Hoshizaki HWR40A(-D), HUR96A(-D), HUR68A(-D) Cabinet Temperature Correction calibration factor

Page 25

c)Cabinet Temperature Correction (calibration factor)

In cases where there is a discrepancy between the actual cabinet center temperature and the displayed temperature for a particular model, a calibration factor is used to correct the displayed temperature.

WARNING

This unit has been factory tested with the default settings listed. Avoid using this function except to confirm that the setting is correct. If set incorrectly, the display could show an acceptable temperature even though the temperature is out of the proper range. This value should only be changed after consulting with the factory.

To view the current value, follow the steps below.

1)Turn the power on while pressing the up button. The current correction calibration factor will be shown. If "18" is displayed, the value is 1.8°F (1.0°C). See the table below for the default values.

Cabinet Temperature Correction (Calibration Factor)

 

Default

 

Model

Setting Range

1-Section

2-Section

3-Section

Refrigerator

 

00 (0.0°F)

36 (3.6°F)

-9.9 to 9.9°F in 0.9°F increments

(00 (0.0°C))

( 20 (2.0°C))

 

Freezer

(-9.5 to 9.5°C in 0.5°C increments)

18 (1.8°F)

45 (4.5°F)

 

 

(10 (1.0°C))

(25 (2.5°C))

 

 

 

 

2)If it is determined through discussion with the factory that the setting needs to be changed, press the up or down button to increase or decrease the value.

3)Press the button to save the new value.

4)Turn the power off and then back on. The unit will start running with the new value.

[Example]

When the average cabinet temperature is 5.4°F (3.0°C) higher than the thermistor detected temperature, change the correction calibration factor to 5.4°F (3.0°C).

25

Image 25
Contents Superior Degree Reliability Energy Star Contents Page Dimensions Specifications Nameplate RatingsUndercounter Model Names HUR40A, HUF40A Units mm 1a. HUR40A-D, HUF40A-D 2a. HWR40A-D, HWF40A-D HWR40A, HWF40A3a. HUR68A-D, HUF68A-D HUR68A, HUF68A4a. HWR68A-D, HWF68A-D HWR68A, HWF68AHUR96A Units mm 5a. HUR96A-D HWR96A Units mm 6a. HWR96A-D Evaporator Case II. General Information ConstructionRefrigerators Continuous Operating Mode Sequence of Operation and Timing ChartsSequence of Operation Operating Timing ChartFreezers Continuous Operating Mode Freezers Continuous Defrost End Defrost thermistor reaches defrost Refrigerators Energy Saving Operating ModeEnergy Board Self Check Minute Delay Freezers Energy Saving Operating ModeFreezers Energy Control Board Start-Up DelayThermistor Wiring Harness K151 Relay Wiring Harness K311Rear FrontGaining Access to Settings and Diagnostics Settings and DiagnosticsSwitching the Display Between Fahrenheit and Celsius F5 Temperature DisplayAdjusting the Setpoint Temperature Cabinet Temperature Correction calibration factor Later Section Settings and Diagnostics MenuDefrost Interval F0 Defrost Termination Temperature F1Setpoint Temperature Differential F2 Low Temperature Alarm Delay Time F4 High Temperature Alarm Delay Time F3Alarm History F6 Temperature Display Scale F5Operating Modes Compressor Run Time F7Continuous Perimeter Frame HeaterEnergy Saving Alarm Signals Alarm Code Problem III. Service Diagnosis Alarm CodesError Code Priority Description Alarm Display PriorityHigh Temperature Alarm E1 Alarm Details and CountermeasuresReset Options Possible CausesLow Temperature Alarm E2 High Pressure Alarm E4 Defrost Alarm E3Clogged Filter Alarm E7 Defrost Temperature Sensor Malfunction Alarm E8 Clogged Filter Sensor Malfunction Alarm E9 Control Board Error Alarms EA and ED Problem Possible Cause Remedy Diagnosis ChartProblem Possible Cause Remedy Problem Possible Cause Remedy Thermistor Check Service for Refrigerant Lines IV. Removal and Replacement of ComponentsRefrigerant Recovery BrazingEvacuation and Recharge Removal and Replacement of Compressor Removal and Replacement of Refrigeration UnitRemoval and Replacement of Evaporator Page Page Cabinet Thermistor Removal and Replacement of ThermistorsDefrost Thermistor Clogged Filter Thermistor sensorRemoval and Replacement of Defrost Heater Removal and Replacement of Door GasketRemoval and Replacement of Control Board Door Re-Hinging and Drawer Conversion Removal and Replacement of Fan MotorsCondenser Fan Motor Evaporator Fan MotorCleaning Cleaning and Maintenance InstructionsAir Filter MaintenanceShelves Drawers115/60/1 A2. HUR40A-D, HWR40A-D auxiliary code Q6 and later HUF40A-D, HWF40A-D C1. HUR68A, HWR68A auxiliary code Q5 and earlier C2. HUR68A-D, HWR68A-D auxiliary code Q6 and later HUF68A-D, HWF68A-D HUR96A-D, HWR96A-D