C. Control Board
•A Hoshizaki exclusive
•All models are pretested and
CAUTION
1.Fragile, handle very carefully.
2.The control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the unit when handling or replacing the board.
3.Do not touch the electronic devices on the board or the back of the board to prevent damage to the board.
4.Do not attempt to repair the board in the field. Always replace the whole board assembly if it goes bad.
5.Do not short out power supply to test for voltage.
6.Keep the thermistor leads, clogged filter sensor leads, and pressure switch leads at least 1.5" away from high voltage leads (AC 100 volts or more) to protect against electrical noise.
1.Start-Up Delay
The start circuit of the compressor is timed such that at
Note: The compressor must run a minimum of three minutes during each run cycle.
21