near to the designed air flow and external static pressure.)

Condition : Designed air flow 70CMM

Designed external static pressure 60Pa

Calculation : The designed point is A. Therefore, duct resistance line passing A is

dotted line.

 

(Pa)

 

 

Fan Performance Curve 50Hz

 

450

 

 

 

 

 

 

 

 

 

 

 

 

 

Therefore, actual point is B for Δconnection

 

 

 

 

 

Recommended

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actual air flow = 77CMM

 

400

 

 

 

 

 

For

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

line

 

Actual external static pressure = 70Pa

 

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes: Duct resustance line is secondary curve.

 

300

 

 

 

 

 

 

 

 

 

 

B

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

 

 

60Pa

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

 

For

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

line

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

55

60

 

 

 

 

 

 

 

 

Fan speed

(rpm)

1400

1300

1200

1100

1000

900

800

- 14 -

Air flow (CMM)

 

Image 15
Contents Data Book Contents For correct installation Safety for USEDo not wash the unit with water Complete Line UP Indoor unitOutdoor unit Descriptions FeaturesTypical Installation Example Mechanical Specifications10 M Y C MODEL-DESIGNATION BreakdownPE-7~20MYC Cooling only SpecificationsPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump PE-7~20MYC-EU Electrical DataHeating PEH-5,7,8MYA-EUPEH-10,15,20MYA-EU Model Selection With actual examples Selection ProcedureCalculation of net capacity Efficiency CalculationCapacity Tables Cooling Capacity Standard Air FlowFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU Use for low ambient cooling parts PEH-8MYA-EUPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU Combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Cooling Operation RangePE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EU FAN PerformancePEH-5MYA-EU PE-7MYC-EU PEH-7MYA-EUPE-20MYC-EU PEH-20MYA-EU PE-15MYC-EU PEH-15MYA-EUPulley outside dimensions are shown below Unit mm Outdoor units Sound DataPosition mesurement Indoor unitsOutline Dimensions PEH-5PEH-7,8 DRAINRc HOLES26 PEH-10PEH-15 28.6Flange HOLES28 PEH-20Holes 2-ø15 Ø19.053/4 PUH-5PUH-7,8,10 Upper blow HolesCable Entry 44 Holes 2-ø15 PUH-8,10 Side blowPU-15 Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8Holes 6-ø15 Control Cable Entry ø27 PU-20PUH-15,20 Ø28.61-1/8 Ø15.885/8Duct work is local supply PE-7MYC-EU Standard Wiring DiagramsPE-8,10MYC-EU Standard Internal thermostat indoor fanOver current relayfanI/D,O/D PE-15MYC-EU Standard TB1 PE-20MYC-EU StandardPE-7MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fan PE-8,10MYC-EU Special Order Anti Short Cycle TimerPE-15MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor PE-20MYC-EU Special Order Anti Short Cycle Timer49F Internal thermostatfan O/D 23C Ambient temperaturePE-7MYC-EU Special Order LOW Ambient Cooling 52F1 Contactor fan I/DPE-8,10MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relays PE-15MYC-EU Special Order LOW Ambient CoolingPE-20MYC-EU Special Order LOW Ambient Cooling Auxiliary relay fanI/D30FZ Auxiliary relay fanI/D MF2 PEH-5MYA-EU StandardOption controller connection PEH-7MYA-EU StandardThermostat defrost Way valvePEH-8,10MYA-EU Standard C1~7CR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat PEH-8,10MYA-EU CR1 Surge killer Timer Anti short cyclePEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26L PEH-8,10MYA-EU Special Order LOW Ambient CoolingMF2 Fan motor outdoor 52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F463H1,2 High-pressure switch 26L1,2 PEH-15,20MYA-EU Special Order LOW Ambient Cooling51F1~5 Electrical Operation Flow Charts PE-7,8,10MYC-EUPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU Refrigerant Schematics PE-7,8,10,15,20MYC-EUPEH-5,7,8,10,15,20MYA-EU PE-7,8,10MYC-EU PE-15,20MYC-EU Safety & Control DevicesPEH-7,8,10MYA-EU Service ref Special OrderYear PE-7,8,1015,20MYC-EU Physical DataIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Installation Space required around unit Indoor unitOutdoor unit Service-panel Ceiling OverOver 500 Over Service Panel PU-15 At a single installationPreparation before installing Indoor unit Over Service-panelOver Service-panel 500 Nut M10 Washer Installation of the unit Indoor unitOutdoor unit Nut WasherLifting method Duct constructionCase of Brazing type Piping connectionExtension pipe Use the attached new packing Fig Valve knobPipe assy Throw away Fig By-pass tube Flange assy Extension pipeGood example Bad example Airtight test EvacuationAdditional refrigerant charge Drain piping Electric wiring Arrangement such as terminal block in control boxControl module of outdoor unit PUH-5, 8 Control module of outdoor unit PU-20 Terminal block for connection wiresPower supply wires Control module of outdoor unit PUH-7, 8Method for connecting electric wire Selection of other capacities should be Protection switch50A 60APutting condition of the belt Before starting the Trial run=4.5mm Flexion loadW 1.4 2.2kg Ceiling Ceiling Obstacle blocking air outlet Instructions for USECheck points for operation Outlet grillePaste Alcohol MaintenanceFingermarks Neutral Grease Adhesive IsopropylTransferring work, and construction When beginning to use air conditioner againWhen the air conditioner is not to be used for a long time Transfer of installationConseration of the noise Place for installationMaintenance and inspection Regarding electric workAt cooling, water which places to cooling piping Trouble shootingOn / OFF Start an operation HOW to Operate Option PAC-204RCDisplay section Before starting operationFor cooling Selecting operation When selecting operationRoom temperature adjustment To change room temperature For fanClock key Time settingDays timer key Timer Hold/Resume keyError Display Trouble shootingOutdoor Unit Specification GuidelinesMemo Data Book PE,PEH Mitsubishi Electric Corporation