Problem | Possible Cause |
| Remedy |
[9] Defrost cycle | a)Defrost Thermistor | 1. Defective. | 1. Replace. |
lasts too long. | b)Control Board | 1. Defective. | 1. Replace. |
| c) Defrost | 1. Not enough defrosts | 1. Factory default is once every |
|
| occurring per day. | 6 hours. If coil is frosting too |
|
| Operation in humid | much, can shorten defrost |
|
| conditions. | interval. |
| d)Defrost Heater | 1. Defective. | 1. Replace heaters. |
| e)Safety Defrost | 1. Defective, turning off | 1. Replace safety defrost |
| Thermostat | heaters prematurely, | thermostat. |
|
| or fused open. |
|
[10]Condensate | a)Cabinet Contents | 1. Loading of large | 1. Cover product with plastic |
water overflow. |
| volumes of warm, | wrap. |
|
| moist, uncovered |
|
|
| product. |
|
| b)Location of Unit | 1. Unit located near high | 1. Relocate. |
|
| humidity source such |
|
|
| as fryer, steamer, etc. |
|
| c) Seals | 1. Poor sealing around | 1. Adjust or replace. |
|
| evaporator, door |
|
|
| gaskets. |
|
| d)Environment | 1. Extreme environment | 1. Adjust conditions. |
|
| and |
|
|
| conditions. |
|
[11]Abnormal Noise | a)Fasteners | 1. Loose fasteners allow | 1. Tighten fasteners. |
|
| vibration of part. |
|
| b)Compressor | 1. Problem with mount. | 1. Properly mount compressor. |
|
|
| Replace any missing |
|
|
| grommets. |
|
| 2. Floodback to | 2. Check for signs of floodback |
|
| compressor. | to compressor. Evacuate and |
|
|
| recharge if necessary. |
|
| 3. Defective. | 3. Replace. |
| c) Fan | 1. Fan blade loose. | 1. Adjust and tighten. |
|
| 2. Defective motor. | 2. Replace. |
| d) Relay | 1. Chattering. | 1. Replace. |
44