Extron electronic XPA2001-100V, XPA2001-70V, XPA1002 manual Removing the IEC Connector

Page 14

100-

 

 

240V

1.3

z

 

A50-

 

 

60H

Remove screws

(both sides) to release IEC connector plate.

Blue Wire Brown Wire

N

L

 

 

Remove nut

Figure 6. Removing the IEC Connector

4.Remove the ground wire nut from the grounding stud on the bottom of the enclosure, as shown above.

5.Remove the 2 screws from the IEC plate, and remove the IEC connector plate and the attached wires through the rear panel of the XPA, as shown above.

6.Thread the 18-gauge power wires through the length of the electrical conduit tube.

7.Install the EMT adapter plate with conduit attached into the opening from which the IEC connector was removed in step 5.

8.Slide the conduit nut over the bundle of wires exiting the conduit and onto the conduit itself. Hand tighten the conduit nut to the conduit.

9.Attach the EMT adapter plate assembly to the XPA using the 2 screws that were removed in step 5.

10.Connect the black hot (line) and white neutral wires to the terminal block on the

PCB using the 2 screws that were removed in step 3. Use the included zip tie wrap to secure the two wires together close to the terminals. See the following illustration.

WARNING: Failure to follow these instructions may result in serious injury. Ensure that you observe correct wire polarity. The following illustration shows the location of the hot (L) and neutral (N) terminals.

Terminal Block

Zip-Tie

 

LINE

L

NEUTRAL

N

Conduit Nut

EMT Adapter Plate

Hot

Terminal (Black)

Neutral Terminal (White)

Ground

Wire Nut

Figure 7. Installing the EMT Adapter Plate Assembly

11.Connect the ground wire, as shown above, to the grounding stud on the bottom of the enclosure using the nut that was removed in step 4.

12.Replace the cover of the XPA by attaching the 8 screws that were removed in step 2.

XTRA Series • Installation

8

Image 14
Contents User Guide Safety Instructions English Specifications Availability FCC Class B NoticePage Contents Page About this Manual FeaturesContinuous power output for larger rooms Terms Used in this ManualXtra Series Introduction Application Examples XPA 1002 Application ExampleUL Guidelines for Rack Mounting Mounting the XPA 1002 and XPATabletop Use Rack Mounting Rack Mounting of the AmplifierFlexible Conduit Adapter Kit Installation Allow Sufficient Spacing for Adequate VentilationUL Requirements Removing the IEC Connector Front Panel Features and Operation Power indicator LED This LED lightsLIMITER/PROTECT Rear Panel Features and Operation Attenuation Inputs RemoteInputsinputs See Remote Volume Control on XPA XPA Do not tin the wires Remote Volume Control Controlling Multiple Amplifiers with One Volume Controller Bridged Mono Output Bridging the Output of the XPAAmplifier Enters Standby Mode Too Early TroubleshootingAmplifier Fails to Exit Standby Mode Promptly LED State Problem Description Problem Solution Limiter/Protect LED Warning IndicatorsOver Temp Indicator LED Included parts Replacement Part number Part Numbers and AccessoriesOptional Accessories Accessories Part numberAsia Middle East USA, Canada, South America Japan Central AmericaEurope and Africa China Europe