Mitsubishi Electronics PEH-20MYA, PE-8MYC, PE-15MYC, PE-10MYC, PEH-10MYA PE-20MYC-EU Standard, TB1

Page 52

PE-20MYC-EU (STANDARD)

OUTDOOR UNIT

L1

TB1

 

Power supply, 3 Phase

 

RED

 

RED

 

380~415 Volt, 50Hertz

L2

WHITE

 

 

L3

WHITE

BLACK

 

 

BLACK

NBLUE

PE

RED

WHITE

CIRCUIT BREAKER

 

(FIELD SUPPLY)

BLACK

PU-20MYC1-EU---125A

 

 

F3(3.15A)

 

 

 

 

 

49C1

49C2

 

 

 

 

52

52

 

 

51

C1

C2

 

 

51

 

52

52

F2

F3

 

C1

C2

 

 

 

52C1

51C1

RED

 

 

 

 

 

 

 

 

WHITE

 

MC1

 

 

BLACK

 

 

 

 

 

52C2

51C2

RED

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

MC2

 

 

BLACK

 

 

 

 

 

52F2

51F2

1C1

RED

 

RED

 

2

 

WHITE

 

WHITE

MF2

 

3

BLACK

 

BLACK

 

 

 

 

RED

51F3

1C2

RED

 

 

 

 

 

 

WHITE

 

2

WHITE

MF3

 

3

BLACK

 

BLACK

 

 

 

 

INDOOR UNIT

TB2

L1

Power supply, 3 Phase

L2

380~415 Volt, 50Hertz

L3

 

 

N BLUE

 

PE

CIRCUIT BREAKER (FIELD SUPPLY)

PE-20MYC-EU---30A

 

63H1

 

 

63H2

 

 

 

CH1 CH2

51C1

 

 

51C2

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

30

CZ2-1

CR2

30

CZ2-2

CR3

 

 

CZ1

CZ2

 

 

 

 

 

 

 

 

 

52

 

 

52

2

52

 

 

C1

 

 

C2

F2

 

 

 

 

 

 

30

 

30

 

 

 

 

CZ1

 

CZ2

 

 

 

RED

52F1

 

51F1

 

 

 

 

 

WHITE

 

 

 

MF1

BLACK

 

 

 

 

 

 

 

F1

 

 

 

52F1

(3.15A)

 

GRAY

1

 

 

 

 

 

 

 

TB3

 

51F1

 

 

 

 

C3

 

 

 

 

1

 

 

SWITCH BOX (FIELD SUPPLY)

26L1

 

 

 

F2

 

 

 

 

 

 

C3

 

(3.15A)

 

 

3

Tr

 

 

 

C8

 

 

 

 

 

 

 

1

AC

 

 

 

26L2

 

 

 

220

AC

 

 

C8

 

 

240V

24V

 

 

3

 

 

 

 

23

23 SW1

FZ

 

 

 

 

WA

WA

30

 

 

 

 

TB4

GRAY 11 12

CZ

2-1

CZ 2-2

13

CZ CZ 1-1 1-2

TB3

11 12 OUTDOOR

11 12

CZ

2-1

CZ 2-2

FZ

CR1

 

 

 

52

TB3

2

3

4

 

 

 

F1

 

 

 

 

30

CZ

CZ

 

FZ

FZ

 

1-1

1-2

 

GRAY

5

13

13

Symbol

Name

MC1,2

Compressor motor

MF1

Fan motor (indoor)

MF2,3

Fan motor (outdoor)

52C1,2

Contactor (compressor)

52F1

Contactor (fan I/D)

52F2

Contactor (fan O/D)

TB1 4

Terminal block

CH1,2

Crankcase heater

F1 3

Fuse (3.15A)

Tr

Transformer

49C1,2

Internal thermostat(compressor)

51C1,2

Over current relay(compressor)

51F1,2

Over current relay(fanI/D)

51F2,3

Over current relay(fanO/D)

63H1,2

High-pressure switch

26L1,2

Thermostat (freeze protection)

FZ

Auxiliary relay (fan)

30FZ

Auxiliary relay (fan)

CZ1-1,2/2-1,2

Auxiliary relay

30CZ1,2

Auxiliary relay (check)

<SW1>

Switch (on)

<23WA>

Thermostat (room temp.)

C1~3, 8

Connector

CR1 3

Surge killer

2

Timer

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting. 4.Not specified color of wire is brown. 5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current, Over current relays <51C1,2>, <51F1,2,3> are installed. Therefore, do not change factory set value of Over current relays.

Option controller connection.

Symbol

No.

Function

PAC-204RC (Option)

terminal no.

 

 

 

 

1

Power (Active)

24VAC(L)

TB3

2

Cooling operation

COMP1

3

Cooling operation

COMP2

 

4

Fan operation

FAN HI

 

5

Power (Neutral)

24VAC(N)

- 51 -

Image 52
Contents Data Book Contents Safety for USE For correct installationDo not wash the unit with water Indoor unit Complete Line UPOutdoor unit Features DescriptionsMechanical Specifications Typical Installation ExampleMODEL-DESIGNATION Breakdown 10 M Y CSpecifications PE-7~20MYC Cooling onlyPEH-5,7,8MYA Heat pump PEH-10,15,20MYA Heat pump Electrical Data PE-7~20MYC-EUPEH-5,7,8MYA-EU HeatingPEH-10,15,20MYA-EU Selection Procedure Model Selection With actual examplesEfficiency Calculation Calculation of net capacityCooling Capacity Standard Air Flow Capacity TablesFactor for Various Air Flow Heating Capacity Standard Air Flow PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYC1-EU PEH-8MYA-EU Use for low ambient cooling partsPE-8MYC-EU , PEH-8MYA-EU combined with PUH-8MYE-EU PE-8MYC-EU , PEH-8MYA-EU combined with PUH-8ME-EU Combined with PUH-8MYE-EUPE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYC1-EU PEH-10MYA-EU PE-10MYC-EU , PEH-10MYA-EU combined with PUH-10MYE-EU Combined with PUH-10MYE-EU PE-15MYC-EU 976 PEH-15MYA-EU 989 011 PE-20MYC-EU Use for low ambient cooling parts PEH-20MYA-EU PEH-20MYC-EU AIR Volume CMM Operation Range CoolingFAN Performance PEH-5MYA-EUPE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PE-10MYC-EU PEH-8MYA-EU PEH-10MYA-EUPE-15MYC-EU PEH-15MYA-EU PE-20MYC-EU PEH-20MYA-EUPulley outside dimensions are shown below Unit mm Sound Data Position mesurementIndoor units Outdoor unitsPEH-5 Outline DimensionsPEH-7,8 PEH-10 PEH-1528.6 DRAINRc HOLES26PEH-20 Flange HOLES28PUH-5 PUH-7,8,10 Upper blowHoles Holes 2-ø15 Ø19.053/4PUH-8,10 Side blow PU-15Ø15.885/8130 Refrigerant Pipe PUH-8ø25.41 PUH-10ø28.61-1/8 Cable Entry 44 Holes 2-ø15PU-20 PUH-15,20Ø28.61-1/8 Ø15.885/8 Holes 6-ø15 Control Cable Entry ø27Duct work is local supply Wiring Diagrams PE-7MYC-EU StandardInternal thermostat indoor fan PE-8,10MYC-EU StandardOver current relayfanI/D,O/D PE-15MYC-EU Standard PE-20MYC-EU Standard TB1PE-7MYC-EU Special Order Anti Short Cycle Timer PE-8,10MYC-EU Special Order Anti Short Cycle Timer Internal thermostatindoor fanPE-15MYC-EU Special Order Anti Short Cycle Timer PE-20MYC-EU Special Order Anti Short Cycle Timer Symbol Name MC1,2 Compressor motor23C Ambient temperature PE-7MYC-EU Special Order LOW Ambient Cooling52F1 Contactor fan I/D 49F Internal thermostatfan O/DPE-8,10MYC-EU Special Order LOW Ambient Cooling PE-15MYC-EU Special Order LOW Ambient Cooling Do not change factory set value of Over current relaysAuxiliary relay fanI/D PE-20MYC-EU Special Order LOW Ambient Cooling30FZ Auxiliary relay fanI/D PEH-5MYA-EU Standard MF2PEH-7MYA-EU Standard Thermostat defrostWay valve Option controller connectionC1~7 PEH-8,10MYA-EU StandardCR1 Surge killer PEH-15,20MYA-EU Standard MF2 Cool Heat CR1 Surge killer Timer Anti short cycle PEH-8,10MYA-EUPEH-15,20MYA-EU Special Wiring Anti Short Cycle Timer PEH-7MYA-EU Special Order LOW Ambient Cooling PEH-8,10MYA-EU Special Order LOW Ambient Cooling MF2 Fan motor outdoor52F1 Contactor fan I/D 52F2 Contactor fan O/D 52F4 CR1 Surge killer 21S4 Way valve 26D1 Thermostat defrost 26LPEH-15,20MYA-EU Special Order LOW Ambient Cooling 63H1,2 High-pressure switch 26L1,251F1~5 PE-7,8,10MYC-EU Electrical Operation Flow ChartsPEH-5MYA-EU, PEH-7,8,10MYA-EU PE-15MYC-EU PE-20MYC-EU PEH-15,20MYA-EU PE-7,8,10,15,20MYC-EU Refrigerant SchematicsPEH-5,7,8,10,15,20MYA-EU Safety & Control Devices PE-7,8,10MYC-EU PE-15,20MYC-EUPEH-7,8,10MYA-EU Special Order Service refYear Physical Data PE-7,8,1015,20MYC-EUIndoor AIR Circuit Enclosure and Frame PEH Series PEH-5MYA-EU PE-8MYA-EU JH527YE JH521YE 596X1415 PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU Space required around unit Indoor unit InstallationOutdoor unit Ceiling Over Service-panelOver 500 PU-15 At a single installation Over Service PanelOver Service-panel Preparation before installing Indoor unitOver Service-panel 500 Installation of the unit Indoor unit Outdoor unitNut Washer Nut M10 WasherDuct construction Lifting methodPiping connection Case of Brazing typeValve knob Pipe assyThrow away Fig By-pass tube Flange assy Extension pipe Extension pipe Use the attached new packing FigGood example Bad example Evacuation Airtight testAdditional refrigerant charge Drain piping Arrangement such as terminal block in control box Electric wiringControl module of outdoor unit PUH-5, 8 Terminal block for connection wires Power supply wiresControl module of outdoor unit PUH-7, 8 Control module of outdoor unit PU-20Method for connecting electric wire Protection switch 50A60A Selection of other capacities should beBefore starting the Trial run Putting condition of the belt=4.5mm Flexion loadW 1.4 2.2kg Instructions for USE Check points for operationOutlet grille Ceiling Ceiling Obstacle blocking air outletMaintenance Fingermarks Neutral GreaseAdhesive Isopropyl Paste AlcoholWhen beginning to use air conditioner again When the air conditioner is not to be used for a long timeTransfer of installation Transferring work, and constructionPlace for installation Maintenance and inspectionRegarding electric work Conseration of the noiseTrouble shooting At cooling, water which places to cooling pipingHOW to Operate Option PAC-204RC Display sectionBefore starting operation On / OFF Start an operationSelecting operation When selecting operation Room temperature adjustment To change room temperatureFor fan For coolingTime setting Days timer keyTimer Hold/Resume key Clock keyTrouble shooting Error DisplaySpecification Guidelines Outdoor UnitMemo Mitsubishi Electric Corporation Data Book PE,PEH