Mitsubishi Electronics PEH-5MYA, PE-8MYC Airtight test, Evacuation, Additional refrigerant charge

Page 97
The outdoor unit of PE-5,8,10 have side blow type and upper blow type.
Factory charge refer to the table below.

Airtight test

Airtight test should be made by pressurizing nitrogen gas to 3Mpa. For the test method, refer to the following figure.

(Make a test with the valve closed. Be also sure to pressurize both liquid and gas pipe.) The test result can be judged good if the pressure has not been reduced after leaving for about one day after completion of nitrogen pressurization.

a.

Nitrogen gas

b.

To indoor unit

c.

System analyzer

d.

Low knob

e.

High knob

f.

Valve

g.

Liquid gas

h.

Gas pipe

i.

Outdoor unit

j.

Service port

 

 

 

f

 

 

b

g

 

 

 

i

 

 

c

h

a

d

e

j

Evacuation

Evacuation should be made from the service port provided on the outdoor unit’s valve to the vacuum pump commonly used for both liquid pipe and gas pipe.

(Make evacuation from both liquid pipe and gas pipe with valve closed.) Remember :Never carry out air purge by refrigerant.

a.

System analyzer

b.

To indoor unit

c.

Low knob

d.

High knob

e.

Valve

f.

Liquid gas

g.

Gas pipe

h.

Outdoor unit

i.

Service port

j.

Vacuum pump

e

bf

h

a

g

cd

i j

Additional refrigerant charge

The mount of refrigerant charged in this unit is a appropriate for 5-meter long refrigerant pipes. Refer to the table below and add the corresponding amount of refrigerant if the pipes are extended.

(The refrigerant is charged in the outdoor unit.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory charge

 

 

 

 

 

 

Refrigerant piping length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

unit

5m

10m

15m

20m

25m

30m

35m

40m

45m

50m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PU-7

 

 

 

 

 

 

 

 

 

 

 

 

Side blow

Upper blow

 

PU-8

0

0.8

1.6

2.4

3.2

4.0

4.8

5.6

6.4

7.2

 

 

 

 

 

 

PU-7

5.7

 

 

 

 

 

 

 

charge

PU-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PU-8

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PU-15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PU-10

8.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mount

 

0

2x0.8

2x1.6

2x2.4

2x3.2

2x4.0

2x4.8

2x5.6

2x6.4

2x7.2

 

 

 

 

 

 

 

 

 

 

PU-20

 

charge

 

 

 

 

PU-15

2x4.8

R-22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(kg)

PUH-5

0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

 

mount

 

 

 

 

PU-20

2x9.7

 

 

 

 

 

 

PUH-7

0

0.8

1.6

2.4

3.2

4.0

4.8

5.6

6.4

7.2

 

R-22

PUH-5

5.0

 

 

 

 

 

 

(kg)

 

 

 

 

 

PUH-8

0

0.8

1.7

2.5

3.3

4.2

5.0

5.8

6.7

7.5

 

 

 

 

 

 

PUH-7

5.7

 

 

 

 

 

 

 

 

PUH-10

 

 

PUH-8

6.6

PUH-8

6.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUH-15

0

2x0.8

2x1.7

2x2.5

2x3.3

2x4.2

2x5.0

2x5.8

2x6.7

2x7.5

 

 

PUH-10

9.9

PUH-10

9.9

 

PUH-20

 

 

 

 

 

 

PUH-15

2x6.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUH-20

2x9.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 96 -

Image 97
Contents Data Book Contents For correct installation Safety for USEDo not wash the unit with water Indoor unit Complete Line UPOutdoor unit Descriptions FeaturesTypical Installation Example Mechanical Specifications10 M Y C MODEL-DESIGNATION BreakdownPE-7~20MYC Cooling only SpecificationsPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump PE-7~20MYC-EU Electrical DataHeating PEH-5,7,8MYA-EUPEH-10,15,20MYA-EU Model Selection With actual examples Selection ProcedureCalculation of net capacity Efficiency CalculationCooling Capacity Standard Air Flow Capacity TablesFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU Use for low ambient cooling parts PEH-8MYA-EUPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU Combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Cooling Operation RangePEH-5MYA-EU FAN PerformancePE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-20MYC-EU PEH-20MYA-EU PE-15MYC-EU PEH-15MYA-EUPulley outside dimensions are shown below Unit mm Position mesurement Sound DataIndoor units Outdoor unitsPEH-5 Outline DimensionsPEH-7,8 PEH-15 PEH-1028.6 DRAINRc HOLES26Flange HOLES28 PEH-20PUH-7,8,10 Upper blow PUH-5Holes Holes 2-ø15 Ø19.053/4PU-15 PUH-8,10 Side blowØ15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 Cable Entry 44 Holes 2-ø15PUH-15,20 PU-20Ø28.61-1/8 Ø15.885/8 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply PE-7MYC-EU Standard Wiring DiagramsInternal thermostat indoor fan PE-8,10MYC-EU StandardOver current relayfanI/D,O/D PE-15MYC-EU Standard TB1 PE-20MYC-EU StandardPE-7MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fan PE-8,10MYC-EU Special Order Anti Short Cycle TimerPE-15MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor PE-20MYC-EU Special Order Anti Short Cycle TimerPE-7MYC-EU Special Order LOW Ambient Cooling 23C Ambient temperature52F1 Contactor fan I/D 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relays PE-15MYC-EU Special Order LOW Ambient CoolingAuxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D MF2 PEH-5MYA-EU StandardThermostat defrost PEH-7MYA-EU StandardWay valve Option controller connectionC1~7 PEH-8,10MYA-EU StandardCR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat PEH-8,10MYA-EU CR1 Surge killer Timer Anti short cyclePEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling MF2 Fan motor outdoor PEH-8,10MYA-EU Special Order LOW Ambient Cooling52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26LPEH-15,20MYA-EU Special Order LOW Ambient Cooling 63H1,2 High-pressure switch 26L1,251F1~5 PE-7,8,10MYC-EU Electrical Operation Flow ChartsPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PE-7,8,10,15,20MYC-EU Refrigerant SchematicsPEH-5,7,8,10,15,20MYA-EU PE-7,8,10MYC-EU PE-15,20MYC-EU Safety & Control DevicesPEH-7,8,10MYA-EU Special Order Service refYear PE-7,8,1015,20MYC-EU Physical DataIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Space required around unit Indoor unit InstallationOutdoor unit Ceiling Over Service-panelOver 500 Over Service Panel PU-15 At a single installationOver Service-panel Preparation before installing Indoor unitOver Service-panel 500 Outdoor unit Installation of the unit Indoor unitNut Washer Nut M10 WasherLifting method Duct constructionCase of Brazing type Piping connectionPipe assy Valve knobThrow away Fig By-pass tube Flange assy Extension pipe Extension pipe Use the attached new packing FigGood example Bad example Evacuation Airtight testAdditional refrigerant charge Drain piping Arrangement such as terminal block in control box Electric wiringControl module of outdoor unit PUH-5, 8 Power supply wires Terminal block for connection wiresControl module of outdoor unit PUH-7, 8 Control module of outdoor unit PU-20Method for connecting electric wire 50A Protection switch60A Selection of other capacities should beBefore starting the Trial run Putting condition of the belt=4.5mm Flexion loadW 1.4 2.2kg Check points for operation Instructions for USEOutlet grille Ceiling Ceiling Obstacle blocking air outletFingermarks Neutral Grease MaintenanceAdhesive Isopropyl Paste AlcoholWhen the air conditioner is not to be used for a long time When beginning to use air conditioner againTransfer of installation Transferring work, and constructionMaintenance and inspection Place for installationRegarding electric work Conseration of the noiseAt cooling, water which places to cooling piping Trouble shootingDisplay section HOW to Operate Option PAC-204RCBefore starting operation On / OFF Start an operationRoom temperature adjustment To change room temperature Selecting operation When selecting operationFor fan For coolingDays timer key Time settingTimer Hold/Resume key Clock keyError Display Trouble shootingOutdoor Unit Specification GuidelinesMemo Data Book PE,PEH Mitsubishi Electric Corporation