Mitsubishi Electronics PEH-20MYA Sound Data, Position mesurement, Indoor units, Outdoor units

Page 41

SOUND DATA

Indoor units

Sound Levels

 

PWL

SPL

 

 

OCTAVE BAND FREQ. Hz

 

 

 

MODEL

 

 

 

 

 

 

 

 

dB(A)

dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PEH-5MYA-EU

63

55

60.5

57.5

57.5

52.5

50.5

43

34.5

28.5

 

 

 

 

 

 

 

 

 

 

 

PE-7MYC-EU

63

55

62

60

54

53

50

42.5

37

31.5

PEH-7MYA-EU

 

 

 

 

 

 

 

 

 

 

PE-8MYC-EU

64

56

63

61

55

54

51

43.5

38

32.5

PEH-8MYA-EU

 

 

 

 

 

 

 

 

 

 

PE-10MYC-EU

67

59

62

62.5

58.5

59.5

53

48

43.5

36

PEH-10MYA-EU

 

 

 

 

 

 

 

 

 

 

PE-15MYC-EU

69

61

25

40

47

52

55

57.5

52

36.5

PEH-15MYA-EU

 

 

 

 

 

 

 

 

 

 

PE-20MYC-EU

70

62

32

44

49

53.5

56.5

57.5

53

51

PEH-20MYA-EU

 

 

 

 

 

 

 

 

 

 

Outdoor units

Sound Levels

 

PWL

SPL

 

 

OCTAVE BAND FREQ. Hz

 

 

 

MODEL

 

 

 

 

 

 

 

 

dB(A)

dB(A)

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

 

 

 

 

 

 

 

 

 

 

 

 

PUH-5MYE-EU

68

57

68

58

57

52.5

52

47.5

49

40

 

 

 

 

 

 

 

 

 

 

 

PU-7MYC1-EU

76

65

62

63.5

62

62

60

57.5

54

54

PUH-7MYC1-EU

 

 

 

 

 

 

 

 

 

 

PU-8MYC1-EU

76

65

62

63.5

62

62

60

57.5

54

54

PUH-8MYC1-EU

 

 

 

 

 

 

 

 

 

 

PUH-8MYE-EU

76

65

45.4

58

58

58.5

61

60

51.5

47

 

 

 

 

 

 

 

 

 

 

 

PU-10MYC1-EU

76

65

64.5

65

64

62.5

60

57

54.5

53

PUH-10MYC1-EU

 

 

 

 

 

 

 

 

 

 

PUH-10MYE-EU

76

65

45.4

58

58

58.5

61

60

51.5

47

 

 

 

 

 

 

 

 

 

 

 

PU-15MYC1-EU

78

67

68

72

70

65

60

57

53

49.5

 

 

 

 

 

 

 

 

 

 

 

PU-20MYC1-EU

79

68

66

69

70.5

65

62

59

56.5

53

 

 

 

 

 

 

 

 

 

 

 

PUH-15MYC1-EU

80

69

43

51

59

64

65

64

55

50.5

 

 

 

 

 

 

 

 

 

 

 

PUH-20MYC1-EU

80

69

43

51

59

64.5

65

64

55.5

51.5

 

 

 

 

 

 

 

 

 

 

 

Position mesurement

Indoor unit

 

Outdoor unit

PE(H)

 

PU(H)

 

 

1m

Outlet

Inlet

Service

 

1m panel side

 

 

1m

- 40 -

Image 41
Contents Data Book Contents For correct installation Safety for USEDo not wash the unit with water Outdoor unit Complete Line UPIndoor unit Descriptions FeaturesTypical Installation Example Mechanical Specifications10 M Y C MODEL-DESIGNATION BreakdownPE-7~20MYC Cooling only SpecificationsPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump PE-7~20MYC-EU Electrical DataHeating PEH-5,7,8MYA-EUPEH-10,15,20MYA-EU Model Selection With actual examples Selection ProcedureCalculation of net capacity Efficiency CalculationFactor for Various Air Flow Capacity TablesCooling Capacity Standard Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU Use for low ambient cooling parts PEH-8MYA-EUPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU Combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Cooling Operation RangePEH-5MYA-EU FAN PerformancePE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-20MYC-EU PEH-20MYA-EU PE-15MYC-EU PEH-15MYA-EUPulley outside dimensions are shown below Unit mm Position mesurement Sound DataIndoor units Outdoor unitsPEH-7,8 Outline DimensionsPEH-5 PEH-15 PEH-1028.6 DRAINRc HOLES26Flange HOLES28 PEH-20PUH-7,8,10 Upper blow PUH-5Holes Holes 2-ø15 Ø19.053/4PU-15 PUH-8,10 Side blowØ15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 Cable Entry 44 Holes 2-ø15PUH-15,20 PU-20Ø28.61-1/8 Ø15.885/8 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply PE-7MYC-EU Standard Wiring DiagramsOver current relayfanI/D,O/D PE-8,10MYC-EU StandardInternal thermostat indoor fan PE-15MYC-EU Standard TB1 PE-20MYC-EU StandardPE-7MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fan PE-8,10MYC-EU Special Order Anti Short Cycle TimerPE-15MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor PE-20MYC-EU Special Order Anti Short Cycle TimerPE-7MYC-EU Special Order LOW Ambient Cooling 23C Ambient temperature52F1 Contactor fan I/D 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relays PE-15MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient CoolingAuxiliary relay fanI/D MF2 PEH-5MYA-EU StandardThermostat defrost PEH-7MYA-EU StandardWay valve Option controller connectionCR1 Surge killer PEH-8,10MYA-EU StandardC1~7 PEH-15,20MYA-EU Standard MF2 Cool Heat PEH-8,10MYA-EU CR1 Surge killer Timer Anti short cyclePEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling MF2 Fan motor outdoor PEH-8,10MYA-EU Special Order LOW Ambient Cooling52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26L51F1~5 63H1,2 High-pressure switch 26L1,2PEH-15,20MYA-EU Special Order LOW Ambient Cooling PEH-5MYA-EU, PEH-7,8,10MYA-EU Electrical Operation Flow ChartsPE-7,8,10MYC-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PEH-5,7,8,10,15,20MYA-EU Refrigerant SchematicsPE-7,8,10,15,20MYC-EU PE-7,8,10MYC-EU PE-15,20MYC-EU Safety & Control DevicesPEH-7,8,10MYA-EU Year Service refSpecial Order PE-7,8,1015,20MYC-EU Physical DataIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Outdoor unit InstallationSpace required around unit Indoor unit Over 500 Service-panelCeiling Over Over Service Panel PU-15 At a single installationOver Service-panel 500 Preparation before installing Indoor unitOver Service-panel Outdoor unit Installation of the unit Indoor unitNut Washer Nut M10 WasherLifting method Duct constructionCase of Brazing type Piping connectionPipe assy Valve knobThrow away Fig By-pass tube Flange assy Extension pipe Extension pipe Use the attached new packing FigGood example Bad example Additional refrigerant charge Airtight testEvacuation Drain piping Control module of outdoor unit PUH-5, 8 Electric wiringArrangement such as terminal block in control box Power supply wires Terminal block for connection wiresControl module of outdoor unit PUH-7, 8 Control module of outdoor unit PU-20Method for connecting electric wire 50A Protection switch60A Selection of other capacities should be=4.5mm Flexion loadW 1.4 2.2kg Putting condition of the beltBefore starting the Trial run Check points for operation Instructions for USEOutlet grille Ceiling Ceiling Obstacle blocking air outletFingermarks Neutral Grease MaintenanceAdhesive Isopropyl Paste AlcoholWhen the air conditioner is not to be used for a long time When beginning to use air conditioner againTransfer of installation Transferring work, and constructionMaintenance and inspection Place for installationRegarding electric work Conseration of the noiseAt cooling, water which places to cooling piping Trouble shootingDisplay section HOW to Operate Option PAC-204RCBefore starting operation On / OFF Start an operationRoom temperature adjustment To change room temperature Selecting operation When selecting operationFor fan For coolingDays timer key Time settingTimer Hold/Resume key Clock keyError Display Trouble shootingOutdoor Unit Specification GuidelinesMemo Data Book PE,PEH Mitsubishi Electric Corporation