CPSM | CCS – Cellar |
Mode | between 45°f - 67°f. |
(Cont.) |
|
| bLL/Act – Compressor Off or On for Low (bLL) or High (Act) Temperature Alarm: These parameters |
| are set at “n”. With this parameter set at “n” the refrigeration system will continue to operate nor- |
| mally, if there is a High or Low temperature Alarm. To change this parameter, change the setting to |
| “y”, and the compressor/refrigeration system will shut off during a High or Low temperature Alarm. |
| Con/Cof – Compressor On time (Con) and Off time (Cof) with a Probe 1 failure/Alarm. These pa- |
| rameters are set at Con 40 min/Cof 10 min. In the event that there is a Probe 1 failure/Alarm, the |
| compressor/refrigeration system automatically starts a predetermined ON/OFF cycle, which is con- |
| trolled by the Con and the Cof parameters. The customer can adjust these parameters to maintain |
| the desired Bottle Probe temperature. During a Probe 1 failure/Alarm, the Bottle Probe tempera- |
| ture can be monitored by pressing the Up or Down arrow to view the High and Low Temperature |
| History. |
| Hes – Differential for Energy Reduction – This parameter is set at 4, which results in a set point of |
| 52°f during the Energy Reduction mode. A decrease in this setting will decrease the set point, and |
| an increase in this feature will increase the set point. |
AUX | “AUX” indicates that the condenser fan is running. Pressing the “AUX” button on the control panel |
| will turn it off. |
|
|
|
| Alarm Codes | |
|
|
|
|
Message | Cause |
| Outputs |
“P1” | Room probe failure |
| Toggle “Con” and “COF” based on your temperature needs |
“P2” | Evaporator probe failure |
| Defrost end is timed |
“P3” | Condenser probe failure |
| Outputs unchanged |
“HA” | Max bottle probe temp alarm |
| Outputs unchanged |
“LA” | Min bottle probe temp alarm |
| Outputs unchanged |
“HA2” | Condenser high temperature |
| It depends on the “Ac2” parameter |
“LA2” | Condenser low temperature |
| It depends on the “bLL” parameter |
“EA” | External alarm |
| Outputs unchanged |
“POF” | Keypad locked |
| Hold “Up” and “Down” buttons for 3 to 5 seconds to disable, |
|
|
| “PON” should appear |