ET temperature is recorded 30 seconds after PM energizes. Water temperature correction value (CB Setting 13) is added to ET temperature and this is used as WT value in following harvest cycle.
If CBT>81°F (27°C) (CB Setting 74) and CBT≤111°F (44°C) (CB Setting 70), when
CB monitors time after ET temperature≤32°F (0°C). CB terminates freeze cycle when the following equation is satisfied:
temp. (absolute value) × time (min.) = (absolute value of CB Setting 2) × (CB Setting 3)
Using default settings, freeze cycle is terminated when: temp. (absolute value) × time (min.) = 185
This formula helps maintain consistent dimple size regardless of differences in seasonal ambient and water temperatures.
4. Shutdown
When BC is engaged (open) for more than 10 seconds, the icemaker shuts down after harvest cycle.
When BC is disengaged (closed) for more than 80 seconds, icemaker restarts at startup cycle.
If BC is engaged (open) while the water tank is opening after the power supply is turned on (or after the "RESET" button is pressed), shutdown does not start: Shutdown occurs 10 seconds after actuator motor's internal position sensor indicates water tank is fully open.