7. The putting condition of the belt.

(PE(H)-15,20 only)

1.Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below. 2.Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1

below at the proper flexion. (A=4.5mm)

3.Adjust the suitable tension after the belt sit properly across the pulley (after more 24-28 hours working). When the new belt is used, adjust the suitable tension about the 1.3 times of the maximum value of the flexion load.

4.Readjust the belt every 2,000 hours after the first adjustment.

Exchange the belt when the belt's surroundings length has expanded by 2% including the first expansion of the belt. (about 1%)

(about 8,000 hours converted working time)

table

parallel angle

K ( )

note

pulley

pulley

10 or less

gap of 3mm every 1m

 

 

 

K

K

K

A

A=4.5mm

Flexion load(W) 1.4 2.2kg

K

Figure1 Parallel degree of pulley

Figure2 Belt tension

8. Before starting the Trial run.

Check items

(1)Check to see wheter there are refrigerant leakage, and slack power or transmission cable.

(2)Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and ground.

(3)Do not operate in the case of 1.0M ohm or less.

Note : Never carry out megger-ohm check over terminal control board. Otherwise the control board would be broken.

(4)Check to see wheter both gas and liquid valves are fully opened. Note : Be sure to tighten caps.

(5)Turn universal power supply at least 6 hours before gettig test run in order to current to crank heater. If current-carrying hours are too short, it may result in a malfunction of compressor.

(6)Confirm operation of high-pressure switch.

If the two lead wires of the outdoor unit fan motor are disconnected from the connector and cooling is performed, the high-pressure switch should operate and stop the unit after 5 to 10 minutes.

(7)Confirm that the fans of the indoor and outdoor unit rotate in the correct direction. Change the power supply phase connections if it is rotating in the reverse direction.

Perform trial operation after completion of the above items.

- 102 -

Image 103
Contents Data Book Contents For correct installation Safety for USEDo not wash the unit with water Indoor unit Complete Line UPOutdoor unit Descriptions FeaturesTypical Installation Example Mechanical Specifications10 M Y C MODEL-DESIGNATION BreakdownPE-7~20MYC Cooling only SpecificationsPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump PE-7~20MYC-EU Electrical DataHeating PEH-5,7,8MYA-EUPEH-10,15,20MYA-EU Model Selection With actual examples Selection ProcedureCalculation of net capacity Efficiency CalculationCooling Capacity Standard Air Flow Capacity TablesFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU Use for low ambient cooling parts PEH-8MYA-EUPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU Combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Cooling Operation RangePE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EU FAN PerformancePEH-5MYA-EU PE-7MYC-EU PEH-7MYA-EUPE-20MYC-EU PEH-20MYA-EU PE-15MYC-EU PEH-15MYA-EUPulley outside dimensions are shown below Unit mm Outdoor units Sound DataPosition mesurement Indoor unitsPEH-5 Outline DimensionsPEH-7,8 DRAINRc HOLES26 PEH-10PEH-15 28.6Flange HOLES28 PEH-20Holes 2-ø15 Ø19.053/4 PUH-5PUH-7,8,10 Upper blow HolesCable Entry 44 Holes 2-ø15 PUH-8,10 Side blowPU-15 Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8Holes 6-ø15 Control Cable Entry ø27 PU-20PUH-15,20 Ø28.61-1/8 Ø15.885/8Duct work is local supply PE-7MYC-EU Standard Wiring DiagramsInternal thermostat indoor fan PE-8,10MYC-EU StandardOver current relayfanI/D,O/D PE-15MYC-EU Standard TB1 PE-20MYC-EU StandardPE-7MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fan PE-8,10MYC-EU Special Order Anti Short Cycle TimerPE-15MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor PE-20MYC-EU Special Order Anti Short Cycle Timer49F Internal thermostatfan O/D 23C Ambient temperaturePE-7MYC-EU Special Order LOW Ambient Cooling 52F1 Contactor fan I/DPE-8,10MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relays PE-15MYC-EU Special Order LOW Ambient CoolingAuxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D MF2 PEH-5MYA-EU StandardOption controller connection PEH-7MYA-EU StandardThermostat defrost Way valveC1~7 PEH-8,10MYA-EU StandardCR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat PEH-8,10MYA-EU CR1 Surge killer Timer Anti short cyclePEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26L PEH-8,10MYA-EU Special Order LOW Ambient CoolingMF2 Fan motor outdoor 52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4PEH-15,20MYA-EU Special Order LOW Ambient Cooling 63H1,2 High-pressure switch 26L1,251F1~5 PE-7,8,10MYC-EU Electrical Operation Flow ChartsPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PE-7,8,10,15,20MYC-EU Refrigerant SchematicsPEH-5,7,8,10,15,20MYA-EU PE-7,8,10MYC-EU PE-15,20MYC-EU Safety & Control DevicesPEH-7,8,10MYA-EU Special Order Service refYear PE-7,8,1015,20MYC-EU Physical DataIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Space required around unit Indoor unit InstallationOutdoor unit Ceiling Over Service-panelOver 500 Over Service Panel PU-15 At a single installationOver Service-panel Preparation before installing Indoor unitOver Service-panel 500 Nut M10 Washer Installation of the unit Indoor unitOutdoor unit Nut WasherLifting method Duct constructionCase of Brazing type Piping connectionExtension pipe Use the attached new packing Fig Valve knobPipe assy Throw away Fig By-pass tube Flange assy Extension pipeGood example Bad example Evacuation Airtight testAdditional refrigerant charge Drain piping Arrangement such as terminal block in control box Electric wiringControl module of outdoor unit PUH-5, 8 Control module of outdoor unit PU-20 Terminal block for connection wiresPower supply wires Control module of outdoor unit PUH-7, 8Method for connecting electric wire Selection of other capacities should be Protection switch50A 60ABefore starting the Trial run Putting condition of the belt=4.5mm Flexion loadW 1.4 2.2kg Ceiling Ceiling Obstacle blocking air outlet Instructions for USECheck points for operation Outlet grillePaste Alcohol MaintenanceFingermarks Neutral Grease Adhesive IsopropylTransferring work, and construction When beginning to use air conditioner againWhen the air conditioner is not to be used for a long time Transfer of installationConseration of the noise Place for installationMaintenance and inspection Regarding electric workAt cooling, water which places to cooling piping Trouble shootingOn / OFF Start an operation HOW to Operate Option PAC-204RCDisplay section Before starting operationFor cooling Selecting operation When selecting operationRoom temperature adjustment To change room temperature For fanClock key Time settingDays timer key Timer Hold/Resume keyError Display Trouble shootingOutdoor Unit Specification GuidelinesMemo Data Book PE,PEH Mitsubishi Electric Corporation