Mitsubishi Electronics PE-10MYC Preparation before installing Indoor unit, Over Service-panel

Page 91

PUH-15, 20

(1) At a single installation

The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2) The obstacle is in three directions. (Fig 3,4)

ceiling

1500 over

The right and left side

and the back and forth 300 over side must be opened.

Fig 1

However, the outlet side must be opened.

300 over

300 over

Service-panel

 

 

 

However, outlet side

 

 

500 over must be opened.

 

 

300 over

And the obstacle in

 

 

two directions must be

 

 

 

Service Panel

 

lower than the unit.

Fig 2

300over

Service-panel

500 over

Fig 3

Fig 4

(2) Relation of unit when many set up unit. (Fig 5,6,7)

300 over

 

Service-panel

500 over

 

 

300 over

500

300 over

over

Service-panel

Fig 5

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A A

Fig 6 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

300 over

A

A

A

300 over

Fig 7 All "A" is 500 over in any case.

2. Preparation before installing

Indoor unit

Please use the specified hanging bolt in any case.

Hanging bolt is local supply.

 

Please use the method below or use the angle and the

 

rectangular lumber, etc. and install the hanging bolt.

Insert etc

 

100-150kg

Reinforcement

Hanging bolt

M10 (PEH-5,PE(H)-7,8,10)

M12 (PE(H)-15,20)

- 90 -

Image 91
Contents Data Book Contents For correct installation Safety for USEDo not wash the unit with water Indoor unit Complete Line UPOutdoor unit Descriptions FeaturesTypical Installation Example Mechanical Specifications10 M Y C MODEL-DESIGNATION BreakdownPE-7~20MYC Cooling only SpecificationsPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump PE-7~20MYC-EU Electrical DataHeating PEH-5,7,8MYA-EUPEH-10,15,20MYA-EU Model Selection With actual examples Selection ProcedureCalculation of net capacity Efficiency CalculationCooling Capacity Standard Air Flow Capacity TablesFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU Use for low ambient cooling parts PEH-8MYA-EUPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU Combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Cooling Operation RangePE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EU FAN PerformancePEH-5MYA-EU PE-7MYC-EU PEH-7MYA-EUPE-20MYC-EU PEH-20MYA-EU PE-15MYC-EU PEH-15MYA-EUPulley outside dimensions are shown below Unit mm Outdoor units Sound DataPosition mesurement Indoor unitsPEH-5 Outline DimensionsPEH-7,8 DRAINRc HOLES26 PEH-10PEH-15 28.6Flange HOLES28 PEH-20Holes 2-ø15 Ø19.053/4 PUH-5PUH-7,8,10 Upper blow HolesCable Entry 44 Holes 2-ø15 PUH-8,10 Side blowPU-15 Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8Holes 6-ø15 Control Cable Entry ø27 PU-20PUH-15,20 Ø28.61-1/8 Ø15.885/8Duct work is local supply PE-7MYC-EU Standard Wiring DiagramsInternal thermostat indoor fan PE-8,10MYC-EU StandardOver current relayfanI/D,O/D PE-15MYC-EU Standard TB1 PE-20MYC-EU StandardPE-7MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fan PE-8,10MYC-EU Special Order Anti Short Cycle TimerPE-15MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor PE-20MYC-EU Special Order Anti Short Cycle Timer49F Internal thermostatfan O/D 23C Ambient temperaturePE-7MYC-EU Special Order LOW Ambient Cooling 52F1 Contactor fan I/DPE-8,10MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relays PE-15MYC-EU Special Order LOW Ambient CoolingAuxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D MF2 PEH-5MYA-EU StandardOption controller connection PEH-7MYA-EU StandardThermostat defrost Way valveC1~7 PEH-8,10MYA-EU StandardCR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat PEH-8,10MYA-EU CR1 Surge killer Timer Anti short cyclePEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26L PEH-8,10MYA-EU Special Order LOW Ambient CoolingMF2 Fan motor outdoor 52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4PEH-15,20MYA-EU Special Order LOW Ambient Cooling 63H1,2 High-pressure switch 26L1,251F1~5 PE-7,8,10MYC-EU Electrical Operation Flow ChartsPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PE-7,8,10,15,20MYC-EU Refrigerant SchematicsPEH-5,7,8,10,15,20MYA-EU PE-7,8,10MYC-EU PE-15,20MYC-EU Safety & Control DevicesPEH-7,8,10MYA-EU Special Order Service refYear PE-7,8,1015,20MYC-EU Physical DataIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Space required around unit Indoor unit InstallationOutdoor unit Ceiling Over Service-panelOver 500 Over Service Panel PU-15 At a single installationOver Service-panel Preparation before installing Indoor unitOver Service-panel 500 Nut M10 Washer Installation of the unit Indoor unitOutdoor unit Nut WasherLifting method Duct constructionCase of Brazing type Piping connectionExtension pipe Use the attached new packing Fig Valve knobPipe assy Throw away Fig By-pass tube Flange assy Extension pipeGood example Bad example Evacuation Airtight testAdditional refrigerant charge Drain piping Arrangement such as terminal block in control box Electric wiringControl module of outdoor unit PUH-5, 8 Control module of outdoor unit PU-20 Terminal block for connection wiresPower supply wires Control module of outdoor unit PUH-7, 8Method for connecting electric wire Selection of other capacities should be Protection switch50A 60ABefore starting the Trial run Putting condition of the belt=4.5mm Flexion loadW 1.4 2.2kg Ceiling Ceiling Obstacle blocking air outlet Instructions for USECheck points for operation Outlet grillePaste Alcohol MaintenanceFingermarks Neutral Grease Adhesive IsopropylTransferring work, and construction When beginning to use air conditioner againWhen the air conditioner is not to be used for a long time Transfer of installationConseration of the noise Place for installationMaintenance and inspection Regarding electric workAt cooling, water which places to cooling piping Trouble shootingOn / OFF Start an operation HOW to Operate Option PAC-204RCDisplay section Before starting operationFor cooling Selecting operation When selecting operationRoom temperature adjustment To change room temperature For fanClock key Time settingDays timer key Timer Hold/Resume keyError Display Trouble shootingOutdoor Unit Specification GuidelinesMemo Data Book PE,PEH Mitsubishi Electric Corporation